Operating Instructions Edition 12/2003
Transmitter for pressure, differential pressure
and flow, filling level,
absolute pressure from differential pressure
7MF4*34-...
I
SIEMENS
EFTA01216716
EFTA01216717
SIEMENS
SITRANS P, DS III PA series
7MF4*34-...
Edition 12/2003
Operating Instructions
Transmitters for Pressure, Differential Pressure and Flow, Filling Level
Absolute pressure from differential pressure series and absolute pressure from
pressure series, DS III series with PROFIBUS-PA
Edition of
operating
manual
Firmware identification
License plate
System integration
Installation path
PDM
02
FW: 300.01.03
FW: 300.01.04
FW: 300.01.05
FW: 300.01.06
PDM V.5.02 + SP1:
Dev. R.1/2
SITRANS P DSIII
03
FW: 300.01.07
PDM V.5.02 + SP1;
Dev. R.1/2
SITRANS P DSIII
04
FW: 300.01.07
PDM V.5.02 + SP1;
Dev. R.1/2
SITRANS P DSIII
Table 1
History of this instruction manual
SITRANS P. DS III PA series
A5E00053276-04
1
EFTA01216718
SITRANS P. DS III PA series
2
ASE00053276-04
EFTA01216719
Table of contents
Classification of Safety—Related Notices
7
General Notes
8
Technical description
11
1.1
Application range
11
1.2
Product features
11
1.3
Measuring type
12
1.3.1
Pressure
12
1.3.2
Differential pressure and flow
12
1.3.3
Filling level
12
1.3.4
Absolute pressure
13
1.4
Design and functional principle
13
1.4.1
Design
13
1.4.2
Mode of operation
16
1.4.2.1 Mode of operation of the electronics
16
1.4.2.2
Pressure
18
1.4.2.3
Differential pressure and flow
18
1.4.2.4
Filling level
19
1.4.2.5
Absolute pressure from the differential pressure series
19
1.4.2.6
Absolute pressure from the pressure series
20
2
Communication structure for PROFIBUS PA
21
2.1
Block model for recording and processing measured values
21
2.1.1
Pressure measuring block
22
2.1.2
Electronics temperature measuring block
22
2.1.3
Analog input function block
22
2.1.4
Counter function block
22
2.1.5
Local operation and display
22
2.1.6
Connection between the blocks using parameters
23
2.1.7
Parameters for measured value display
23
2.2
Description of individual blocks
24
2.2.1
Pressure measuring block (Transducer Block 1)
24
SITRANS P. Series DS III PA
ASE00053276-04
3
EFTA01216720
2.2.1.1
Type of linearization function group
25
2.2.1.2
Units for the pressure measuring block
28
2.2.2
Electronics temperature measuring block
28
2.2.3
Analog input function block
29
2.2.4
Counter function block
30
3
System integration
33
3.1
Cyclic data transmission
33
3.1.1
Setting the PROFIBUS address
33
3.1.2
Configuration
33
3.1.2.1 Configuring the user data
34
3.1.2.2
Transmission of user data via PROFIBUS
35
3.1.2.3
Status
36
3.1.2.4
Diagnosis
39
3.2
Acyclic Data Transmission
41
3.3
SIMATIC PDM
41
4
Local operation and display
43
4.1
General operating instructions
43
4.1.1
Digital display
43
4.1.2
Measured value display
44
4.1.3
Unit display
44
4.1.4
Error signaling
44
4.1.5
Mode display
45
4.2
Operation with the keyboard
45
4.2.1
Measured value display
47
4.2.2
Error display
47
4.2.3
Mode 4: Electric damping
48
4.2.4
Mode 7: Zero point adjustment (position error correction)
48
4.2.5
Mode 10: Key lock
49
4.2.6
Mode 13: Source of measured value display
49
4.2.7
Mode 14: Physical unit
51
4.2.8
Mode 15: PROFIBUS address
54
4.2.9
Mode 16: Device operating mode
54
4.2.10
Mode 17: Position of the decimal point
55
4.2.11
Mode 18: Zero point adjustment display
55
4.2.12
Mode 19: LO adjustment
56
4.2.13
Mode 20: HI adjustment
57
5
Functions/Operation via PROFIBUS-PA
59
5.1
Measuring operation
59
5.2
Settings
59
5.2.1
Pressure measurement
60
5.2.2
Filling level (level, volume and mass) measurement
60
5.2.2.1 Level measurement
60
5.2.2.2
Volume measurement
61
5.2.2.3
Mass measurement
62
5.2.3
Flow measurement
63
5.2.3.1
Application point for the root function, creep quantity suppression
64
4
SITRANS P. Series DS III PA
A5E00053276-04
EFTA01216721
5.2.3.2
Flow measurement correction
65
5.2.4
Adjustment to the desired process variable
65
5.2.5
Electric damping
67
5.2.6
Warning and alarm limits
67
5.2.7
Fault Behavior
69
5.2.7.1 Output
69
5.2.7.2
Counter output
69
5.2.8
Simulation
70
5.2.8.1 Output simulation
70
5.2.8.2
Input simulation
70
5.2.8.3 Pressure sensor simulation
71
5.2.8.4
Simulation of the sensor and electronics temperature
72
5.2.9
Calibration interval and service interval
72
5.2.9.1
Warning
73
5.2.9.2
Alarm
73
5.2.10
Slave pointers
73
5.2.11
Operating hours counter
74
5.2.12
Sensor adjustment
75
5.2.13
Positional error adjustment
76
5.2.14
Resetting
76
5.2.14.1 Resetting to delivery status
76
5.2.14.2 Restart (warm start)
76
5.2.14.3 Resetting the PROFIBUS address to 126
77
5.2.15
Operator input inhibits
77
6
Modular design
79
7
Installation
81
7.1
Installation (except filling level)
82
7.1.1
Mounting without mounting bracket
83
7.1.2
Mounting with mounting bracket
83
7.2
Mounting "filling lever
85
7.2.1
Installation
85
7.2.2
Connecting the low pressure line
85
7.3
Rotating the measuring cell in relation to the housing
87
7.4
Electrical Connection
89
7.4.1
Connection to screw terminals
90
7.4.2
Connection with plug M12
91
7.5
Turn digital display
93
8
Commissioning
95
8.1
Pressure, absolute pressure from the differential pressure series and absolute pressure
from the pressure series 96
8.1.1
Measuring gases
97
8.1.2
Measuring vapor and liquid
98
8.2
Differential pressure and flow
99
8.2.1
Measuring gases
99
8.2.2
Measuring liquids
100
8.2.3
Measuring vapor
102
SITRANS P. Series DS III PA
ASE00053276-04
5
EFTA01216722
9
Technical data
103
9.1
Nominal measuring ranges and overload limits
108
9.1.1
Pressure
108
9.1.2
Differential pressure and flow
108
9.1.3
Absolute pressure from the pressure series
109
9.1.4
Absolute pressure from the differential pressure series
109
9.1.5
Filling level
110
9.2
Dimensions
110
10
Care and maintenance
115
11
PROFIBUS
117
11.1
Transmission method
117
11.2
Topology
117
11.3
Properties of the PROFIBUS PA
119
11.3.1
Profile
119
11.3.2
Interfacing
120
12
Ordering Data
123
12.1
Ordering data for basic device
124
12.2
Ordering data for spare parts
131
12.3
Ordering data for accessories
135
13
Certificates
137
14
Index
139
15
139
16
Appendix
141
16.1
Literature and catalogs
141
16.2
Summary of error messages and status codes
142
16.3
Certificates
146
6
SITRANS P. Series DS III PA
A5E00053276-04
EFTA01216723
Classification of safety—related notices
This manual contains notices which you should observe to ensure your own personal
safety, as well as to protect the product and connected equipment. These notices are
highlighted in the manual by a warning triangle and are marked as follows according
to the level of danger:
rTe
DANGER
indicates an immenently hazardous situation which, if not avoided, will result in
death or serious inury.
WARNING
iindicates a potentially hazardous situation which, if not avoided, could result in
death or serious injury.
CAUTION
used with the safety alert symbol indicates a potentially hazardous situation which,
if not avoided, may result in minor or moderate injury.
CAUTION
used without the safety alert symbol indicates a potentially hazardous situation
which, if not avoided, may result in property damage.
NOTICE
indicates a potential situation which, if not avoided, may result in an undesirable
result or state.
NOTE
ihighlights important information on the product, using the product, or part of the
documentation that is of particular importance and that will be of benefit to the
user.
Copyright
Siemens AG 2001 All rights reserved
The reproduction. transmission or use of this document
or its contents is not permitted without express written
authority. Offenders will be liable for damages. All rights,
including rights created by patent grant or registration of
a utility model or design, are reserved.
Siemens AG
Bereich Automatisiwungs- and Antriebstechnik
Geschaftsgebiet Process Instrumentation
0-76161 Karlsruhe
SITFtANS P. Series OS III PA
A5E00053276-03
Disclaimer of Liability
We have checked the contents of this manual for agreement
with the hardware and software described. Since deviations
cannot be precluded entirely. we cannot guarantee full
agreement. However. the data in this manual are reviewed
regularly and any necessary corrections included in
subsequent editions. Suggestions for improvement are
welcomed.
Siemens AG 2001
Technical data subject to change.
7
EFTA01216724
General notes
This device has left the factory in a perfect condition as regards safety. The notes
and warnings in these Operating Instructions must be observed by the user if this
state is to be maintained and hazard-free operation of the device assured.
NOTE
Dear customer,
You have purchased a modular device in which you can exchange the electronics.
In the event of an exchange, please observe the instructions enclosed with the
component to be exchanged.
For reasons of clarity the manual does not contain detailed information about all
types of products and cannot take into account every conceivable case of
installation, operation or maintenance.
If you require further information or should problems occur which are not
sufficiently explained in the manual, you can consult your local Siemens branch to
obtain the necessary information.
May we also draw your attention to the fact that the contents of the manual are not
part of a previous or existing agreement, approval or legal relationship or an
amendment thereof. All obligations of the Siemens AG result from the contract of
purchase which also contains the full and solely valid warranty agreement. These
contractual warranty conditions are neither extended nor restricted by the contents
of the manual.
The contents reflect the technical state at the time of going to print. Subject to
technical modifications in the course of further development.
WARNING
Explosion-proof devices may only be opened when the power is off.
Intrinsically safe devices lose their license as soon as they are operated on circuits
which do not meet the test requirements valid in your country.
The device may be operated with high pressure and corrosive and dangerous
media. Therefore serious injuries and/or considerable material damage cannot be
ruled out in the event of improper handling of the device.
The perfect and safe operation of this equipment is conditional upon proper trans-
port, proper storage, installation and assembly as well as on careful operation and
commissioning.
The equipment may only be used for the purposes specified in the instruction
manual.
Excluded Liability
The user is responsible for all changes made on the device, provided that these are
not explicitly mentioned in the instruction manual.
SITRANS P. Series DS III PA
8
A5E00053276-03
EFTA01216725
Qualified Personnel
are persons familiar with the installation, assembly, commisioning and operation of
the product and who have the appropriate qualifications for their activities such as:
•
training or instruction or authorization to operate and maintain devices/systems
according to the standard of safety technology for elecrical circuits, high
pressures and corrosive as well as hazardous media.
•
for devices with explosion protection: training or instruction or authorization to be
allowed to work on electrical circuits for potentially explosive systems.
•
training or instruction according to the standards of safety engineering in the care
and use of suitable safety equipment.
CAUTION
Modules which are sensitive to electrostatic charge may be destroyed by voltages
which are far below the human level of perception. These voltages occur already
when you touch a component or electrical connections of a module without first
discharging yourself electrostatically. The damage incurred by a module as a
result of an overvoltage is not usually immediately perceptible but only becomes
noticeable after a long time in operation. Therefore, a suitable equipotential
bonding must be guaranteed when repairing the device.
Trademarks
SIMATIC®, SIPART®, SIREC®, SITRANS® are registered trademarks of
Siemens AG.
Third parties using for their own purposes any other names in this document which
refer to trademarks might infringe upon the rights of the trademark owners.
SITRANS P. Series OS III PA
A5E00053276-03
9
EFTA01216726
SITRANS P. Series DS III PA
10
A5E00053276-03
EFTA01216727
Technical description
IIr
The transmitter must warm up for about 5 minutes after switching on the power in
order to obtain stable measured values.
I
NOTE
1.1
Application range
The SITRANS P, Series DS III PA transmitter measures the pressure of non-
corrosive and corrosive as well as critical gases, vapors and liquids. You can use it
in the following applications
• Pressure
• Differential pressure
•
Level
•
Volume
•
Volume flow
•
Mass flow rate
The transmitters are available with different designs of pressure-transmitting seals
for special applications, e.g. measuring highly viscous substances.
The device can be operated as a stand-alone unit or using its PROFIBUS interface.
1.2
Product features
•
Transmitter with bus connection according to IEC 61158-2 and EN 50170
•
Transmitter designs with intrinsic safety against explosion can be installed in
SITRANS P. Series OS III PA
A5E00053276-04
11
EFTA01216728
Technical description
areas where there is an explosion hazard.
•
The certificate of conformity meets the European rules (CENELEC).
• Data transmission and auxiliary power (9 to 32 V) via bus connection together
• Bus connection independent of polarity and fixed bus current limiting in the event
of an error
•
Contact separation (test voltage 500 V AC)
•
Intrinsically-safe and flameproof version for use in explosion protected area (Ex-
area)
•
Can communicate through PROFIBUS-PA (profile version 3.0, Class B);
•
The transmitter can be parameterized locally using three buttons or externally via
SIMATIC PDM.
1.3
Measuring type
1.3.1
Pressure
This version of the device measures the pressure of non-corrosive and corrosive as
well as critical gases, vapors and liquids. Can be operated with measuring cells from
1 to 400 bar.
1.3.2
Differential pressure and flow
This version of the device is used to measure
•
the differential pressure, e.g. the active pressure,
•
of a small positive or negative excess pressure,
•
of the flow q
1670 (together with a flow control valve)
non-corrosive and corrosive and ciritical gases, vapors and liquids. Can be operated
with measuring cells from 20 mbar to 30 bar
1.3.3
Filling level
This version of the device with mounting flange measures the filling level of non-
corrosive and corrosive as well as critical liquids in open and closed containers. Can
be operated with measuring cells from 250 mbar to 5 bar The nominal width of the
mounting flange is DN 80 or DN 100 or 3 or 4 inch.
In the filling level measurement on an open container the low pressure connection of
the measuring cell remains open (measurement "compared to atmospheric"), in the
measurement on a closed container this connection is usually connected to the
vessel to compensate the static pressure.
SITRANS P. Series DS III PA
12
ASE00053276-04
EFTA01216729
Technical description
The wetted parts are made of different materials (see chapter 9, pg. 103) according
to the required corrosion resistance.
1.3.4
Absolute pressure
This version of the device measures the absolute pressure of non-corrosive and
corrosive as well as critical gases, vapors and liquids.
There are two series: one "differential pressure" series and one "pressure" series.
The "differential pressure series' is characterized by a high overload capacity.
Can be operated with measuring cells from 250 mbar to 30 bar
1.4
Design and functional principle
1.4.1
Design
The device consists of different components depending on what the customer has
specified in the order. The possible variants are listed in chapter 12, pg. 123.
The rating plate (Figure 1, pg. 13 and Figure 4, pg. 15) with the order number is on
the side of the housing. You can determine the optional constructional details and the
possible measuring range (physical properties of the built-in sensor element) with the
specified number and specifications in chapter 12, pg. 123.
1 Order number
2 Serial number
•
SIEMENS
0.76101 Karlsruhe
•
SITRANS P
PED:SEP
( 0032
Transmitter for pressure
7MF0034-1EB10-1DA1
Fab. Nr. N1 LN11-004711
Us:DC 9-321/ (no, inlr.savel PROF IBUS-PA
Mat.:Connoc. Dianne.
Filling
1.4404
2 4819
Silikon61
Measuring span
Overrange limits
: -63 bar
: -1 - 100 bar
oleetiOniPe$
Figure 1
Example for a rating plate
SITRANS P. Series OS III PA
A5E00053276-04
13
EFTA01216730
Technical description
Opposite it is the license plate (Figure 2, pg. 14 and Figure 4, pg. 15). This contains
information about the hardware and firmware versions among other thing.
•
SIEMENS
0.76131 Kadsruha
•
SITRANS P
'1102 G GEN d NC 7.1/70
U.:DC S 32V
I PRODOUS.PA)
FIBSOKIEX 1160
Observe EC rod ExaminMIonConiIoaoI
•
..85,60°G
FVt. 0300.01.01 ION: 02.01 01
•
FW: )OOOCYY.ZZ
FM: XX.YY.ZZ
I
I
I
I I L — — Compatibility identifier
I
I I
I
L
-
-
- Terminal board product status
L
-
-
— Serial number
I
I I _
— FW edition
— Function range identifier
Profile revision (0300 = 3.00)
Figure 2
Example of approval plate
The electronics housing is made of diecast aluminum or stainless steel precision
casting. There is an unscrewable, round cover on the front and rear. The front cover
(4, Figure 3, pg. 15) can be designed as a window in order to be able to read
measured values directly from the digital display. The inlet (2, Figure 3, pg. 15) to the
electrical connection box is located on the side, either left or right. The opening which
is not used is sealed by a blanking plug (e.g. 5, Figure 4, pg. 15). The PE conductor
terminal (2, Figure 4, pg. 15) is mounted at the front of the housing.
The electrical connection box is accessible for power supply and screen when
the rear cover (1, Figure 4, pg. 15) is removed. The bottom part of the housing
contains the measuring cell with process connection (8, Figure 3, pg. 15). This is
secured turning by a locking screw (7, Figure 3, pg. 15). The modular concept of the
SITRANS P, Series DS III PA allows the measuring cell and electronics to be
exchanged as required.
At the top of the housing you can see a plastic cover (3, Figure 3, pg. 15) which can
be opened. The input keyboard is beneath this.
14
SITRANS P. Series DS III PA
A5E00053276-04
EFTA01216731
Technical description
Figure 4
Rear view of device SITRANS P. Series DS III PA. pressure series
Figure 3
Front view of device SITRANS P, Series DS III PA, pressure series
Rating plate
Inlet with cable gland
Plastic access cover to the input keys
Screwable cover, optional with window
Digital display
Measuring point plate
Locking screw
Process connection
Unscrewable cover for
access to electrical
connection box
PE conductor connection
Alternative measuring
point plate
License plate
Blanking plug
SITRANS P. Series DS III PA
A5E00053276-04
15
EFTA01216732
Technical description
1.4.2
Mode of operation
This chapter describes how the transmitter operates and what protection and safety
measures you need to observe. First of all the electronics are described on a
Funktionsplanebene (functional level), then the sensors used for the individual
measuring modes in the various versions of the device.
The process variable to be measured is referred to generally in the following sections
as the input variable.
1.4.2.1 Mode of operation of the electronics
The input variable provided by the sensor (1, Figure 5) is amplified by an instrument
amplifier (2) and converted into a digital signal via an analog-digital converter (3).
This is evaluated in a microprocessor (4), its linearity and temperature behavior cor-
rected and made available using the isolated interface (5) on the PROFIBUS-PA (7).
The measuring cell-specific data of the electronics and the data for transmitter
parameterization are stored in two non-volatile memories (6).
You can parameterize the transmitter directly at the measuring point with the three
input keys (8) and view measuring results, error messages and modes of operation
on the digital display (9), which is securely screwed onto the device. You can get the
measuring results with status values and diagnosis using the PROFIBUS-PA's
cyclical data transmission (see chapter 3.1, pg. 33). Using the acyclical data
transmission (see chapter 3.2, pg. 41), you carry out the parameterization and can
view all results and error messages. To do this, you require a tool, for example the
SIMATIC PDM.
SITRANS P. Series DS III PA
16
ASE00053276-04
EFTA01216733
Technical description
OOO
IIIIIIIIIII
111,1 1,11,1 1,1 1
0 0 -
Liu
7
Power supply
10
1 Sensor of the measuring cell
2 Instrument ampii er
3 Analog-digital converter*
4 Microcontroller
5 Isolation
6 two non-volatile memories in the measuring cell and in the electronics
7 Proflbus-PA interface
8 three input keys (local operation)
9 Digital display
10 Auxiliary power source
11 DP/PA coupler or link
12 Bus master
Figure 5
Transmitter SITRANS P, Series DS III PA, electronics
SITRANS P. Series DS III PA
A5E00053276-04
17
EFTA01216734
Technical description
Figure 6
Pressure measuring cell, functional diagram
1.4.2.2 Pressure
The pressure pe is fed in through the process connection (3, Figure 6, pg. 18) of the
measuring cell (2). It is passed further through the seal diaphragm (4) and the filling
liquid (5) to the silicon pressure sensor (6) and its measuring diaphragm flexes as a
result Four piezo-resistors in bridge circuit doped in the measuring diaphragm
change their resistance as a result. The change in resistance causes a bridge output
voltage proportional to the input pressure.
The transmitters with measuring spans 5 63 bar measure the input pressure
compared with atmospheric, those with measuring spans z 160 bar compared with a
vaccum.
CAUTION
If the measuring signal fails due to a sensor break, the isolating diaphragms may
also be destroyed. In this case,process medium may leak from the threaded collar
of the device in pressure transmitters with relative pressure cell (5 63 bar).
Reference pressure
Measuring cell
Process connection
Seal diaphragm
Filling liquid
Silicon pressure sensor
Input variable pressure
1.4.2.3 Differential pressure and flow
The differential pressure is transmitted via the seal diaphragms (7, Figure 7, pg. 19)
and the filling liquid to the silicon pressure sensor (5). On exceeding the measuring
limits, the overload diaphragm (6) flexes until one of the seal diaphragms (7) comes
into contact with the body of the measuring cell (4) and protects the silicon pressure
sensor (5) against overloading. The seal diaphragm is deflected by the resulting
differential pressure. Four piezo-resistors in bridge circuit doped in the measuring
diaphragm change their resistance as a result. The change in resistance causes a
bridge output voltage proportional to the differential pressure.
18
SITRANS P. Series DS III PA
A5E00053276-04
EFTA01216735
Technical description
Input pressure P,
Process flange
O-ring
Body of the measuring cell
Silicon pressure sensor
Overload diaphragm
Seal diaphragm
Filling liquid
Input pressure P_
Figure 7
Measuring cell for differential pressure and flow, functional diagram
1.4.2.4 Filling level
The input pressure (hydrostatic pressure) acts through the seal diaphragm (10,
Figure 8, pg. 19) at the mounting flange hydraulically on the measuring cell. The
differential pressure applied at the measuring cell is transmitted via the seal
diaphragms (6) and the filling liquid (7) to the silicon pressure sensor (3). On
exceeding the measuring limits, the overload diaphragm (5) is deflected until one of
the seal diaphragms (6) comes into contact with the body of the measuring cell (4)
and protects the silicon pressure sensor (3) against overloading. The measuring
diaphragm is flexed by the differential pressure. Four piezo-resistors in bridge circuit
doped in the measuring diaphragm change their resistance as a result. The change
in resistance causes a bridge output voltage proportional to the differential pressure.
Process flange
2 O-ring
3
Silicon pressure sensor
4
Body of the measuring cell
5
Overload diaphragm
6
Seal diaphragm at the measuring cell
7
Filling liquid of the measuring cell
8
Capillary tube with filling liquid of the
mounting flange
9 Flange with tube
10 Seal diaphragm at the mounting flange
Figure 8
Measuring cell for filling level, functional diagram
1.4.2.5 Absolute pressure from the differential pressure series
The absolute pressure is transmitted via the seal diaphragm (6, Figure 9, pg. 20) and
the filling liquid (7) to the silicon pressure sensor (3). On exceeding the measuring
limits, the overload diaphragm (5) is deflected until the seal diaphragm (6) comes into
contact with the body of the measuring cell (4) and protects the silicon pressure
sensor (3) against overloading. The pressure difference between the input pressure
(pe) and the reference pressure (8) on the low pressure side of the measuring cell
flexes the measuring diaphragm. Four piezo-resistors in bridge circuit doped in the
measuring diaphragm change their resistance as a result. The change in resistance
causes a bridge output voltage proportional to the absolute pressure.
SITRANS P. Series DS Ill PA
ASE00053276-04
19
EFTA01216736
Technical description
Process flange
Seal diaphragm at the measuring cell
O-ring
Body of the measuring cell
Silicon pressure sensor
Overload diaphragm
Filling liquid of the measuring cell
Reference pressure
Input variable pressure
Figure 9
Measuring cell for absolute pressure, functional diagram
1.4.2.6 Absolute pressure from the pressure series
The pressure is transmitted via the seal diaphragm (3, Figure 10, pg. 20) and the
filling liquid (4) to the absolute pressure sensor (5) and flexes its measuring
diaphragm. Four piezo-resistors in bridge circuit doped in the measuring diaphragm
change their resistance as a result. The change in resistance causes a bridge output
voltage proportional to the input pressure.
Measuring cell
Pressure connection
Seal diaphragm
Oil filling
Absolute pressure sensor
Input variable pressure
20
Figure 10 Measuring cell for absolute pressure from pressure series, functional diagram
SITRANS P, Swiss DS III PA
ASE00053276-04
EFTA01216737
Sensor
Communication structure for
PROFIBUS PA
2
This chapter describes the mode of operation of the device-specific function blocks
with the aid of a graphic block model, which is broken up sequentially into its
individual levels. Knowledge of the physical block is assumed: Therefore it is not
described in this chapter.
2.1
Block model for recording and processing measured
values
The functions of the device are divided into blocks for different areas or responsibility
(Figure 11). They can be parameterized by acyclic data transfer (see chapter 3.2,
pg. 41).
T
Pressure measuring
block, absolute pres-
sure, differential pres-
sure,
also filling level, flow and
Measuring block for
electronics temperature
_II
Analog input
function block
Counter function
block:
Local operation
.- - and display
PROFIBUS•
Figure 11
Block connection diagram for recording and processing measured values
SITFtANS P. Series OS III PA
A5E00053276-04
21
EFTA01216738
Communication structure for PROFIBUS PA
2.1.1
Pressure measuring block
The pressure measuring block (Figure 11) carries out adjustments to the sensor. Its
initial value is the linearized and temperature-compensated measuring result. For
measurement of the filling level and flow, the required conversions take place here.
An example is the conversion of an input pressure into level or volume for hydrostatic
filling level measurement.
The pressure sensor temperature measurement is also processed here and the
pressure and temperature limits are constantly monitored.
2.1.2
Electronics temperature measuring block
The electronics temperature measuring block (Figure 11) carries out the required
temperature measurement functions and monitors the permitted temperature limits.
2.1.3
Analog input function block
In the analog input function block (Figure 11), the selected measured value is
processed further and is adjusted to the automation task.
Example: For a flow measurement, the volume flow needs to be converted into the
number of containers filled. The output of this block supplies the measured value and
the associated status information to the PROFIBUS.
2.1.4
Counter function block
For flow measurement, the volume or mass which has flowed through can be totalled
in the counter function block (Figure 11). Its function, therefore, is very similar to that
of a water clock. The output of this block supplies the total values and the associated
status information to the PROFIBUS.
2.1.5
Local operation and display
With local operation (Figure 11), the desired measured value can be set and
displayed with its physical unit.
SITRANS P. Series DS III PA
22
ASE00053276-04
EFTA01216739
Communication structure for PROFIBUS PA
2.1.6
Connection between the blocks using parameters
The output values of the pressure and electronics temperature measuring blocks can
be fed into the analog input and counter function blocks as input values for further
processing. For this, the parameter "Channel" must be set accordingly in the relevant
function block.
Measuring block
Output value
(Parameter)
Usable in analog
input function
block
Usable in
counter function
block
Pressure
Temperature
X
Secondary variable 1
X
Secondary variable 2
X
Primary variable
X
X
Secondary variable 3
X
X
Electronics
temperature
Electronics
temperature
X
Table 2
Connection between the blocks
2.1.7
Parameters for measured value display
The values of the following parameters from the measuring and function blocks can
be presented on the digital display For this, the parameter -Source for the display"
must be set accordingly (see chap er 4.2.6, pg. 49).
Block
Parameter
Can be presented on
the digital display
Pressure measuring block
Temperature
X
Secondary variable 1
X
Secondary variable 2
Primary variable
X
Secondary variable 3
X
Non-linearized
pressure value
X
Electronics temperature
measuring block
Electronics
temperature
X
Analog input function block
Output
X
Counter function block:
Counter output
X
Table 3
SITRANS P. Series DS 111 PA
A5E00053276-04
Display on the digital display
23
EFTA01216740
Communication structure for PROFIBUS PA
2.2
Description of individual blocks
2.2.1
Pressure measuring block (Transducer Block 1)
Figure 12 shows the signal flow of measured values from the measuring cell through
the pressure measuring block (which also processes filling level, flow and sensor
temperature) into the respective output values (temperature, measured value
(primary variable) etc.). The parameters of the individual functions (measuring range,
output range etc.) can be changed via acyclic access.
Parameters vla acydical access
I
l
measiming
cell
a
c
S
8.E.E
i
! 'd
E
Ileeics
g
Of
C
>
e
ea
CC
r
oal
g
2
co ,
CO
0202MCe
1.
e.a
t
5
. t2,- .
CIS
P
13,2 S
2 a
, •
i
a
.
13`35 3.
Ng.
21
i
§
0
s a ,
E.
e
il
1
r,
a
e
g
a
a
a
e
li
e
.11
2
x
b
i;
3
.
..i
C
q
1 I
E s
l 3
I
2 a
81
21
c.
P
Calbra-
fit=
Normal-
0 1 Linea-
swing
It
ton
(Posnon
error cotton-
Lion)
rdniril ;sal
izaton
nzabon
tyPe
d
Picalion
Alul0-
e
z
Secondary variable 2
c
co
2,
Secondary vanabte 3
Figure 12
Functioning mode
Pressure measuring block function groups
The non-linearized pressure value first of all passes through an adjustment. The
resulting corrected pressure value is checked for its sensor limits. If the limits are
24
SITRANS P. Series DS III PA
ASEOOO53276-O4
EFTA01216741
Communication structure for PROFIBUS PA
exceeded, this results in a "Bad" status and the error message "Error in recording
measured value". The corrected pressure value is stored in Secondary variables 1.
Next, it undergoes normalization, whereby the input signal is mapped onto the
range 0 to 1 (percent/100). The normalized pressure value is stored in Secondary
variables 2.
After this — depending on the measuring task — it goes through one of four types of
linearization (see following chapter). The scaling maps the normalized and
linearized measured value (pressure, level, volume or volume flow) onto the actual
process value using the specification of the operating range. This is stored in
measured values (Primary variables).
By multiplying by the density, for a volume flow, the mass flow can be calculated
It is stored in Secondary variables 3.
The pressure sensor temperature value is available in the "Temperature"
parameter.
2.2.1.1 Type of linearization function group
The normalised pressure is passed through linearization algorithms, which are
presented in Table 4, to adjust it to the relevant process requirements. The algorithm
is changed using the "Characteristic curve type" parameter.
Figure 13 Linearization type function group
SITRANS P, Series DS III PA
ASE00053276-04
25
EFTA01216742
Communication structure for PROFIBUS PA
Measuring
task
Linearization
symbol
Characteris-
tic curve type
Description
Pressure
measurement
-
Linear
No linearization
Filling level:
Level
-
Linear
No linearization
Filling level:
Volume
User-
defined
(table)
Linearization of container
characteristic curves.
The relationship between filling level
and volume is described by a
maximum of 31 points with any
intervals.
Flow: Mass-/
Volume flow
without
correction
Extracted
Root extraction of the input value for
measurement according to the
screening method.
Additional parameters for the root
function
Root function application point and
creep quantity suppression, see
Table 5
r
Flow: Mass-/
volume flow
with
correction
Extracted
and table
Root extraction of the input value for
measurement according to the
screening method with linearization.
For the screening method, the high-
est level of accuracy is achieved
when the operating point is at the
design point. If there are deviations,
the measured deviation also
increases, therefore the measuring
accuracy is corrected using a charac-
teristic curve with a maximum 31
points.
----
/
—/—/
Table 4
Linearization functions available
Table 5 describes the manufacturer-specific parameters, which are used in the flow
measuring type to supplement the root function. See also PROFIBUS profile
parameters in the Appendix.
To enter a characteristic curve, select the characteristic curve type "User-defined
(table)". Enter the "New number of interpolation points", which you subsequently
want to enter.
The interpolation points must always be entered in pairs. For each point x[n) in the
operating range, a point yin] is required.
The device checks between which two interpolation points the pressure (secondary
variable 1) related to the measuring range lies and uses the characteristic curve sec-
26
SITRANS P, Series DS III PA
ASE00053276-04
EFTA01216743
Communication structure for PROFIBUS PA
tion (straight line) to map the pressure to the measured value (primary variable) in
the operating range.
Operating range (y)
e.g. Volume measured
value (primary variable)
451,151
Pressure
Measuring
(secondary variable 1)
range (x)
Figure 14 Entry of user-defined characteristic curve using interpolation points x(i). y(i)
Parameter
Description
Application point of the
root function
This parameter determines the flow point in %, below which
the differential pressure is set in a linear relationship to the
flow.
Creep quantity
suppression
This parameter determines the flow point in %, below which
the flow becomes 0.
Table 5
SITFtANS P. Series OS III PA
A5E00053276-04
Manufacturer-specific parameters for flow measurement
27
EFTA01216744
Communication structure for PROFIBUS PA
2.2.1.2 Units for the pressure measuring block
In the pressure measuring block, there are four different points where you have the
possibility of selecting units. Depending on the measuring type, units from the
following measuring functions are permitted:
Variable
Pressure
Filling
level
Measuring type
Volume
Volume Flow
Mass
flow
Non-linearized
pressure value
P
P
P
P
P
Secondary variable 1
P
P
P
P
P
Measured value
(Primary variable)
P
L
V
F
F
Secondary variable 3
—
---
---
---
M
Table 6
Overview of the available units
P: Pressure
L: Filling level
V: Volume
F: Volume flow
M: Mass flow
For all measuring types, you can set the unit "%" as a measured value (primary
variable).
For all measuring types, secondary variable 2 has a standardized value of 1. The unit
is fixed as "none".
For each of the measuring functions P, L, V, F and M, the physical units are listed in
chapter 4.2.7, pg. 51.
2.2.2
Electronics temperature measuring block
This measuring block is manufacturer-specific and is not described in the profile. It is
responsible for monitoring the internal temperature of the device electronics and
cannot change the pressure value, only its status.
The permitted limits correspond to those of the permitted ambient temperature. If a
limit is exceeded, the status changes to 'GOOD — Active Critical Alarm — High/Low-
limit". The status of the corrected pressure value in the pressure measuring block
(see chapter 2.2.1, pg. 24) receives the status "UNCERTAIN — Value not accurate —
high/low-limit". This action is accompanied by a PROFIBUS diagnostic message
"Electronics temperature too high".
Furthermore, indicators for maximum and minimum values are available (see
chapter 5.2.10, pg. 73)
SITRANS P. Series DS III PA
28
ME00053276-04
EFTA01216745
Communication structure for PROFIBUS PA
2.2.3
Analog input function block
The analog input function block is one of the standard functions of transmitters.
Figure 15 shows the processing of measured values up to the output.
Parameters via acyclical access
Measured
value from
pressure
measuring
Nock
0
a
63
et:a
Simulation enable
1
a
Filter time constant
Fault
logic
a
si MAN
if
AUTO
Simulation
Scaling
Mapping
Damp- Limit value Replace-
switch
to 0-1
onto output
ing
testing
mont value
range
behavior
,
'
O/S = Out of Service
to
to
E et)
rs
Mode and
status pro-
cessing
Output
(value status)
Figure 15
Analog input function block function groups
Functioning mode
The measured value from the pressure measuring block —or a simulation value
given by the simulation switch — undergoes a further normalization (measured
value scaling) and mapping onto the output range using output scaling
(application-specific measured variable).
The signal is then filtered (damping) and checked to see that it is within given limits.
For this, upper and lower warning and alarm limits are available.
If the measured value has the status "bad", the fault logic can output a preset safety
value: This can be set as the last usable measured value or a given substitute value.
Using the target mode selected in mode and status processing you can choose
between output of the automatically-recorded measured value (AUTO setting) or a
SITRANS P, Series DS Ill PA
A5E00053276-04
29
EFTA01216746
Communication structure for PROF/BUS PA
manually-set simulation value (MAN setting). If the function block is not working
(O/S), the preset safety value will also be output.
The analog input function block deals with the numerical value separately from the
physical unit. This means that you can set around 1000 pre-defined units. The most
important are listed in chapter 4.2.7, pg. 51.
2.2.4
Counter function block
The counter function block is one of the standard functions of transmitters. It is used
for flow measurement. Figure 16 shows the processing of measured values up to the
output values.
Parameters via acyclical access
Measured
value from
Fault Behavior
last
— "good'
value
Fault
logic
the pressure
measuring
block
EE
1•
3
130LANCECP.
POS ONLY:
Ea .13 Mon 1 olio 0
NEG ONLY:
Ea bMNon1NY0
HOLD: O.
----Time differential 1
E
E E
=C 23 LL L
(0 tv
Nino
k
ilt
Ili
a aJ
O -
Fault behavior
behavior with bad
Summation
Integration/
status
direction
resetting
Summation takes place weighted according to the length of the time period
OrS = Out of Service
L mit value
test
F.Es 1
O.
O
O
I MAN
0/S.
AUTO
E
2,
to
Mode and
status
processing
Counter
output
__„
0„
(Vabe Sitars)
Figure 16
Counter function block function groups
30
SITRANS P. Series DS Ill PA
ASE00053276-04
EFTA01216747
Communication structure for PROFIBUS PA
Functioning mode
The function block processes the measured values from the pressure measuring
block. If a value's status is -bad", the fault behaviour setting decides whether this
value or the last "good" value is passed on for totalling.
The measured values now pass through fixing of the summation direction, to which
you allocate either forwards, backwards or net counting.
Next, they are integrated with the time, so that the flow in a given time interval can
be determined, and checked to see that they within the limits. Here, it is also
possible to reset the total to a pre-loaded value.
You can configure the counter function block in such a way that you can reset or pre-
set it not only using the acyclic services but also from the user programme via the
cyclic data traffic. For more details see chapter 3.1.2.1, pg. 34.
Using the target mode selected in mode and status processing you can choose
between output of the automatically-recorded measured value (AUTO setting) or a
manually-set simulation value (MAN setting).
The possible units correspond to the volume and mass variables for the pressure
measuring block (see chapter 2.2.1.2, pg. 28).
SITFtANS P. Series DS III PA
ASE00053276-04
31
EFTA01216748
Communication structure for PROFIBUS PA
SITFtANS P. Serb s DS III PA
32
A5E00053276-04
EFTA01216749
System integration
3.1
Cyclic data transmission
3
Using cyclic data transmission, the user data relevant for process automation is
transferred between the class 1 Master (control or automation system) and the
transmitter.
3.1.1
Setting the PROFIBUS address
Upon delivery, the PROFIBUS address is set to 126. You can set it on the device
(chapter 4.2.8, pg. 54) or via the bus, with a parameterization tool such as
SIMATIC PDM or HWKonfig.
The new address only becomes effective after a warm start or if the device has been
disconnected from the bus for a short time.
3.1.2
Configuration
Information on the input and output range, as well as the consistency of the cyclically
transmitted data is defined in the DeviceMasterData file (DMD file) , tested with the
device's configuration message and, if appropriate, declared to be valid. During the
design, the user data which will be transmitted in cyclic operation is set. This means
that it is possible to optimise the quantity of data to be transmitted. The DMD files for
all common devices are already stored in the Siemens control system, however they
are also accessible over the Internet (http://www.ad.siemens.deicsi_e/gsd) and
can be subsequently imported.
SITRANS P. Series DS III PA
ASE00053276-04
33
EFTA01216750
System integration
3.1.2.1 Configuring the user data
The user data which is made available to the control system or the open-loop
control via the PROFIBUS depends on the desired configuration selected (see
chapter 5.2.3, pg. 63). In principle, it is supplied by the function blocks (see
chapter 2.1.3, pg. 22 ff.) and put together in the following order:
The analog input function block supplies the content of the "Output" parameter, the
counter function block supplies the content of the "Counter output" parameter. The
configuration allows you to select the function block from which output data will be
transmitted:
1. Output and/or
2. Counter output
For the "Counter output" parameter, you can add the following additional functions:
3. Reset counter output
4. Operating mode
Using "Reset counter output", you can reset the integrator from the operator
programme and change its functioning mode using "Operating mode".
NOTE
For STEP 7. the configuring tool is HW-Konfig. For STEP 5, it is
Function
block/
Parameter
byte
User data sent
to the Master
User data, sent
by the Master
Meaning depending on
further parameters
Analog
input/output
1.-4.
Measured value
---
Pressure, level
Volume, mass flow
5.
Status
Volume flow.
Sensor temperature
Electronics temperature
Counter/
counter
output
6.-9-
Measured value
---
Mass or volume
5.
Status
Table 7
34
User data. depending on the function block selected
SITRANS P. Series DS III PA
ASE00053276-04
EFTA01216751
System integration
Additional
function
byte
User data sent
to the Master
-User data
sent by the
Master
Meaning
Reset
counter
output
1.
-••
Reset counter
output
Counter reset function
0: Normal operation of the
counter Integration is
running
1: Stop integration and
reset integrator to 0
2: Stop integration and
preset integrator with the
pre-loaded value
Operating
mode
2.
—
Operating mode
Counter operating mode
0: Net counter, count
upwards and downwards
1: Forward counter.
2: Backward counter
3: Stop count
Table 8
User data depending on the additional functions selected for the counter output
function block
3.1.2.2
Transmission of user data via PROFIBUS
The user data is continuously updated by the cyclic service of PR0FIBUS.
Bits
7
6
5
4
3
2
1
0
byte
1
VZ
27
25
E
25
24
23
22
21
2
E
26
2-1
2_2
M
2-2
2-4
2-6
2_6
22
3
2-8
2-6
2_10
M 2_il
2_12
2_i3
2_14
2_15
4
2_16
2_17
2_18
M 2_19
2-2o
2_21
2_22
2_23
Table 9
Floating point illustration for the measured value according to IEEE standards
VZ: preceding sign; 0 = positive, 1 = negative
M: Mantissa
E: Exponent
SITRANS P, Series DS III PA
A5E00053276-04
35
EFTA01216752
System integration
3.1.2.3 Status
Status provides information about:
1. the usability of the measured value in the user programme
2. the device status (self-diagnosis/system diagnosis)
3. additional process information (process alarms)
The coding of the status byte is listed on the following pages. In addition, possible
causes of an error are given, along with measures to remove it.
Hex
Digital
display
PDM display
Cause
Measure
80
G_128
—
Normal operation
--
84
G_132
update.event
A parameter relevant for
the behavior of the device
has been changed . The
display is extinguished
after 10 s.
Note to the control system
89
G_137
Fallen below
warning limit
Fallen below lower
parameterized waming
limit.
Correct error using user
programme.
8A
G_138
Warning limit
exceeded
Upper parameterized
waming limit exceeded.
Correct error using user
programme.
8D
G_141
Fallen below
alarm limit
Fallen below lower
parameterized alarm limit.
Correct error using user
programme.
8E
G_142
Alarm limit
exceeded
Upper parameterized
alarm limit exceeded.
Correct error using user
programme.
A4
G_164
Maintenance
required
Maintenance interval has
expired: Calibration or
service
Maintenance work,
calibration of the
electronics or servicing of
the measuring cell is
required.
Table 10
36
Status coding for "Good quality"
SITFtANS P. Serb s DS III PA
A5E00053276-04
EFTA01216753
System integration
Hex
Digital
display
PDM display
Cause
Measure
00
8_000
--
Is used if no other
information is available.
--
04
B_004
Configuration
error
Adjustment range too
small
Repeat the adjustment
process with pressure
values which are further
apart from one another.
08
B_011
Bad, not connect
led, value con-
slant
Variable Is not calculated
Correct the "Measuring
transducer type" setting
0C
B_012
Bad, device error
Device has an irrepara-
ble error
Replace the electronics.
OF
B_015
Device error.
value constant
Device has an irreparable
error.
Change the electronics.
10
B_016
Sensor error
Sensor shows error.
Have the measuring cell
checked by service
personnel.
11
B_017
Sensor error,
Fallen below limit
value
Negative pressure too
high Fallen below lower
overload limit
Increase the pressure in a
positive direction.
(<-20% of
nominal measuring range).
12
B_018
Sensor error,
Limit value
exceeded
Positive pressure too high
Upper overload limit
exceeded
(>120% of nominal
measuring range).
Reduce the pressure.
1F
B_031
Out of order,
value constant
The function block is put
out of order with a target
mode command. A
parametrized safety value
is supplied.
For normal operation,
reset the target mode to
"AUTO-.
Table 11
SITRANS P, Series DS III PA
ME00053276-04
Status coding for "Quality bad"
37
EFTA01216754
System integration
Hex
Digital
display
PDM display
Cause
Measure
47
U_071
Last usable
value, value
constant
Input condition "Fail Safe"
is met. the parameterized
safety setting is set to
'keep last valid value".
Check the recording of
measured values.
48
U_072
Substitute value
Use of the totalizer block,
if the measured value
status = "Bad* and the
parameterized safety
setting is set to "keep last
valid value". The total
value changes. Fault
behavior = Safe operation
Chock the recording of
measured data.
48
U_075
Substitute value
constant
Value is not an automatic
measured value. This
Identifies a
parameterized, static
substitute value or a
preset value.
Chock the recording of
measured values.
4F
U_079
Initial value, value
constant
After run-up, an initial
value is entered in the
device memory.
Reject the value in the
user program.
50
U_080
Value inaccurate
Unreliable operating
parameters or
maintenance alarm
Check the operating
parameters, e.g. the
permitted ambient
temperature. Immediate
maintenance work
required.
51
U_081
Value inaccurate,
fallen below limit
value
Fallen below lower
nominal measuring range
limit (< 10%)
Increase the pressure in a
positive direction.
52
U_082
Value inaccurate,
limit value
exceeded
Upper nominal measuring
range limit has been
exceeded (> 110%)
Reduce the pressure.
Table 12
38
Status coding for "Quality uncertain"
SITRANS P. Series DS III PA
A5E00053276-04
EFTA01216755
System integration
3.1.2.4 Diagnosis
Alongside status information, the device can also actively report information on its
own device status. Diagnoses are important information, which an automation
system can use to introduce remedial measures.
Standard PROFIBUS DP mechanisms are used to transport diagnosis information
and actively report it to the class —1 Master. For this, PROFIBUS DP provides a
protocol to transmit information which is higher-ranked than user data to the class
—1 Master.
The content of the "Device status" parameter from the physical block is reported and,
in addition, information on whether a change of status has occurred (event arrived/
event gone).
The diagnostic object consists of 4 bytes. For SITRANS P, Series DS III PA, only the
first two bytes are relevant.
byte
Bit
Meaning when "1"
Cause
Measure
byte 0
0
1
2
3
Electronics tempe-
rature too high
The measuring trans-
ducer monitors the
temperature of the
measuring transducer
electronics. If this
exceeds 85°C, then
this message is gene-
rated.
Reduce the ambient
temperature to within
the permissible range.
4
Memory error
During operation, the
memories for the cell
and the electronics are
constantly checked for
check sum errors and
read/write errors. In
case of error, this mes-
sage is generated.
Replace the electro-
nics and, if necessary.
the measuring cell.
5
Error in measured
value recording
In case of a sensor
failure or the overload
limits being exceeded
(<-20% or >4-120% of
the nominal measu-
ring range)
Have the measuring
cell checked by the
service department.
6
7
Table 13
SITRANS P, Series DS III PA
A5E00053276-04
Diagnostic message
39
EFTA01216756
System integration
byte
Bit
Meaning when "1"
Cause
Measure
byte 1
0
1
2
3
Warm restart car-
vied out (goes to "0"
after 10s)
The supply current has
been fed to the device
or a warm start has
been triggered using
SIMATIC PDM or the
internal watchdog has
responded.
Check the cabling and
the power unit.
4
Restart (goes to "0"
after 10s)
The device has been
reset to its factory set-
tings.
5
Servicing required
A calibration or service
interval has expired.
Carry out the calibre-
lion or servicing and
reset the messages
using SIMATIC PDM.
6
7
ID number changed
You have changed the
parameter PROFIBUS
(dent Number during
cyclic operation. The
device is reporting the
violation of the Ident
number and showing
you a preliminary
failure warning. In the
case of a warm restart,
the device will no lon-
ger participate in cycli-
cal communication of
reference data without
a change in the system
configuration.
Carry out an adjust-
ment of the configure-
lion data (change of
GSD), so that it is con-
sistent with the Ident
number set in the
device.
Table 13
Diagnostic message
NOTE
The device status can be simulated with the aid of SIMATIC PDM. This allows you
to test the reaction of the automation system to errors.
40
SITFtANS P. Serb s DS III PA
A5E00053276-04
EFTA01216757
System integration
3.2
Acyclic Data Transmission
Acyclic data transmission is mainly used for transmitting parameters during
commissioning, maintenance, batch processes, or for displaying further variables
which do not take part in cyclic user data traffic (Example: Non-linearized pressure
value).
Data traffic occurs between a class-2 Master and the field device with so-called C2
connections. So that several class-2 Masters can simultaneously access the same
transmitter, the device supports up to four C2 connections. However, you must
ensure that they are not writing to the same data.
3.3
SIMATIC PDM
SIMATIC PDM is a software package for designing, parameterizing, commissioning,
diagnosing and maintaining the SITRANS P, Series DS III PA and other process
devices.
SIMATIC PDM contains a simple process monitoring of the process values, alarms
and status signals of the device.
Using SIMATIC PDM you can
•
display,
•
set,
•
change,
•
compare,
•
check the plausibility of,
•
manage and
•
simulate
process device data.
SITRANS P. Series DS III PA
ASE00053276-04
41
EFTA01216758
System integration
SITFtANS P. Serb s DS III PA
42
A5E00053276-04
EFTA01216759
Local operation and display
4.1
General operating instructions
4
You can operate the device locally using the keys (M), [T] and [1] (Figure 21). These
are accessible when you loosen the two screws on the protective cover and lift it up.
The cover must be closed again after operation.
Under normal circumstances, the device is in the "measured value display" mode.
You can select a mode using the (M)key. You can change a value in a mode using
the keys [T] and (4]. By pressing the (M] key again, you switch to the next mode,
whereby the setting is transferred, if it has been changed. Exceptions to this
procedure are described in the following paragraphs.
4.1.1
Digital display
The digital display is used to locally display the measured value (1, Figure 17) and
associated information, e.g. limits being reached.
1 Measured value
1
2
Unit/error code
3 Root display (Bow)
4
Mode/key disable
7
5
6
Lower sensor limit reached
Sign for measured value
6
100000
TWO 1,11)1
7
Upper sensor limit reached
5
8
Communication Indicator
no
u H1
Figure 17 Structure of the digital display
2
SITRANS P, Series DS III PA
A5E00053276-04
43
EFTA01216760
Local operation and display
4.1.2
Measured value display
The measured value display consists of five 7-segment fields with a sign (6, Figure
17) and overflow indicator (5 and 7). The measured value is displayed in a unit which
can be selected. Additional symbols give you further information:
I
Upper warning, alarm or sensor limit reached.
Lower warning. alarm or sensor limit reached.
Communication active. This symbol becomes active for at least 0.3 s and represents
communication currently taking place in terms of acyclic and/or cyclic data transmis-
sion.
4.1.3
Unit display
The unit display consists of five 14-segment fields to represent the physical unit.
onnn
CE
UL
!HI ni l
Figure 18 Examples of measured value displays
4.1.4
Error signaling
If hardware or software errors occur in the transmitter, the "Error" message appears
in the measured value display. A status code is displayed in the unit display (see
chapter 4.2.2, pg. 47 and chapter 3.1.2.3, pg. 36), which indicates the type of error.
This information is also available via the PROFIBUS interface.
Figure 19 Error message, example 'Sensor error"
44
SITRANS P. Series DS III PA
A5E00053276-04
EFTA01216761
Local operation and display
4.1.5
Mode display
The mode display consists of two 7-segment fields which, in local operation, display
the currently selected mode. In the following example (Figure 20) a damping of 0.2 s
has been set in mode 4.
1 numerical value
2 Physical unit
3 Mode display
3
u
11
2
Figure 20 Example of a mode display
If no mode is selected, the digital display will be in the measured value display
function. In this function, the mode display (3) can display
•
active simulation "Si" (see chapter 5.2.8, pg. 70)
•
active operator input inhibit "L", "LC", "LA", "LL" (see chapter 5.2.15, pg. 77)
4.2
Operation with the keyboard
The position of the keyboard is as shown in Figure 21. You can use it to locally
parameterize the transmitter. You can select and execute all the functions described
in Table 14 with settable modes WI key). These are available as part of an extended
range of functions via PROFIBUS (see chapter 5, pg. 59).
Figure 21 Position of the keyboard (three input keys)
SITRANS P, Series DS III PA
A5E00053276-04
45
EFTA01216762
Local operation and display
•
The keylock (see chapter 4.2.5, pg. 49) must be released for keyboard operation.
• If you hold down a key for longer than 1 s, a repetition function will be activated,
which corresponds to around four key presses per second.
•
If more than 2 minutes have elapsed since a key was last pressed, the setting is
saved and the measured value display is returned to automatically.
•
Numerical values are always set from the least significant digit still displayed. In
the case of an overflow in key repetition mode, the device switches to the next
significant digit and only this one continues to be counted. This allows rapid
rough setting of a wide range of figures. For fine setting, you have to release the
[t] or (41 key and press it again. Exceeding of the upper or lower measured value
limits are represented on the display by t or 4. .
•
In the case of disabled operation, it is possible to read parameters, but an attempt
to change anything will be rejected (error code F_001: see chapter 4.2.2, pg. 47).
Function,
Parameter in PDM
Mode
Key function
Display, explanations
[MI I)
in
[4,1
[T] and [11
Measured value display
Display of the measured value selected in
Mode 13
Error display
Error, if transmitter disturbed
Electric damping, time
constant
4
greater
smaler
lime constant T63 in s
Setting range: 0.0 to 100.0
Zero point adjustment
Position correction' 2)
7
—
—
execute
Key and/or function
disable
10
change
5 s
release
For locking variants see Table 32, pg. 77
Source of measured value
display
13
select from several
possibilities
display desired measuring result
Physical unit
14
select
Physical units
bus address
15
higher
lower
User address on PROFIBUS (0.. 126)
Device operating mode
16
change
Selection of device operating mode
- conforms to profile 1 Al
conforms to profile with extensions
Previous device SITRANS PIPA
- conforms to profile 1 Al. 1 TDT
Decimal point
17
change
Position of decimal point in the display
Zero point adjustment
18
-
-
Display of the remaining available measuring
range
LO adjustment
19
Preset
greater
Preset
smaller
execute
Adjustment of the lower point of the
characteristic curve
HI adjustment
20
Preset
greater
Preset
smaller
execute
Adjustment of the upper point of the
characteristic curve
Table 14
46
Summary of opera ing functions using keys
SITRANS P. Serb s DS III PA
A5E00053276-04
EFTA01216763
Local operation and display
1. If 'V appears in the display, the keylock is working.
2. If the r) and [4)keys are pressed simultaneously for about 2 s. the displayed value disappears and
the current value appears after about 2 s.
3. If "LA" or 'LL" appears after releasing the keylock, there is an additional dock on local operation via
the bus. Chapter 5.2.15, pg. 77 explains how to release this using SIMATIC PDM. In measuring
mode, if neither L. "LA' nor 'LL" appear in the mode display, local operation is possible.
4. If the symbol or 4 appears on the left-hand edge of the display, the measured pressure value is
outside the sensor limits, or the parameterized warning or alarm limits have been reached.
4.2.1
Measured value display
In the "Measured value display" function, the measured value selected in Mode 13 is
displayed. The physical unit is set in Mode 14, and the position of the decimal point
in Mode 17.
4.2.2
Error display
Every measured value which can be diplayed is given a status to identify its quality.
If is is classified as "Bad" or "Uncertain", the text "Error" alternates with the measured
value in the display and the status code alternates with the unit.
If the status is not equal to 128 (80H) — irrespective of error signaling — its content is
displayed as a decimal figure with preceding quality classification in the unit display.
The status display has priority, therefore the physical unit is not visible at this
moment.
Examples:
B_000:
B_016:
U_075:
G_138:
Quality bad (Bad), no further information available
Quality bad (Bad), sensor error
Quality uncertain (Uncertain), replacement value
Quality good (Good), warning limit exceeded
The status codes can be found in chapter 3.1.2.3, pg. 36.
SITRANS P. Series DS III PA
A5E00053276-04
47
EFTA01216764
Local operation and display
In the case of exceptional events, error messages can appear during local operation
and are displayed for around 10 s after the occurrence of the error:
Error code
Meaning
Measure
F_001
Local operation disabled
Release write protection
F_002
Change of bus address not possible as
the device is exchanging data with class
1 Master
End communication with class 1
Master.
F_003
Change of device operating mode not
possible as device is exchanging data
with class 1 Master
End communication with class 1
Master.
F_004
Display overflow
Check the physical unit and decimal
point position settings, and adjust
them to the current measured value.
F_005
Value is read only
—
F_006
Adjustent unsuccessful
Check adjustment range, repeat
procedure.
F_007
Measurements across whole measuring
range no longer possible after zero point
adjustment.
Check measuring range, If necessary
reduce inconsistency.
F_008
Local operation has been blocked with
SIMATIC PDM
Set the 'Local operation' parameter to
'enable' with SIMATIC PDM
Table 15
Error messages available
4.2.3
Mode 4: Electric damping
You can set the time constant of the electric damping in steps of 0.1 s between 0 and
100 s with the input keyboard. This damping acts additionally to the device-internal
basic damping.
•
The electric damping is set as follows:
- Set mode 4.
- Select damping with 01 or 01
- Save with [MJ.
Damping only affects the output of the analog input function block.
4.2.4
Mode 7: Zero point adjustment (position error correction)
If the transmitter is installed and ready for operation, outside influences such as
installation location, ambient temperature or installation-dependent admission
pressures (e.g. hydraulic column in the pressure pipe to the transmitter) can move
the original zero point. You can correct this inconsistency here within the following
limits:
SITRANS P. Series DS III PA
48
A5E00053276-04
EFTA01216765
Local operation and display
• Differential pressure: -100 % to +100 % of the nominal measuring range
• Pressure:
-100 % (not more than —1 bar, however)
up to +100 % of the nominal measuring range
•
Absolute pressure:
Mode 7 disabled.
•
You execute a zero point adjustment as follows:
- Create pressure alignment.
- Set mode 7.
- Press [1] and [I] simultaneously for around 2 s.
Depending on the nominal measuring range of the transmitter and the pressure unit
selected, the value 0 appears in the display with the relevant number of decimal
places.
4.2.5
Mode 10: Key lock
In this mode, you can protect against unwanted overwriting of data by local
operation.
•
You set the keylock as follows:
- Set mode 10.
- Activate keylock and function disable with (11 and RI
- Save with [Mb
L appears in the mode display.
The keylock is released, if you press [1] and 01 for more than 5 s in Mode 10.
4.2.6
Mode 13: Source of measured value display
In this mode, you select the value to be displayed. The selections available depend
on the device function set (in the factory or via the bus).The device function cannot
be set locally.
In SIMATIC PDM this is the "Transmitter type" parameter.
•
You select the source of the measured value display as follows:
- Set mode 13.
- Select the source for the measured value display using m or [41
- Save with [MJ.
The physical unit you can assign in Mode 14 depends on the source of the measured
value display.
The following tables show the sources of the measured value display which you can
select for each device function, and which units are available in each case. The
sources of the measured value display given are the parameters which are
reproduced in chapter 2, pg. 21 and in the table of PROFIBUS parameters in the
Appendix.
SITRANS P. Series DS III PA
ASE00053276-64
49
EFTA01216766
Local operation and display
Source of measured value
display
Assistance in the
unit display
Units available
From analog input function block:
101: Output:
OUT
Pressure (P) and user-
specific (U)
From pressure measuring block:
(1] : Secondary variable 1
(2] : Measured value (Primary
variable)
(3] : Sensor temperature
(4] : Electronics temperature
17] : Non-linearized pressure value
SEC 1
PRIM
TMP S
TMP E
SENS
Pressure (P)
Pressure (P)
Temperature (T)
Temperature (T)
Pressure (P)
50
Table 16
Source of measured va ue display for absolute pressure, differential pressure
and pressure device functions
Source of measured value
I
Assistance in
display
the unit display
Units available
From analog input function block:
(0] : Output
OUT
Volume flow (F) or mass flow
(M) and user-specific (U) I)
From pressure measuring block:
(11 : Secondary variable 1
121: Prinary variable
(3) : Sensor temperature
(4] : Electronics temperature
(5] : Secondary variable 3
(7): Non-linearized pressure value
SEC 1
PRIM
TMP S
TMP E
SEC 3
SENS
Pressure (P)
Volume flow (F)
Temperature (T)
Temperature (1)
mass flow (M)
Pressure (P)
From counter function block
(6] : Counter output
TOTAL
Volume (V) or mass flow (LM)
Table 17
Source of measured value display for flow device function
The possible selections for physical units are also determined by the channel setting
(mass or volume) of the analog input and counter function blocks.
SITRANS P. Series DS III PA
A5E00053276-04
EFTA01216767
Local operation and display
Source of measured value
display
Assistance in the
unit display
Units available
From analog input block:
(01: Output
OUT
Filling level (L) and user-
specific (U)
From pressure measuring block:
(11: Secondary variable 1
(21: Prinary variable
(31: Sensor temperature
(41: Electronics temperature
SEC 1
PRIM
TMP S
TMP E
Pressure (P)
Filling level (L)
Temperature (T)
Temperature (T)
Table 18
Source of measured value display for filling level (level) device function
Source of measured value
display
Assistance in the
unit display
Units available
From analog input block:
(01: Output
OUT
Volume (V) and user-specific
From pressure measuring block:
(1] : Secondary variable 1
(21: Prinary variable
(31: Sensor temperature
(41: Electronics temperature
SEC 1
PRIM
TMP S
TMP E
Pressure (P)
Volume (V)
Temperature (T)
Temperature (T)
Table 19
Source of measured value display for filling level (volume) device function
4.2.7
Mode 14: Physical unit
The physical unit is set by selecting one option from a list. The group of units you can
select from depends on the source of the measured value display (Mode 13):
•
You set the physical unit as follows:
- Set mode 14. The identifier of the current unit appears in the measured value
display, and the associated plain text appears in the unit display.
- Select a unit using [1] and RI
- Save with [MI.
The following tables show the physical units available in each measuring type.
SITRANS P. Series DS III PA
ASE00053276-04
51
EFTA01216768
Local operation and display
Unit
ID
Display
Pa
1130
Pa
MPa
1132
MPa
kPa
1133
KPa
hPa
1136
hPa
bar
1137
bar
mbar
1138
mbar
loff
1139
Torr
atm
1140
ATM
psi
1141
PSI
glan?
1144
G.1 cm2
kg/cm'
1145
KGcm2
InH20
1146
INH2O
InH2O(4°C)
1147
INH2O
mrnH2O
1149
mmH2O
mmHZO(4°C)
1150
mrnH2O
ftH2O
1152
FTH2O
InHg
1155
IN HG
mmHg
1157
mm HG
Table 20
Available units of pressure (P)
Unit
ID
Display
u
1010
u
cm
1012
cm
mm
1013
mm
ft
1018
FT
In
1019
IN
Yd
1020
Yd
Table 21
Available units for Siling level
(L, level information)
Unit
ID
Display
m3
1034
m3
dm3
1035
dm3
=
3
1036
cm3
mm3
1037
mm3
Table 22
52
Available units for voluma (V)
Unit
ID
Display
1
1038
L
ci
1039
cL
ml
1040
mL
hl
1041
hL
ina
1042
IN3
ft3
1043
FT3
763
1044
Yd3
pint (US)
1046
Pint
quart (US)
1047
Quart
US gallon
1048
GAL
imp. gallen
1049
ImGAL
bushel
1050
BUSHL
barrel
1051
bbl
barrel liquid
1052
bblii
Table 22
Available units for voluma (V)
Unit
ID
Display
m3/s
1347
m3/S
m3/min
1348
malm
m3/h
1349
m3/h
m3/d
1350
mard
lis
1351
US
l/min
1352
L/min
Ifi
1353
Uh
Vd
1354
Ud
MI/d
1355
MUd
ft3/s
1356
CFS
ft 3/min).
1357
CFM
ft3/h
1358
CFH
ft3/d
1359
CFD
US gallon/s
1362
GAUS
US gallon/min
1363
GPM
US gallon/h
1364
GAUK
US gallon/d
1365
GAUd
bbl/s
1371
bbUS
Table 23
Available units for
Voluma flow (F)
SITRANS P, Series DS III PA
ASE00053276-04
EFTA01216769
Local operation and display
Unit
ID
Display
bbIlmln
1372
bblim
bblth
1373
MTh
bbild
1374
bbUd
Table 23
Available units for
Volume flow (F) (Forts.)
Unit
ID
Display
Ws
1318
G/S
g/min
1319
G/mIn
got
1320
GM
g/d
1321
GM
kg/s
1322
KG/s
kg/min
1323
KG/m
kg/h
1324
KG/h
kg/d
1325
KG/d
Us
1326
T/S
UmIn
1327
Tian
bb
1328
T/h
t/d
1329
T/d
lb/s
1330
lb/S
lb/min
1331
Ibim
lb/h
1331
lb/h
lb/d
1332
bid
STon/s
1334
ST/S
STon/mIn
1335
ST/m
Table 24
Available units for mass flow (M)
Unit
ID
Display
STon/h
1336
ST/h
STon/d
1337
ST/d
LTon/s
1338
LT/S
Lion/min
1339
LT/m
LTon/h
1340
LTM
LTon/d
1341
LT/d
Table 24
Available units for mass flow (M)
Unit
ID
Display
kg
1088
KG
e
1089
G
t
1092
T
oz
1093
oz
lb
1094
lb
Sion
1095
Sion
LTon
1096
LTon
Table 25
Available units for total
mass flow (EM)
Unit
ID
Display
K
1000
K
°C
1001
4C
°F
1002
4F
°R
1003
Oft
Table 26
Available units of temperature (T)
Unit
ID
Display
any
1995
Max. 16 characters
For more than 5 characters, display is as light writing.
Input of the characters to be displayed is possible via bus.
%
1342
%
Table 27
Available user-specific units (U)
SITRANS P, Series DS III PA
A5E00053276-04
53
EFTA01216770
Local operation and display
NOTE
The profile allows a much greater number of possible units. Particularly for the
analog input function block, it is not limited to certain physical values. If you have
selected a unit which is not contained in the valid list, e.g. using SIMATIC PDM,
the current measured value is output in the measured value display with no
dimension.
4.2.8
Mode 15: PROFIBUS address
uaD
In Mode 15, you set the user address of the device on the PROFIBUS. The permitted
range is from 0 to 126
The PROFIBUS address is set as follows:
- Set mode 15. The user address currently set appears in the measured value
display.
- Change this, within the framework of the permitted range, using [1] and [1].
- Save with IM).
NOTE
Ensure that you are not changing the address of the device during operation of
your system. Otherwise, the device can no longer be contacted from the user soft-
ware.
4.2.9
Mode 16: Device operating mode
In relation to its behavior towards the DP Master, the SITRANS P, Series DS III PA
device recognises three operating modes:
[0]
conforms to profile: can be exchanged for transmitters according to
PROFIBUS-PA profile 3.0 with analog input function block (without counter)
[1]
conforms to profile with extensions full functional range of the SITRANS P,
Series DS III PA with analog input and counter function blocks
(supply status)
[2] can be exchanged for the forerunner device SITRANS P/PA
[128)conforms to profile: can be exchanged for pressure transmitter according to
PROFIBUS-PA profile 3.0 with analog input function block and counter.
The device operating mode is set as follows:
- Set mode 16. The current device operating mode (0, 1, 2 or 128) appears in
the measured value display
- Select the desired device operating mode using [ ] and [4.]
- Save with [M].
SITRANS P. Series DS III PA
54
A5E00053276-04
EFTA01216771
Local operation and display
NOTE
Each device operating mode has a particular device master data file assigned to it.
101:
pa_29700.gsd or pa_39700.gsd
11):
siem80A6.gsd
12):
sip1804B.gsd
1128): pa_29740.gsd or pa_39740.gsd
If the configuration of your PROFIBUS-PA channel does not correspond to the
device operating mode set, the device will not pick up the cyclic data exchange.
Successful connection is confirmed by the communication display [o) at the top left
of the digital display (see Figure 17, pg. 43).
4.2.10 Mode 17: Position of the decimal point
Measured values can be displayed to up to 4 decimal places.
The decimal point is shifted as follows:
- Set mode 17. A form with the current position of the decimal point appears in
the measured value display.
- Select the desired display format using 01 and 01
8.8888
88.888
888.88
8888.8
88888
- Save with [M].
CAUTION
— If you place the decimal point too far to the right, the resolution of the display
can turn out too low, i. e. the displayed value always remains 0.
- If you place the decimal point too far to the left, an overflow of the display can
occur. In this case, instead of the measured value, the character string
9.9.9.9.9 is output and the error code F_004 is displayed.
4.2.11 Mode 18: Zero point adjustment display
In this mode, the measuring range (positive pressure) which remains after the zero
point adjustment (Mode 7) or the adjustment process (Mode 19 and 20) is displayed.
You display the current adjustment range as follows:
- Set mode 18. The current adjustment range is displayed.
- Close with (M).
SITRANS P. Series OS III PA
A5E00053276-04
55
EFTA01216772
Local operation and display
4.2.12 Mode 19: LO adjustment
In this mode you can change the slope of the characteristic curve. The characteristic
curve rotates around the HI setting point. This function replaces the zero point
adjustment (Mode 7), which is not permitted on absolute pressure transmitters.
You determine the unit in which you want to make the adjustment by setting the
source of the measured value display (Mode 13) to 7 (non-linearized pressure value,
SENS) and selecting the desired pressure unit with Mode 14.
NOTE
la731 Changing this setting can constrict the measuring range to such an extent that the
permitted sensor limits can be damaged by only a slight change in pressure.
You execute a LO adjustment as follows:
Set mode 19. The value of the last adjustment process appears on the display
with the associated unit.
If you only want to view this information, you can leave the mode by pressing
(M), otherwise you now apply the reference pressure.
Press [t) or [I] The measured value display switches to the current measured
pressure value. Using [11 and 01 you can input the value of the reference
pressure starting at this value.
Press [11 and [41 simultaneously and hold for 2 s to execute the adjustment.
If the adjustment has been successful, the current measured value is
displayed, which should correspond to the adjustment value if it is still close to
the reference pressure.
If the two adjustment points are too close to one another, F_006 is displayed.
The smallest adjustment range depends on the nominal measuring range.
Select either a higher reference pressure in Mode 20 or a lower reference
pressure in Mode 19.
As long as Mode 19 is active, this process can be repeated any number of
times.
- Save with IM).
SITRANS P. Series DS III PA
56
A5E00053276-04
EFTA01216773
Local operation and display
4.2.13 Mode 20: HI adjustment
In this mode you can change the slope of the characteristic curve. The characteristic
curve rotates around the LO setting point.
You determine the unit in which you want to make the adjustment by setting the
source of the measured value display (Mode 13) to 7 (non-linearized pressure value,
SENS) and selecting the desired pressure unit with Mode 14.
NOTE
Changing this setting can constrict the measuring range to such an extent that the
permitted sensor limits can be damaged by only a slight change in pressure.
You execute a HI adjustment as follows:
Set mode 20. The value of the last adjustment process appears on the display
with the associated unit.
If you only want to view this information, you can leave the mode by pressing
(M), otherwise you now apply the reference pressure.
Press Ill or [1] The measured value display switches to the current measured
pressure value. Using [1] and 01 you can input the value of the reference
pressure starting at this value.
Press [1] and [II simultaneously and hold for 2 s to execute the adjustment.
If the adjustment has been successful, the current measured value is
displayed, which should correspond to the adjustment value if it is still close to
the reference pressure.
If you switch to the measured value display, without taking into account a
sufficiently large adjustment range, the pressure status becomes "bad" B_004.
The fault logic of the function block becomes active and the output leads to an
"uncertain" value (U_0xx, depending on the setting).
If the two adjustment points are too close to one another, F_006 is displayed.
Select either a higher reference pressure in Mode 20 or a lower reference
pressure in Mode 19.
As long as Mode 20 is active, this process can be repeated any number of
times.
- Save with [Mb
SITRANS P. Series DS III PA
ASE00053276-04
57
EFTA01216774
Local operation and display
58
SITFtANS P. Serb s DS III PA
A5E00053276-04
EFTA01216775
Functions/Operation via
PROFIBUS-PA
5
For operation via PROFIBUS-PA it is necessary to use PC software such as
SIMATIC PDM. Please consult the appropriate operating instructions or online help
for details of how to operate this. The full scope of functions of the SITRANS P,
Series DS III PA is available via PROFIBUS-PA communication.
5.1
Measuring operation
In measuring operation, measured values such as pressure, filling level or flow are
provided via the PROFIBUS interface. PROFIBUS-PA communication is signaled on
the digital display by the communication character [o] (see chapter 4.1.1, pg. 43).
5.2
Settings
The SITRANS P, Series DS III PA handles numerous measuring tasks. You only
need to carry out the following settings:
•
Settings using a configuration tool, e.g. STEP 7, HW-Konfig: Here, you select the
desired configuration according to which the cyclically transmitted user data will
be structured (see chapter 3.1.2.1, pg. 34).
•
Settings using SIMATIC PDM: Here you set parameters which also influence the
cyclic user data.
If you are setting a new device, you select the measuring type — e.g. pressure or
filling level — and obtain corresponding preset parameters in the SIMATIC-PDM
interface. The following paragraphs only apply to those which you have to
additionally set yourself.
SITRANS P. Series DS III PA
ASE00053276-04
59
EFTA01216776
Functions/Operation via PROFIBUS-PA
In general, we recommend the following procedure:
• First of all read the current settings from the device, by initiating the action "Load
to PG/PC",
•
Check the current settings,
•
Change the required settings,
• Load the parameter settings into the device and also save the parameter settings
offline.
5.2.1
Pressure measurement
•
Select the desired configuration "Output".
•
Connect a device with the measuring type "Pressure", "Differential pressure" or
"Absolute pressure, differential pressure series".
Start SIMATIC PDM. Special parameter settings are not required.
5.2.2
Filling level (level, volume and mass) measurement
•
Select the desired configuration "Output".
•
Connect a device with the measuring type "Filling level".
Depending on whether you want to measure a level, volume or mass, carry out the
following settings.
5.2.2.1 Level measurement
•
Start SIMATIC PDM and create an association between the pressure to be mea-
sured (measuring range) and the level to be recorded (operating range), by set-
ting the following parameters:
» Input
» » Transducer block 1
Measuring transducer type: Level
O 0 » Measuring range
Initial value, final value:
O 0 » Operating range
Unit: Unit of length (m, cm, mm, ft, in, yd)
Initial value, final value
•
Create an association between the measured level value and the initial value, by
setting the following parameters:
SITRANS P. Series DS III PA
60
A5E00053276-04
EFTA01216777
Functions/Operation via PROFIBUS-PA
» Output
» » Function block 1 — analog input
Channel: Measured value (primary variable)
» » Measured value scaling
Initial value, final value: as for operating range
•
)) » Output scaling
Unit, initial value, final value: as for operating range
You can also adjust the output to the other process variables (see Chapter 5.2.4,
p. 67). Associate the desired unit and the initial and final values in accordance with
the measured value scaling with the parameters under the heading Output scaling.
5.2.2.2 Volume measurement
•
Start SIMATIC PDM and create an association between the pressure to be mea-
sured (measuring range) and the volume to be recorded (operating range), by
setting the following parameters:
» Input
» » Transducer block 1
Measuring transducer type: Volume
» » Measuring range
Initial value, final value:
» » Operating range
Unit: Unit of volume (m3, dm3, cm3, mm3
Initial value, final value
• If your container does not have a linear relation between the level and the vol-
ume, you can also specify a characteristic curve:
» Input
» » Transducer block 1
» » » Characteristic curve
Characteristic curve type: User-defined (table)
» » » Interpolation points
New number of interpolation points: max. 31
x[n] measuring range: Pressure value
y[n] operating range: Associated volume value
•
Create an association between the measured volume value and the initial value,
by setting the following parameters:
» Output
» » Function block 1 — analog input
Channel: Measured value (primary variable)
» » » Measured value scaling
Initial value, final value: as for operating range
» » » Output scaling
Unit, initial value, final value: as for operating range
SITRANS P. Series DS III PA
ASE00053276-04
61
EFTA01216778
Functions/Operation via PROFIBUS-PA
You can also adjust the output to another process variable (see chapter 5.2.4,
pg. 65). Associate the desired unit and the initial and final values in accordance with
the measured value scaling with the parameters under the heading Output scaling.
5.2.2.3 Mass measurement
•
Start SIMATIC PDM and create an association between the pressure to be mea-
sured (measuring range) and the volume to be recorded (operating range), by
setting the following parameters:
» Input
» » Transducer block 1
Measuring transducer type: Volume
O »
» Measuring range
Initial value, final value
O 0 » Operating range
Unit: Unit of volume [m3, dm3, cm3, mm3 ,I ...]
Initial value, final value
• If your container does not have a liner relation between the level and the volume,
you can also specify a characteristic curve:
• Input
» » Transducer block 1
» » » Characteristic curve
Characteristic curve type: User-defined (table)
» » » Interpolation points
New number of interpolation points: max. 31
x[n] measuring range: Pressure value
y[n] operating range: Associated volume value
•
Create an association between the measured mass value and the initial value,
by setting the following parameters:
• Output
» » Function block 1 — analog input
Channel: Measured value (primary variable)
» » » Measured value scaling
Initial value: Initial value of operating range • density
Final value: Final value of operating range • density
» » » Output scaling
Unit: Unit of mass [kg, g, t ...]
Initial value: Initial value as for measured value scaling • density
Final value: Final value as for measured value scaling • density
You can also adjust the output to another process variable (see chapter 5.2.4,
pg. 65). Associate the desired unit and the initial and final values in accordance with
the measured value scaling with the parameters under the heading Output scaling.
SITRANS P. Series DS III PA
62
A5E00053276-04
EFTA01216779
Functions/Operation via PROFIBUS-PA
5.2.3
Flow measurement
•
Select the desired configuration with the configuration tool
(see also chapter 3.1.2.1, page 36)
Desired configuration
Measuring type
Output
Current flow/time
Counter output
Flowed volume or flowed mass over a time
period
Output, counter output
Current flow/time,
flowed volume or flowed mass over a time
period,
Reset counter output (using SIMATIC PDM)
Output, counter output, reset counter
output
Current flow/time,
flowed volume or flowed mass over a time
period,
Dose
Output, counter output, reset counter
output, operating mode
Current flow/time,
flowed volume or flowed mass over a time
period,
Dose.
Control operating mode of the counter (net,
forwards, backwards, stop count) from the
user program
Counter output, reset counter output
Flowed volume or flowed mass over a time
period,
Dose
Counter output, reset counter output,
operating mode
Flowed volume or flowed mass over a time
period,
Dose.
Control operating mode of the counter (net,
forwards, backwards, stop count) from the
user program
Table 28
Desired configuration for flow measurement
•
Create a device with the measuring type "Flow".
•
Start SIMATIC PDM and create an association between the pressure to be mea-
sured (measuring range) and the volume or mass flow to be recorded (operating
range), by setting the following parameters:
» Input
» » Transducer block 1
Measuring transducer type: Flow
SITRANS P. Series DS III PA
ASE00053276-04
63
EFTA01216780
Functions/Operation via PROFIBUS-PA
0
» 0
0
Measuring range
Initial value: 0
Final value
Operating range
Unit: Unit of volume/unit of time [m3/s, m3/h, I/s, ...] or
Unit of mass/unit of time [kg/s, t/min, ..]
Initial value: 0
Final value
Characteristic curve
Characteristic curve type: Extracted
•
To record the current flow, use the function block 1 — analog input. Create an
association between the measured flow value and the initial value by setting the
following parameters:
» Output
» » Function block 1 — analog input
Channel: Measured value (primary variable)
•
0 » Measured value scaling
Initial value, final value: as for operating range
•
0 » Output scaling
Unit, initial value, final value: as for operating range
•
To record the flowed quantity (mass or volume), use the counter function block.
» Output
» » Counter function block
Channel: Measured value (primary variable)
Unit (counter)
• If your reference configuration does not contain the operating mode settings
(reset counter or operating mode), you should also set the following parameters
using SIMATIC PDM:
» Output
» » Counter function block
» » » Operating mode
Operating mode: [Pos. and neg. values I only positive values]
Counter output: Figures.
5.2.3.1 Application point for the root function, creep quantity suppression
If you want to avoid the error which occurs at low flow quantities, there are two
possibilities, which you can also use in combination:
•
The application point of the root function determines the point below which the
root function becomes linear.
•
Creep quantity suppression sets the measured flow quanity to 0, when the value
falls below the preset limit.
In each case, enter the application point as a % of the operating range (volume flow).
SITRANS P. Series DS III PA
64
A5E00053276-04
EFTA01216781
Functions/Operation via PROFIBUS-PA
Figure 22 Application point of the root function and creep quantity suppression
5.2.3.2 Flow measurement correction
If you want to carry out a correction as part of your application (e.g. to take account
of the flow coefficient a and the expansion coefficient c), select:
•
Characteristic curve type: Root-extracted and characteristic curve
• Points: For a maximum of 31 points, provide an input value (measured volume
flow) and an output value (corrected volume flow).
5.2.4
Adjustment to the desired process variable
The analog input function block is responsible for mapping the measured value onto
the process value. Normally, you will want to switch the measured value directly onto
the bus: The input and output range is then taken from the operating range. If,
however, the measured pressure, the filling level or the flow has only an indirect but
linear relationship to the process variable, assign starting and end values for the
input range and for the output range, as described in the following examples:
SITFtANS P. Series OS III PA
A5E00053276-04
65
EFTA01216782
Functions/Operation via PROFIBUS-PA
Example 1:
You would like to assign the input range 1 to 4 Pa to the output range 0 to 100%.
•
Set the measuring type "Pressure" as outlined in chapter 5.2.1, pg. 60
•
Set the following parameters:
- In the pressure measuring block:
Unit of the measured value (primary variable) Pa
- In the analog input function block:
Input starting value: 1,0
Input end value: 4,0
Output starting value: 0,0
Output end value 100,0
Unit (Output): cro
Example 2:
You would like to convert the input range 0 to 400 m3 into 200 I barrels. The output
range is, for example, 0 to 2000 barrels.
•
Set the measuring type 'Volume level' as outlined in chapter 5.2.2, pg. 60.
•
Set the following parameters:
- In the pressure measuring block:
Unit of the measured value (primary variable) m3
- In the analog input function block:
Input starting value: 0,0
Input end value: 400,0
Output starting value: 0,0
Output end value 2000.0
Unit (Output): Text
Unit text (Output): Barrels
NOTE
The digital display can only display some of the ASCII character set and cannnot
display all ASCII characters in capitals and lower case. If you enter the lower case
letters f, g, j, p, q, t, x, y, z in the parameter "Unit text (Output)" using SIMATIC
PDM, they can only be reproduced in capitals. The umlauts a, o, ii and f5, as well
as all ASCII characters with a coding higher than 125, are reproduced as a block
symbol with all segments turned on. You should therefore avoid language-specific
characters.
SITRANS P. Series DS III PA
66
A5E00053276-04
EFTA01216783
Functions/Operation via PROFIBUS-PA
5.2.5
Electric damping
Electric damping acts like a 1st order filter. According to the filter time constant you
preset as TB3 the output has reached 63% of a sudden change in pressure.
Set the following parameter in the analog input function block:
• Fifter time constant: Desired time in the range 0 to 100s
5.2.6
Warning and alarm limits
The analog input and counter function blocks each have upper and lower warning
and alarm limits for output or counter output. To prevent unstable display of the
warnings and alarms, you can also provide a hysteresis.
Set the following parameters, according to the process conditions, in the analog input
and/or counter function blocks:
• Limit-value hysteresis
• Upper warning limit
• Upper alarm limit
• Lower warning limit
• Lower alarm limit
If limits are exceeded, the output/counter output is accompanied by a status value,
which you can evaluate in your user program:
Exceeding of the
Status hex.
Digital display
lower warning limit
89
G_137
upper warning limit
8A
G_138
lower alarm limit
8D
G_141
upper alarm limit
8E
G_142
Table 29
SITRANS P. Series DS III PA
ASE00053276-04
Limits and status displays
67
EFTA01216784
Functions/Operation via PROFIBUS-PA
A
Alarm top
Warning top
Warnung bottom
Alarm bottom
Upper_alarm limit à
Upper_warning limit
r
T
_7\1
Lower_warifing limit
Lover alarm limit
I Hysteresis
Hysteresis
Hysteresis
Hysteresis
Figure 23 Warning and alarm limite
68
SITRANS P. Sonos DS Ill PA
A5E00053276-04
EFTA01216785
Functions/Operation via PROFIBUS-PA
5.2.7
Fault Behavior
If the measuring block fails, the analog input and counter function blocks can take on
behavior which you have preset. If the output variable of the measuring block is
accompanied by a "bad" status due to an error, e.g. "Bad — sensor error", the function
blocks actuate fault behavior. The output or counter output is then accompanied by
an "uncertain" status.
5.2.7.1 Output
Set the fault behavior in the analog input function block:
Fault Behavior
Description
The replacement value is taken over to the
output value
The predefined preset safety value is
output (status code U_075)
Saving of the last valid output value
The last valid output value is output (status
code U_071).
The incorrectly calculated measured value
is close to the output.
(Fault logic off)
The bad output value is accompanied by
the status which the measuring block
assigns to it (B_0xx)
Table 30
Fault behavior of the analog inpout function block
So that you can isolate the cause of the error with fault logic turned on, separate the
primary or secondary variables including status using SIMATIC PDM.
5.2.7.2 Counter output
Set the fault behavior in the counter function block:
Fault Behavior
Description
Stop
If there are inputvalues with a bad status.
the counting process is stopped (status
code U_075)
Secure operation
The counting process continues with the
last inputvalue before the fault which
was accompanied by a 'good" status
(status code U_072)
Operation
The bad measured value is accompanied
by the status which the measuring block
assigns to it (status code B_0xx)
Table 31
SITRANS P. Series DS III PA
ASE00053276-64
Fault behavior of the counter function block
69
EFTA01216786
Functions/Operation via PROFIBUS-PA
5.2.8
Simulation
Simulation functions assist you in commissioning part installations and the transmit-
ter. You can create process values without recording actual values. The range of
values of the simulated process values can be fully utilized: This means that errors
can also be simulated.
From the output of the SITRANS P, Series DS III PA, you can gradually move closer
and closer to the sensor, to test the measuring and function blocks.
On the digital display, you will see "sr in the mode display when a simulation has
been activated.
5.2.8.1 Output simulation
With output simulation, you can provide process values for cyclic user data traffic at
the output of the SITRANS P, Series DS III PA using acyclic write accesses. In this
way, you can test the processing of process values in the automation program
Carry out the following settings:
•
Select output simulation.
•
Set the target mode to MAN (manual).
• Enter the desired output value, the quality and the status.
•
Transfer the settings from the program into the transmitter.
You can view the output behavior in e.g. SIMATIC PDM or using a table of variables
(VAT module).
To return to normal operation, you have to set the target mode to AUTO.
5.2.8.2 Input simulation
With input simulation, you can test the adjustment of the measured value to the
desired process variable, the monitoring of your preset process limits, electric
damping and fault behavior.
Carry out the following settings:
•
Select input simulation.
•
Set the target mode to: AUTO
•
Select the simulation mode "Enable".
• Enter the desired input value, the quality and the status.
•
Transfer the settings from the program into the transmitter.
You can view the behavior of the output in e.g. SIMATIC PDM.
To return to normal operation, you have to turn off the simulation.
SITRANS P. Series DS III PA
70
A5E00053276-04
EFTA01216787
Functions/Operation via PROFIBUS-PA
5.2.8.3 Pressure sensor simulation
With pressure sensor simulation — as a fixed value or as a parameterizable slope
(see Figure 24) — you can test adjustment, checking of the zero point movement,
reaction to sensor limits being exceeded, as well as linearization and mapping onto
the operating range.
With a parameterizable slope you can make the simulation value dynamic. It runs
from a starting value to an end value in a step function, dwelling on each step for the
preset period of time. At the end value, the direction is reversed.
Value
Full scale
Initial
value
— PH
Step length
Number of
Figure 24 Parameterizable slope
Carry out the following settings:
•
Select pressure sensor simulation.
•
Set the simulation mode and the parameters:
- simulation mode 'fixed" and pressure value
- simulation mode "slope" and slope parameters
•
Transfer the settings from the program into the transmitter.
You can view the behavior of the measured values (primary variables), secondary
variables 1, 2 and 3 and the output in SIMATIC PDM.
To return to normal operation, you have to turn off the simulation.
SITRANS P. Series DS III PA
A5E00053276-04
71
EFTA01216788
Functions/Operation via PROFIBUS-PA
5.2.8.4 Simulation of the sensor and electronics temperature
With simulation of the sensor and electronics temperature, you can test, for example,
the influence of too high a temperature on the measuring results:
•
Select simulation of sensor and electronics temperature.
•
Continue as for pressure sensor simulation (chapter 5.2.8.3, pg. 71).
You can view the reaction in the status of the measured values (primary variables),
secondary variables 1,2, and 3 and the output using SIMATIC PDM.
To return to normal operation, you have to turn off the simulation.
5.2.9
Calibration interval and service interval
Two timers are contained in the SITRANS P, Series DS III PA:
•
a timer for the calibration interval, which you can use to ensure regular calibration
of the electronics,
•
a timer for the service interval which draws attention to the fact that servicing of
the measuring cell and its connections will soon be required.
The interval length can be selected. The timers can monitor in two stages and first
issue a warning, then an alarm (see Figure 25).
Timer
value value
Alarm
Warning
Warning present
Warning acknowledge
Alarm present
Alarm acknowledged
Off
Resetting
ry
Time.
Figure 25 Calibration and service intervals
72
SITRANS P. Serios DS Ill PA
A5E00053276-04
EFTA01216789
Functions/Operation via PROFIBUS-PA
Set the calibration and service intervals as follows:
•
Set the parameters for warning/alarm.
• Enter the time, after which a warning should be issued.
• Enter the additional time after which an alarm should be issued — when a warning
has already occurred.
5.2.9.1 Warning
As soon as the warning interval has expired, the first monitoring stage issues a
warning. Measured values are accompanied by the status "Good, maintenance
required" and the diagnostic message "Maintenance required" is displayed. SIMATIC
PDM can also display the calibration or service status and the value of the timer.
•
Acknowledge the warning. The diagnostic message is removed and the status is
reset to "Good".
•
Carry out the calibration or service and reset the timer.
5.2.9.2 Alarm
If calibration or servicing is not carried out at the correct time, the second monitoring
stage issues an alarm, which draws attention once again to the fact that maintenance
is urgently required. Measured values are accompanied by the status "Uncertain,
value inaccurate" and the diagnostic message "Maintenance required" is displayed.
•
Acknowledge the alarm. The diagnostic message is removed and the status is
reset to "Good".
•
Carry out the calibration or service and reset the timer.
5.2.10 Slave pointers
The device contains three pairs of slave pointers with which you can monitor the
three measuring variables pressure, sensor temperature and electronics tempera-
ture for negative and positive peak values. For every measuring variable, one reset-
table and one non-resettable slave pointer saves the maximum and minimum peak
values.
The non-resettable slave pointers document the maximum and mimimum values
which have occurred over the whole life cycle of the device.
The resettable slave pointers are updated manually or when the pressure sensor,
sensor temperature or electronics temperature is simulated (see chapter 5.2.8.3,
pg. 71 and chapter 5.2.8.4, pg. 72).
SITRANS P. Series DS III PA
ASE00053276-04
73
EFTA01216790
Functions/Operation via PROFIBUS-PA
P
Upper slave pointer value
Lower slave pointer value
t
Figure 26 Principle display of slave pointers using pressure as an example
5.2.11 Operating hours counter
You can select one operating hours counter each for the electronics and the sensor.
They are activated the first time the transmitter is started.
SITFtANS P. Serb s DS III PA
74
A5E00053276-04
EFTA01216791
Functions/Operation via PROFIBUS-PA
5.2.12 Sensor adjustment
Sensor adjustment allows you to calibrate the transmitter. In the same way as
Mode 19 and 20 of local operation (see chapter 4.2.12, pg. 56 and chapter 4.2.13,
pg. 57) you can change the slope of the characteristic curve of each transmitter.
You can determine the course of the characteristic curve using one lower and one
upper adjustment point.
You can change the slope of the characteristic curve to a minimum of 0.9 and a
maximum of 1.1. A larger deviation from a gradient of 1.0 does not lead to the
relevant adjustment point being saved.
The lower adjustment point must be selected to be at least that distance away from
the upper, which will observe the smallest adjustment range.
The smallest adjustment range is displayed in the sensor adjustment dialog and
depends on the measuring range. If, during adjustment, the range falls below the
smallest range set, the measured values are accompanied by the following status
coding:
"Quality bad, configuration error'.
In this case, you should re-adjust the lower or upper adjustment point to give a
sufficiently large adjustment range.
•
An adjustment of the lower point is carried out as follows:
- Call up the "Sensor adjustment" dialog.
- Apply the reference pressure for the lower adjustment point.
- Enter the value of the reference pressure in the "Lower adjustment point" field.
- Click on "Transmit".
- In the field "Corrected non-linearized pressure value", you can view the effect
of the adjustment. In the "Lower adjustment point" field, you can see whether
or not the new adjustment point has been transferred.
•
An adjustment of the upper point is carried out as follows:
- Call up the "Sensor adjustment" dialog.
- Change to the "Upper adjustment" tab.
- Apply the reference pressure for the upper adjustment point.
- Enter the value of the reference pressure in the "Upper adjustment point" field.
- Click on "Transmit".
- In the "Corrected non-linearized pressure value" field, you can view the effect
of the adjustment. In the "Upper adjustment point" field, you can see whether
or not the new adjustment point has been transferred.
After you have adjusted both points, the quality of the measured value should be
"Good". If "Quality bad, configuration error' is displayed, then you have fallen below
the lowest adjustment range. You must increase the distance between the
adjustment points, by moving one of the two points.
SITRANS P. Series DS III PA
ASE00053276-04
75
EFTA01216792
Functions/Operation via PROFIBUS-PA
5.2.13 Positional error adjustment
Outside influences such as installation location, ambient temperature or installation-
dependent admission pressures (e.g. hydraulic column in the pressure pipe to the
transmitter) can move the original zero point. You can correct this inconsistency here
within the following limits.
• Differential pressure: -100 % to +100 % of the nominal measuring range
• Pressure: -100 % (not more than —1 bar, however)
up to +100 % of the nominal measuring range
•
Absolute pressure:Positional error adjustment not possible;
•
You carry out a positional error adjustment as follows:
- Call up the Positional error adjustment" dialog
- Create a pressure adjustment
- Click on "Transmit"
5.2.14 Resetting
5.2.14.1 Resetting to delivery status
If the SITRANS P, Series DS III PA, has been adjusted to such an extent that it can
no longer fulfil its measuring tasks, you can recreate the delivery status with this
function. It resets all parameters to the factory settings, with the exception of the
PROFIBUS address (see chapter 5.2.14.3, pg. 77), the device operating mode (see
chapter 4.2.9, pg. 54), the static inspection number in Transducer Block 1, in the
analog input and counter function block.
Resetting is displayed by the diagnostic message "Cold starting in progress'. As long
as there is no measured value result, the automation or control system records the
status 'Uncertain, initial value, value constant".
5.2.14.2 Restart (warm start)
For a warm start you will need to turn off the SITRANS P, Series DS III PA, and
restart it. Communication is interrupted and re-established.
You will need this function if, for example, during communication with a cyclic Master,
the PROFIBUS address has been changed.
This restart is displayed by the diagnostic message "New start-up (warm startup)
carried out". As long as there is no measured value result, the automation or control
system records the status "Uncertain, intial value, value constant".
SITRANS P. Series DS III PA
76
A5E00053276-04
EFTA01216793
Functions/Operation via PROFIBUS-PA
5.2.14.3 Resetting the PROFIBUS address to 126
If no other device in your system has the preset address 126, you can extend the
PROFIBUS-PA channel during operation of the automation or control system with
your SITRANS P, Series DS III PA. You then have to change the address of the
newly integrated device to another value.
If you remove a SITRANS P, Series DS III PA from the PROFIBUS channel, you
should use this function to reset its address to 126 so that, if required, it can be re-
integrated into another system.
5.2.15 Operator input inhibits
You can set operator input inhibits according to the following table.
Operator input
inhibit
Effect
Turn on/off
Digital
display
Keylock and
function disable
Parameter changes using SIMATIC
PDM and settings via local operation
are disabled. Independent of the other
operator input inhibits.
Keyboard
Mode 10
L
Write protection
Password protection for changing
parameters via the bus. Local operation
is possible.
SIMATIC PDM
LC
Enable local
operation
If local operation is not enabled, no
access is possible using the keyboard.
Independently of this parameter, local
operation is automatically enabled 30 s
after a communiation failure. Once
communication has been re•stablished,
the parameter -Enable local operation"
in the device is reset to the original
setting.
SIMATIC PDM
LA
Combination of
write-protection
and local
operation not
being enabled
Has the same effect as an active
keylock. Parameters (except operator
input inhibits) cannot be changed via
local operation or using SIMATIC PDM.
SIMATIC PDM
LL
Table 32
SITRANS P, Series DS III PA
A5E00053276-04
Operator input inhibits
77
EFTA01216794
Functions/Operation via PROFIBUS-PA
You can also combine the operator input inhibits:
Key lock and
function
disable
Write-protection for changing
parameters via the bus
Enable local
operation using
SIMATIC PDM
Digital
display
On
On or off
enabled or disabled
L
Off
Off
disabled
LA
Off
Off
enabled
Off
On
disabled
LL
Off
On
enabled
LC
Table 33
Combined operator input inhibits
SITFtANS P. Serb s DS III PA
78
A5E00053276-04
EFTA01216795
Modular design
Summary
6
WARNING
This device has a modular design. This gives you the opportunity to replace vari-
ous components with original spares. When replacing a component, please ensure
that you always observe the instructions enclosed with the component to be
replaced.
This applies particularly to devices used in areas with a risk of explosion.
The two individual components measuring cell and electronics both have a non-
volatile memory (EEPROM). Each contains a data structure which is permanently
assigned to the measuring cell or the electronics. Measuring cell data (e. g.:
measuring range, measuring cell material, oil filling etc.) is stored in the measuring
cell's EEPROM. Data for the electronics (e.g.: turn-down, additional electric damping
etc.) are in the electronics' EEPROM. This ensures that the data relevant to the
remaining component are retained when one component is exchanged.
Before replacing components you can set, via PROFIBUS, whether the common
measuring range settings are to be taken from the measuring cell or the electronics
after the exchange or whether standard parameters should be set. The measuring
accuracy within the specified measuring limits (with gear reduction 1:1) may be
reduced by the temperature error under unfavorable conditions.
In the course of further technical development, extended functions may be imple-
mented in the measuring cell or electronics. This is identified by a changed firmware
version (FW). The firmware version has no influence on the exchangeability.
However, the scope of functions is restricted to the function of the respective older
component.
SITRANS P. Series OS III PA
A5E00053276-04
79
EFTA01216796
Modular design
If a particular combination of the firmware statuses of the measuring cell and
electronics is not possible for technical reasons, the device detects this and displays
the status "Fault current". This information is also provided via the PROFIBUS
interface.
SITFtANS P. Serb s DS III PA
80
A5E00053276-04
EFTA01216797
Installation
7
The installation types described below should be seen as typical examples.
Depending on the system configuration, installation types differing from these may
also be possible.
WARNING
Protection against incorrect user of the measuring device:
It must be particularly ensured that the selected materials of the process-wetted
parts of the measuring device are suitable for the process media used. Failure to
observe this precaution could endanger life and limb and the environment.
CAUTION
At surface temperatures > 70 °C a touch protection should be provided. The touch
protection must be designed so that the max. permissible ambient temperature of
the device is of exceeded.
CAUTION
The device may only be used within the medium pressure limits and voltage limits
specified on the rating plate depending on the explosion protection type with which
the device is operated.
NOTICE
External loads may not be applied to the transmitter.
SITFtANS P. Series D3 III PA
A5E00053276-04
81
EFTA01216798
Installation
WARNING
Explosion proof devices may only be opened when the power is off.
Notes on operation of the intrinsically-safe version in hazardous areas:
Operation is only permitted on circuits which are certified as intrinsically safe. The trans-
mitter is compliant with Category 1 / 2 and may be installed at zone 0.
The EU type examination certificate applies for installation in the walls of containers and
pipes which may contain explosive gas/air or vapor/air mixtures only under atmospheric
conditions (pressure 0.8 bar to 1.1 bar, temperature -20 °C to +60 °C). The permissible
ambient temperature range is -40 °C to +85 °C, in explosion hazard areas -40 °C to max-
imum +85 °C (T4).
The user max also apply the device in non-atmospheric conditions outside the limits set in
the EC-Type Examination Certificate (or the valid test certificate for its country), according
to the conditions for use (explosive mixture) and if the required additional security mea-
sures have been met. The limit values stated in the general technical data must be
observed in any cases.
Additional requirements are necessitated in the case of instalation at zone 0:
The installation must be adequately sealed (IP 67 to DIN EN 60 529). An industrial stan-
dard (e.g. DIN, NPT) threaded joint is suitable for example.
When operating with intrinsically safe power supply units of the la" category, the explo-
sion protection does not depend on the chemical resistance of the seal diaphragm.
When operation with intrinsically safe power supply units of the lb" category or for units
with explosion proof type of protection 'Ex d" and simultaneous use at zone 0, the expli-
sion protection of the transmitter depends on lightness of the diaphragm. Under these
operating conditions, the transmitter max only be used for those imflammable gases and
liquids to which the diaphragms are adequately chemically resistant to avoid corrosion.
7.1
Installation (except filling level)
The transmitter can be arranged above or below the pressure tapping point.
When measuring gases we recommend installing the transmitter above the pressure
tapping point and laying the pressure line with a constant downward gradient to the
pressure tapping point so that condensation which forms can drain into the main
line and the measured value is not falsified (for recommended installation see
chapter 8.1.1, pg. 97).
When measuring vapors and liquids the transmitter should be installed below the
pressure tapping point and the pressure line should have a constant upward gradient
so that gas entrapped in the main line can escape (for recommended installation see
chapter 8.1.2, pg. 98).
The installation point should have good access, if possible in the vicinity of the
measuring point and should not be exposed to strong vibration. The permissible
ambient temperature limits (see chapter 9, pg. 103 for further information) may not
be exceeded. Protect the transmitter from direct heat radiation.
SITRANS P, Series DS III PA
82
A5E00053276-04
EFTA01216799
Installation
The operating data must be compared with the values specified on the rating plate
before assembly.
The housing may only be opened for maintenance, local operation or electrical
installation.
Suitable tools must be used for connecting the transmitter on the pressure side.
Do not rotate the housing, to install the process terminal.
Observe the installation instructions on the housing!
7.1.1
Mounting without mounting bracket
The transmitter may be mounted directly at the process connection.
7.1.2
Mounting with mounting bracket
The mounting bracket is fastened
•
to a wall or a mounting rack with two screws
or
•
with a pipe bracket to a horizontal or vertical mounting pipe (0 50 to 60 mm)
The transmitter is fixed to the mounting bracket with two screws (enclosed).
SITRANS P. Series DS III PA
ASE00053276-04
83
EFTA01216800
installation
Figure 27 Mounting the SITRANS P, Series DS III PA transmitter, with mounting bracket
84
Figure 28 Mounting the SITRANS P, Series OS III PA transmitter, with mounting bracket
(example differential pressure, horizontal active pressure lines)
SITRANS P. Serb s DS III PA
A5E00053276-04
EFTA01216801
Installation
Figure 29 Mounting the SITRANS P, Series DS III PA transmitter, with mounting bracket
(example differential pressure, vertical active pressure lines)
7.2
Mounting "filling level"
7.2.1
Installation
Before installing, check whether the transmitter satisfies the operating conditions
(material, sensor length, measuring span)
The installation location must be easily accessible and free from vibration. The
permissible ambient temperatures may not be exceeded. Protect the transmitter
from heat radiation, rapid temperature fluctuations, heavy soiling and mechanical
damage.
The height of the container flange for mounting the transmitter (measuring point)
must be chosen so that the lowest liquid level to be measured is always above the
flange or at its top edge.
1. Screw the flange of the transmitter (for dimensions see Figure 44, pg. 110) after
fitting a seal (e.g. flat sealing ring DIN EN 1514-1) to the counterflange of the
container (seal and screws are not included in the delivery). The seal must be
central and must not restrict the mobility of the flange's seal diaphragm at any
point.
2. Observe the installation position!
SITRANS P. Series DS III PA
ASE00053276-04
85
EFTA01216802
Installation
7.2.2
Connecting the low pressure line
No line is necessary when measuring on the open container (Figure 30, page 85)
because the low pressure chamber is connected to the atmosphere. The open
connecting pipe should point downwards to prevent dirt getting in.
Figure 30 Measuring setup on the open container
When measuring on the closed container without or with only slight condensation
(Figure 31, page 86) the low pressure line remains unfilled. The line must be laid so
that no condensate sacks can form, you may have to install a condensation vessel.
start of scale
lull scale
start of scale
lull scale
local acceleration due
to gravity
density of the medium
in the container
86
Figure 31 Measuring set up on the dosed container (no or only slight condensation escape
SITRANS P, Series DS III PA
A5E00053276-04
EFTA01216803
Installation
When measuring on the closed container with strong condensation formation
(Figure 32, page 87), the low pressure line must be filled (usually with medium
condensate) and a calibration vessel must be installed. The device can be shut off,
for example using a double valve manifold 7MF9001-2.
Figure 32
start of scale
full scale
start of scale
full scale
outlet spacing
local acceleration due to gravity
density of the medium in the
container
Density of the liquid in the
low pressure return line
corresponds to the prevailing
temperature there
Measuring setup on the closed container (strong condensation formation)
The process connection on the low pressure side is a female thread 1/4-18 NPT or
an oval flange.
The line for the low pressure must be made e.g. of 12 mm x 1.5 mm seamless steel
pipe. See Figure 28, page 84 and Figure 32 for shutoff valves.
7.3
Rotating the measuring cell in relation to the housing
If necessary, you can rotate the electronics housing in relation to the measuring cell
in the SITRANS P, Series DS III PA transmitter so that the digital display (in housing
covers with a window) is visible and access to the input keys and the current
connection for an external measuring instrument is possible.
Only limited rotation is permitted! The range of rotation (1, Figure 33, page 88) is
marked at the base of the electronics housing, there is an orientation mark (3) on the
neck of the measuring cell which must stay within the marked area when rotating.
1. Loosen the locking screw ((2), hexagon socket head 2.5 mm).
2. Rotate the electronics housing in relation to the measuring cell (only within the
marked area)
3. Tighten the locking screw (torque 3.4 to 3.6 Nm).
SITRANS P. Series DS III PA
A5E00053276-04
87
EFTA01216804
installation
Figure 33 Range of rotation of the measuring cell (in pressure and absolute pressure
transmitters of the pressure series)
Figure 34 Range of rotation of the measuring cell (in differential pressure and flow and
absolute pressure transmitters from the differential pressure and filling level series
CAUTION
The range of rotation must be observed otherwise destruction of the electrical
connections of the measuring cell cannot be ruled out.
SITFtANS P. Series DS III PA
88
A5E00053276-04
EFTA01216805
installation
7.4
Electrical Connection
WARNING
The specifications of the examination certificate valid in your country must be
observed.
Laws and regulations valid in your country must be observed for the electrical
installation in explosion hazardous areas. In Germany these are for example:
- Working reliability regulations
- Regulations for installing electrical equipment in hazardous areas DIN EN
60079-14.
It should be checked whether the available power supply is compliant with the
power supply specified on the type plate and specified in the examination certifi-
cate valid in your country. Dust-proof protection caps in the cable inlets must be
replaced by suitable screwtype glands or dummy plugs which must be appropri-
ately certified for transmitters with explosion-proof type of protection!
NOTE
To improve interference it is recommended to:
- lay signal cables separately from cables with voltages >60 V.
- use cables with twisted wires.
- avoid the vicinity of large electrical installations or use shielded cables.
- use shielded cables to guarantee the full specification according to HART.
- use a load of at least 230 ohms in the signal circuit to guarantee error-free
communication. When using feed separators for SMART transmitters, e.g.
Siemens 7NG4021, a load is already built into the device.
- Only use cables with a diameter of 6 to 12 mm in the standard screwed glands
M20x1.5 and '/2-14^ NPT for reasons of tightness (IP degree of protection).
- In devices with "n" type of protection (Zone 2) only use cables with a diameter
of 8 to 12 mm or a suitable screwed gland for a smaller diameter for reasons of
tensile strength.
SITRANS P, Series DS III PA
A5E00053276-04
89
EFTA01216806
installation
7.4.1
Connection to screw terminals
Make the electrical connection as follows:
1. Unscrew the cover of the connection box (marked 'FIELD TERMINALS" on the
housing).
2. Insert the connecting cable through the cable gland.
3. Connect the wires to the "+" and
terminals (Figure 35, page 90).
Despite the markings, the polarity is not important.
4. Connect the screen to the screen screw if necessary. This is connected to the
outer earth terminal. The polarity is unimportant although it is indicated.
5. Screw on the housing cover.
Figure 35 Electrical connection, schematic diagram
Screen plate
Power supply
Screws for fastening the terminal strip
Terminals
Test plug for DC ammeter or connection facility for external display
Cover catchr
PE conductor connectioNEquipotential terminal
WARNING
In explosion-proof transmitters the housing cover must be screwed on tightly and
secured with the cover catch.
90
SITRANS P, Series DS III PA
ASE00053276.04
EFTA01216807
Installation
7.4.2
Connection with plug M12
For devices on which a plug is already installed on the housing of the SITRANS P,
DS III PA series, the bus connection to the PROFIBUS PA is created with a mating
connector.
1. Thread the pressure screw, damping cage, seal, screening ring and coupling
sleeve onto the field bus cable, see Figure 37, page 92
2. Strip the insulation from the bus cable according to Figure 36, page 91.
3. Pull insulated tubing over the screen • or solder the screen to insulated wire"
(0.25 mm2)
4. Pull a shrink-on sleeve over the cable, wires and screen in the insulated tubing
or pull the wire
CAUTION
There should not be a conductive connection between the screen and the
connector housing !
5. Screw the cable ends and the screen (in the insulated tubing) tightly in the pin
insert
6. Pull the coupling sleeve up to the shrink-on sleeve to screw it tightly in the inside
thread of the pin insert.
7. Push the screening ring with seal into the coupling sleeve.
8. Push the seal, clamp cage and pressure screw up to the screening ring and
tighten the pressure screw by hand
Reference edge for dimensions for cable fitting
Strip the bus cable here
Pull a shrink-on sleeve over the
cable, wires and screen
Pull insulated tubing over the screen or
solder the screen to the wire
Figure 36 Preparing the cable
•
twist shield and pull through the insulated tubing
"
Twist and shorten screen and solder it to the wire
SITRANS P. Series DS III PA
A5E00053276-64
91
EFTA01216808
installation
Figure 37 Components of the M12 bus connection
1311
6
7
1 Double pole field bus cable with screen
dr— 8
2 Pressure screw
3
Clamp cage
4
Seal
5
Screening ring with seal
6 Reference edge for dimensions for cable assembly
7
Thread
8
Coupling sleeve
9 Pin insert for screw terminal connection
10 Inside thread
,
12
11 Fixed knurl
12 Rotating knurled screw
7
9
10
11
_ 7
Front view
of pin insert and
pins
2
1 Thread M12 x 1
2 Positioning lug
PIN
PROFIBUS PA
1
PA+
2
Not connected
3
PA-
4
Screen
Front view
of sleeve insert and
sleeves
1
1 Positioning nut
PIN
PROFIBUS PA
1
PA+
2
Not connected
3
PA-
4
Screen
Middle contact tube is not fitted
Figure 38 Pin assignment
92
SITFtANS P. Series DS III PA
A5E00053276-04
EFTA01216809
Installation
7.5
Turn digital display
if the device cannot be operated in a vertical position you can turn the digital display
to make it easier to read. To do this, proceed as follows:
1. Unscrew the cover from the electronics housing.
2. Unscrew the digital display. Depending on the position of the transmitter you can
screw it back in four different positions (rotated by ±90° or ±180° possible).
3. Screw on the housing cover.
WARNING
Explosion-proof devices may only be opened with the power off.
SITRANS P. Series DS III PA
ASE00053276-04
93
EFTA01216810
installation
SITFtANS P. Serb s DS III PA
94
A5E00053276-04
EFTA01216811
Commissioning
The operating data must match the values specified on the rating plate. The
transmitter is in operation when the power supply is switched on.
8
WARNING
In areas with a potential explosion hazard, the housing cover of transmitters with
the ignition category "Pressure-proof encapsulation" may only be unscrewed when
the device is not energized. If transmitters are to be used as category 1/2 equip-
ment, please observe the examination certificates (enclosed as loose sheets).
The following applies for devices with the common admission "intrinsic safety" and
"explosion-proof" type of protection (EEx is + EEx d). The inapplicable type of pro-
tection must be permanently erased from the rating plate before putting into opera-
tion.
"Intrinsic safety" type of protection is no longer guaranteed in case of an improper
power supply.
The following commissioning cases should be seen as typical examples. Depending
on the system configuration, arrangements differing from these may make sense.
SITFtANS P. Series OS III PA
A5E00053276-04
95
EFTA01216812
Commissioning
8.1
Pressure, absolute pressure from the differential
pressure series and absolute pressure from the
pressure series
WARNING
Incorrect or improper operation of the shutoff fittings (Figure 39, pg. 97) may result
in serious injury or considerable material damage.
When using toxic media, the measuring transducer may not be vented.
SITRANS P. Series DS III PA
96
A5E00053276-04
EFTA01216813
Commissioning
8.1.1
Measuring gases
Operate the shutoff fittings in the following order:
Initial position: all valves closed
1. Open the shutoff valve (2B, Figure 39, pg. 97).
2. Apply pressure corresponding to the start of scale through the test connection of
the shutoff fitting (2) to the transmitter.
3. Check the start of scale and correct it if necessary.
4. Close the shutoff valve (2B).
5. Open the shutoff valve (4) on the pressure tap.
6. Open the shutoff valve (2A).
4
3
2A
28
2
3
4
2A
28
2
6
Transmitter above the pressure tap (normal
Transmitter below the pressure tap (exception)
arrangement)
1 Transmitter
2
Shutoff fitting
A
shutoff valve for the process
B
shutoff valve for test connection or venting screw
3 Pressure pipe
4
Shutoff valve
5
Shutoff valve (optional)
6
Condensation vessel (optional)
7
Drain valve
Figure 39 Measuring gases
SITRANS P. Series DS III PA
ASE00053276-04
97
EFTA01216814
Commissioning
8.1.2
Measuring vapor and liquid
Operate the shutoff fittings in the following order:
Initial position: all valves closed
1. Open the shutoff valve (2B, Figure 40, pg. 98).
2. Apply pressure corresponding to the start of scale through the test connection of
the shutoff fitting (2) to the transmitter,
3. Check the start of scale and correct it if necessary.
4. Close the shutoff valve (26).
5. Open the shutoff valve (4) on the pressure tap.
6. Open the shutoff valve (2A).
6
1
3
2A,
2B
2
1 Transmitter
2
Shutoff fitting
A
shutoff valve for the process
B
shutoff valve for test connection or venting screw
3 Pressure pipe
4
Shutoff valve
5 Drain valve
6
Compensation vessel (for vapor only)
Figure 40 Measuring vapor
98
SITRANS P. Series DS III PA
A5E00053276-04
EFTA01216815
Commissioning
8.2
Differential pressure and flow
WARNING
- If the vent valve and/or the sealing screw are missing or are not tight enough
and/or
— if the valves are operated incorrectly or improperly,
serious injury or considerable material damage may result.
In the case of hot media the individual operating steps must be performed in rapid
succession. Otherwise the valves and the transmitter may be heated up beyond
the permissible limit, leading to damage.
8.2.1
Measuring gases
Operate the shutoff fittings in the following order:
Initial position: all shutoff valves closed
1. Open both shutoff valves (5, Figure 41, pg. 100) at the pressure taps
2. Open the compensation valve (2).
3. Open the active pressure valve (3A or 3B).
4. Check and correct zero point, if necessary, at start of scale 0 mbar.
5. Close the compensation valve (2).
6. Open the other active pressure valve (3B or 3A).
SITRANS P. Series D3 III PA
ASE00053276-04
99
EFTA01216816
Commissioning
2
3B .
3A
Transmitter above the active pressure
Transmitter below the active pressure transmitter
transmitter (normal arrangement)
(exception)
1 Transmitter
2 Compensation valve
3 Active pressure valves
4 Active pressure lines
5 Shutoff valves
7 Blowout valves
9 Condensation vessels (optional)
10 Active pressure transmitters
Figure 41 Measuring gases
8.2.2
Measuring liquids
Operate the shutoff fittings in the following order:
Initial position: all valves closed
1. Open both shutoff valves (5, Figure 42, pg. 101) at the pressure taps
2. Open the compensation valve (2).
3. With the transmitter below the active pressure transmitter open both blowout
valves (7) one after the other, with the transmitter above the active pressure
transmitter open both vent valves (8) slightly until air-free liquid emerges.
4. Close both blowout valves (7) or vent valves (8).
5. Open the active pressure valve (3A) and the vent valve at the high pressure
chamber of the transmitter (1) slightly, until air-free liquid emerges.
6. Close the vent valve.
100
SITRANS P. Series DS III PA
ASE00053276-04
EFTA01216817
Commissioning
7. Open the vent valve at the low pressure chamber of the transmitter (1) slightly
until air-free liquid emerges.
8. Close the active pressure valve (3A).
9. Open the active pressure valve (3B) slightly until air-free liquid emerges, then
close it.
10. Close the vent valve at the low pressure chamber of the transmitter (1).
11. Open the active pressure valve (3A) by 112 turn
12. Check and correct zero point, if necessary, at start of scale 0 bar.
13. Close the compensation valve (2).
14. Open the active pressure valves (3A or 3B) fully.
58
10
5A
4
38
3A
4
78
1
TA
1 Transmitter
2
Compensation valve
3
Active pressure valves
4
Active pressure tines
5
Shutoff valves
7
Blowout valves
10 Active pressure transmitters
12 Gas collectors (optional)
a 4
1 IA
12
Transmitter below the active pressure
Transmitter above the active pressure transmitter
transmitter (normal arrangement)
(exception)
Figure 42 Measuring liquids
WARNING
When using toxic media, the measuring transducer may not be vented.
SITRANS P. Series OS III PA
A5E00053276-04
101
EFTA01216818
Commissioning
8.2.3
Measuring vapor
Operate the shutoff fittings in the following order:
Initial position: all valves closed
1. Open both shutoff valves (5, Figure 43, pg. 102) at the pressure taps
2. Open the compensation valve (2).
3. Wait until the vapor in the active pressure lines (4) and in the compensation
vessels (13) has condensed.
4. Open the active pressure valve (3A) and the vent valve at the high pressure
chamber of the transmitter (1) slightly until air-free condensate emerges.
5. Close the vent valve.
6. Open the vent valve at the low pressure chamber of the transmitter (1) slightly
until air-free condensate emerges.
7. Close the active pressure valve (3A).
8. Open the active pressure valve (3B) slightly until air-free condensate emerges,
then close it.
9. Close the vent valve at the low pressure chamber of the transmitter (1).
10. Open the active pressure valve (3A) by half a turn
11. Check and correct zero point, if necessary, at start of scale 0 bar.
12. Close the compensation valve (2).
13. Open the active pressure valves (3A or 3B) fully.
1 Transmitter
2
Compensation valve
3
Active pressure valves
4
Active pressure tines
5
Shutoff valves
7
Blowout valves
10 Active pressure transmitters
13 Compensation vessels
14 Insulation
78
7A
Figure 43 Measuring vapor
CAUTION
The measuring result is only error-free if the active pressure lines (4) contain
equally high condensate columns of equal temperature. Zero adjustment must be
repeated when these conditions are satisfied.
If the compensation valve (2) is opened when the shutoff valves (5) and active
pressure valves (3) are open simultaneously, the transmitter (1) may be damaged
by flowing vapors!
102
SITRANS P. Series DS III PA
ASE00053276 -04
EFTA01216819
Technical data
9
SITRANS P. DS Ill PA series, for
Application
Mode 04 operation
Measuring principle
Input
Measured variable
Pressure
711F4034
Absolute pressure
Pressure bans-
Did. pressure
mutter series
transm. series
7MF4234
7MF4334
See page 11
See page 13
Pine-resistive
Pressure
Absolute pressure
Differential pres-
sure and flow
714F4434/
714F4534
Level
711F41334
Dilletenbal pes.
sure and flow
Level
~anal measuring range
I to 400 bar
250 mbar lo
250 Mum to
(14.510 5802 psi)
30 bar
180 by
(3.6310 435 psi)
(3.8310 2320 pal)
250 mbar to 5 bar
(3.631072.5 psi)
• Nominal pressure PN 32 (MV.? 464 psi
• Nominal pressure PN 160
WIMP 2320 psi)
• Nominal pressure PN 420
(MVP 6092 psi)
• Lower measuring unit
Measuring cell with snore oil tilling
- 1.4easufing cell with inert Ming liquid
Fee process temperature
-20t<ds60
,C
(-4 'F < Os .140 °F)
30 mbar (0 435 psi)
(abSOlule)
0 mbar (0 Pm) (absolute)
30 mbar (0.435 psi) (absolie)
20 mbar (0.29 pt.)
60 mbar to 30 bar
(0.87 to 435 psi)
200 madras7J bar
(3.63 to 435 psi)
-100%a ~net
measuring range'
or 30 mbar (0.435
psi) (absolute)
-100%04 nominal
measuring range
or 30 mbar (0.435
psi) (absokne)
-100% of nominal
measuring range i)
or 30mó& (0.435
psi) (Muskat)
-100% Cl nominal
measuring range
a 30 mbar (0.435
psi) (abs.) depend.
rig
mounting
Hang.
For process tereperalure
tare< 05 I00°C (max •85
la 30-bar nominal meas. range)
140°F < Os 212°C(crux •185°F
la 435 psi nominal meas. range)
30 mbar (abs.) e 20 mbar
(abs.) (0 - 60 °C)PC
0.435 psi (abs.) • 0.29 psi
(abs.) (0- 108 rf- yor
• Upper measuring trot
100%a OOmnal measuring Mtge (Max 160 bar (2320 psi) with oxygen
measurement and inert lilting !loud)
100%01 ncmnal
measuring range
Output
Physical bus
Independent of polarity
Digital PROFIBUS-PA signal
IEC 61158-2
Yea
11.33%wit nominal measuring range 30 bar (435 psi).
SITRANS P. Series DS III PA
A5E00053276-04
103
EFTA01216820
Technical data
SITRANS R DS II PA series. for
Accuracy
Re f seance cord:ions
Premature
71/F4834
Absolute pressure
Pressure trans-
mitter series
734F4234
Diff. pressure
transm. series
7MF4334
Differential pres-
Level
sure and flow
7MF4634
7MF4434/
7/4F4534
Increashg characteristic. Start•Ol•SCale Sue 0 bar. stairtess Steel seal diaphragm (Wei level:
mourning lenge walnut lube). silicone oil filling and room temperature (25 iC (77 °E))
Error in measurement (ircludng nynere•
sis and repealabrity)
• Linea? chaiactenstic
Square
-root characteristic
Roe
ROe 25 to 50%
• Repealabirty and hysteresis
Response time
IT62 Shod abeam dancing)
Approx 025
S0.1%
S 0.1%
s 0.2%
Included In error in measirement
Approx. 025
Approx. 0.2 St
approx. 0.3 s with
20-and 80-mbar
(0.29 and 0.87 psi)
nom. meas. range
s 0.2% per yen
S0.25% per S yews.
max. static pressure Mbar (1015 psi)
s 0.15%
Approx. 0.2 5
Long-term din (change in le.nperalure
s 025% per 5
230 iC (254 °F)
years
• 2o/flaw an psi) nom. inns range
Ambient temperature Ow
• At -1010 4.30 t(l4 to 140'F)
- 250-mbar (3.83 psOnan. meas. rangt
800-mbar (87 psi) nem, meas range
5 0.2% pet year
5 0.7%
50.5%
SOAS%
- 1000- and 5,0WInbw (23.210
72.5 psi) nominal menth) range
• At .40 lo -10 IC and .8010 .85 IC
(-40 to .14 'F and 14010 185 'F)
- 250-mb:0(3.8300)nm. meas. rang
800-mbar (a 7 psi) nom. meas range
5025% / 10 K
s 0.25% / 18 I FI)
S 0.491/10 K (18 IF)
a3%/bo K
<F)
- 1000- and5,000-mbar (23.2 to
72.5 psi) inning ineaSuri1g range
s 0.27%!
10 K (18 IF)
Influence 01 Slit pressure
• On elart-intiCale
s 0.15% per
:Mbar (1450 pal)
S0.15% per 32 bar
(464 psi)
- 20-rnbar 10.29 psi)ncennal measuring
range
- 250-mbar (3.83 psi) nornhal measur-
ing range
5 0.3% per nom.
pressure (PN)
s 0.15% per nem
pressure (PM)
50.1% per nom.
pressure (PN)
0.1% per nom.
pressure (PM)
130Ornbar (8.7 psi) nonnalmeasuring
range
- 1003- and 5.000ffibw (23.2 to
72.5 psi) Maine measurhg range
• On span
502% per 100 bar
(1450 psi)
502% per 32 bar
(484 pal)
- 20-Mbar (0.29 psi)ndrinalmeaswIng
range
Influence Cl mounting positron
Resolution
Rated operating conditions
Installation conditions
• Installation instructions
Ambient conditions
• Ambient INTO. (ObSeme leaMeratire
clan in potentially expl. abneripheren
50.05 Mbar (S0.000725 psi) per lir inch
50.7 mbar (s0.001015pS0 per 10' nth-
nation (Can be Corrected using Zero CM- nation (Can be Corrected using 2er0 COI
shag)
faction)
3 108 -4 nominal measuring range
Dependent on fill-
ing liquid in mount.
ing flange
Process cain. pointing yen. downwards'
Any mounting position
Defined by flange
• Measuring cell Arch silcore Olt MN
-4010 *85 • C (-40 to .185 °F)
30-bar (435 psbnOnInalnleaSurIng
range
-40b.85 C (-4016+185'FI
(-20 03 +NTH to •185 ")w41714534)1
Measuring cell with inert filling amid
- Digiln creplay
• Ambent )emperause limits
• Storage leMpealure
-2010 485'C (-4 10 4185'F)
-3010 .15°C (-2210 •135 °F}
See arnbieni remperause
-50 to •86
(-58 to •185 °F}
104
SITRANS P. Series DS III PA
A5E00053276-04
EFTA01216821
Technical data
SITRANS P. DS Ill PA series. for
• arrive clan--
Pressure
Absolute pressure
TIAF4034
Pressure trans-
Dill. pressure
meter series
transm. series
j 781F4234
781F4334
Differential pees-
Level
awe end flew
714F4834
7h1F4434/
?Wale
- Condensation
P m ssbe
• Degree of prowden (lo EN 60 529)
II' 66
• Electromagnelic compalibiley
Ernilted wierlerence
16 EN EC G61-1
- Noise érinUflily
To EN 61 326 and NAMUR NE 21
Medlin cone:item
• Process temperakse
Measuring cell with silicone al filing
-40 te .100
(-4010 .212 90
Highprees. side:
see «men° flange
Low-press. side:
-4010 •100°C(-40
lo .212 °F)
30-bar (435 ps)norn. mess. range
-4010 485'C (-1010 •185
(-20 to .85 °C (-4 to •185 'F) for
71.4F4534)
Messwirw cell with inert hung liquid
-20Io 4100 'C (.4 to .185 `F)
30-bar (435 p&) nom. meas. range
-20 to *85 °C (-4 to •185 °F)
• Process temperature Ines
See Process iarpeialue
• Ms enum *eking pressure
See page 110
Nominal pressure (PH)
Design
Weight (without options)
Approx. 1.5 kg (3.3 lb)
Approx. 4.5 kg (9.9 lb)
• To DIN (Serene» wM mounling
flange, %Shaul tube)
APPrev
11 to 13 kg
(24.21028.7 lb)
• To ANSI (transmiller with moureng
'range. votreul tube)
APPler
11 fo 18 kg
(24,21039.21b)
Cenensians
Miterial
See Fig. 44
See Rg. 45
I See Rg. 48
See Rg. 47
• Wetted parts maltase&
Connector, shank
Stainless sleet, mal. N0. 1.44041316k o
liastelloy C4, rreL No. 2.4610
- Oval flange
Stainless sleek mal. eb. 14404/318L
Seal diaphragm
Stainless steel mat. No. I.4404/31EL o
Hasletoy 0276. mal. No. 2.4819
Slainless steel. mat. No. 1 4404/316L,
HasleToy C276. mal. No 2 4810 Monet.
mal. No. 2.43€0. tantalen a geld
- Process flanges and
seeing scree
St. sleet, nits. No. 1.4408 up to PH 160
(lAWP 2320 psi). mal. No. 1.4571/318Tî for
PH 420 (keNP 6092 psi).Haselloy C4. wel.
No. 2.4610 or Monet mal. No. 2.4360
0 -ring
FPM (Korn) or as option.
PTFE. FEP. FEPM and NBA
- High-wessure side
Seal diaphragm ol mounting flange
Stainless sleek
mat No. 14571!
31611, Mewl 400.
mat No. 2.4380.
HaslelbyB2. mar
No. 2.4817.
Hasletoy 0278.
mat No. 2.4819.
Hasletoy CA. mal.
No. 2.4810. we.
lurn. PTFE ECTFE
Seale lace
Smooth to DIN
2528 lorm D of
ANSI 616.5 RF tor
stainless sleet. mal.
No. 1.4571/3167i.
DIN 2526101m E or
ANSI 616.5 RFSF
log oint materials
Sealing rraHnal in the process flange
For slandard applications
Vilon
For vecuLen applcanon of mourn-
eg flange
Copper
SITRANS P, Series DS III PA
A5E00053276-04
105
EFTA01216822
Technical data
SITRANS P. DS III PA series. for
Pretense
714F4034
Absolute pressure
Pressure trans-
Dill. pressure
miner series
transm. series
7MF4234
7MF4334
Differential ores-
sure and flow
7MF4434/
7MF4534
Level
7MF4834
- Low-pressure side
Seal dePTFa9m
Stainless steel.
1.4404(31GL
Process flanges and
sealing screw
Stainless Meet
matte,. 14408
Ohing
FPM (Venn)
• Nan-welled parts material
- Electronics neuter)
Die-cast akiminium. ow in copper, GD-ALSi 12, Cr stainless steel precision casting,
polyester-based leeches stainless steel rating plate
- Process flange screws
I
Steel. galvanized and yellOmpassiyeed. Or stainless steel
- Mounting bracket (Option)
Steel, galvanized and yellmopassiNzed, Cr skinless steel
Measuring cell Ming
Silicone of or inert filling livid (max. 160 bar (2320 psi) with oxygen measurement) Silicone oil
• fl ung liqdd of mounting Ilange
Silicone oil Cr other
material
Process connection
Conviction shark GSM to DIN EN837.
fermate thread Y.- 14 NPT d Oral Range
(PH 160 (MVP 2320 ph)) to DIN 19 213
sith mooning thread M10 or 7/18.20 UN
Female thread I4 - 18 NPT and
range comectbn to DIN 19213 with
mounting thread MI00412 ler PN 420
(IMP 6092 psi)) Cr 7/16-20 UNF
• High-pressure side
Flange to DIN and
ANSI
• Low•pressue side
Female thread 11 •
IS NPT and flange
connection to DIN
19 213 with moan!.
ing thread h110 or
7/16•20 UNF
Beelike' OCOneeliOn
Screw terminals. cable Mel via screwed gland
M20 x 1.5 or fii - 14 NPT, or FROFIBUS plug Ill12
Displays and controls
Input keys
3 for local programming direclly on tranwnater
Built-h. cover wilh window (phony
Power supply (14)
Separate 24 V power supply necessary
Supplied via bus
No
Bus voltage
• No:Ex
9 to 32V
• With inhinsicaly-safe operation
Bin 24V
Current consumption
• Basic current (max.)
125 mA
• Starling current 4 baste curreN
Yes
• Max. cwrent in eveM of %sit
15.5 rte
Fain disconnection electronics (FDE)
Present
Yes
Cerlifkahva and approvals
Classificatim accordig to pressure
equipment diective (OGRL 97)23/EC):
711F4034. 7MF4234, WM34. 7IAF4434, 71/F4634
For gases of fluid group 1 and liquds of Iliad 1. complies with requirements of
anicle 3. paragraph 3 Mound engineering practice)
71.1F4534
For gases of ?kid group 1 and liquids of Iliad group 1; complies with basic safety requirements 01
article 3. paragraph 1 (appends 1): assigned to category III.
conformity evalumpn module H by the TIN Nord
Explosion protecte-
• tracheae &Slaty T
FIB 96 ATE( 2122
- Identification
G ii 112G EEx is 'IC T8
- Permissble ambient temperature
-40 'C 10 .85 'C (-40 to +185 ,F) temperature date T4, .60 °C (.140°F) idrperalwe class T43
- Connection
FISCO sipory NM a U, s 24 V linear
- Eflective internal induclancekapactafice
Lf 510 pH/CI 55 if
• Explosion-prod IC
PTB 93 ATEX 1160
- IdeniMcalidi
Gil 1# G EEx d IC T4 /TB
- Permeable ambient temperature
-40 'C 10 .85 'C (-40 to +185 'F) temperature class T4. +60 °C (.140°F) temperature class TO3
• Typed protection In* (zone 2)
named
- Identilication
- Perrrimble ambient temperature
- Connection
106
SITRANS P. Series DS III PA
A5E00053276-04
EFTA01216823
Technical data
SITRANS P. DS III PA series. for
Certificates and approvals
(continued)
• Explosion protection to FM
Pressure
7MF4034
Absolute pressure
Pressure trans-
Dill. pressure
miner series
transm. series
7/.1F4234
7MF4334
Differential Ares-
Level
sure and flow
7MF4634
7141FaCar
71.1F4534
- Identification (XP/DIP) or (IS): (NI)
CL I. DIV I. GP ABCD T4...T6: CL II. ON 1, GP EFG; CL III:
CL I. ZN ON AEx ia IIC
CL I. DIV 2. GP ABCD T4...T8; CL II, ON 2, GP FG; CL III
Pemissrbse amPent temperate
Ta - T4 -40 to 85 °C (-40 to I-185 1F). T5 40 to 701F 1.4010 158'F), T6: .40 to 60 °C (.40 to 140 °F)
- Entity parameters
According to control drawing A5E00116127A:
U0•30V.4.1COrnA,P,.750mW.N.3000.1i.0.4mH,C.Bnr
• Explosion protection so CSA
- Identification (XP/DIP) or (IS)
- Perrnssrbse ambient temperature
Planned
- Entity parameters
Communkallon
Smullareouscommalicationwithrnaste4
Class 2 (max.)
Address settim possible ushg
CyCliC uSelut data
• Output bytes
• Input bytes
Internal preprocessing
Cevice profile
Function blocks
• Ando° input
Car/ovation tool or local operation (Standard setting: oddest 126)
5 (one measured value) or 10 gyro measured values)
0 1 or 2 liolaszer mode and reset Curti:on for dosing)
PROFIBUS•PA polite for process control devices version 3.0. class B
2
- Adaptation to applcalion•spectlic
process variable
Yes. linear 'nog d Wing Characteristic
Electric damping Te3 atkuStable
- Simulation lunCtiOn
Failure response
- Limit monitoring
• Totalizer
0 to IODs
Outpuliblpul
Pararrelerizable (Iasi correct value. default value. tautly value)
Yes. upper as lower warring Writs. upper and loner alarm Writs
Can be reset and preset
Selectable counting direction
SONIalico fLoction of totalizer output
- Failure response
Paranwtenzable (adding with last cared vakre, stop adding,
adding with faulty value)
Upper and lower warring limits. upper and totter alarm limits
1
2
- Lmt mOntOring
• Physical block
TrartsdoCer blocks
• Pressure transducer block
CalbeatiOn by appliCebta 01 Iwo
pressures
- Monitoring 01sensor Writs
Delinticn of vessn characteristic
Yes
Yes
Using max. 30 interpolation pants
- Square-root characteristic Mr flow
MeaSureellent
LOw-Iltro Cutoff and appecation pNnt
01 square-r00919
- Simulation function
Pressure value
Yes
Par Weer OSA
Constant value or using paravieenzable ramp lurctiOn
Conslanl value or useig pararnmerisable maw lonelier)
Sensor temperature
SITRANS P. Series DS III PA
A5E00053276-04
107
EFTA01216824
Technical data
9.1
Nominal measuring ranges and overload limits
9.1.1
Pressure
Nominal measuring range
max. perm.
max. perm. test
operating
pressure ")
pressure ps,
1 bar
=
100.0 kPa
4 bar
=
400.0 kPa
16 bar
=
1.6 MPa
63 bar
=
6.3 MPa
160 bar
=
16.0 MPa
400 bars)
=
40.0 MPa')
1) for oxygen measurement max. 160 bar
•) according to 97/23/EG pressure transmitter regulation
") according to DIN 16086
9.1.2
Differential pressure and flow
4 bar
7 bar
21 bar
67 bar
167 bar')
400 bar')
Nominal pressure
Nominal measuring range
PN 32
20 mbar
=
2
kPa
PN 160
60 mbar
=
6
kPa
PN 160
250 mbar
=
25
kPa
or
600 mbar
=
60
kPa
PN 4201)2)
1600 mbar
=
160
kPa
5000 mbar
=
500
kPa
30000 mbar
=
3000
kPa
1) for oxygen measurement max. 160 bar
2) measuring cell filling oNy silicone oil
3) not suitable for remote seal mounting
6 bar
10 bar
32 bar
100 bar
250 barn
600 bail)
SITRANS P. Series DS III PA
108
A5E00053276-04
EFTA01216825
Technical data
9.1.3
Absolute pressure from the pressure series
Nominal measuring range
max. perm.
operating
pressure pe)
max. perm. test
pressure •*)
250 mbar
=
25.0 kPa
1.5 bar
6 bar
1,300 mbar
=
130.0 kPa
2.6 bar
10 bar
5,000 mbar
=
500.0 kPa
10 bar
30 bar
30,000 mbar
=
3,000.0 kPa
45 bar
100 bar
1 according to 97/23/EC pressure transmitter regulation
**) according to DIN 16086
NOTE on 250 mbar cell
III&
D See above...
9.1.4
Absolute pressure from the differential pressure series
Nominal measuring range
Overload limits
250 mbar
=
25.0 kPa
32 bar
1.300 mbar
=
160.0 kPa
32 bar
5.000 mbar
=
500.0 kPa
32 bar
30.000 mbar
=
3.000.0 kPa
160 bar
100.000 mbar
=
10,000.0 kPa
160 bar
NOTE on 250 mbar cell
This measuring cell is designed for operation within the measuring limits 0 mbar
(absolute) to 250 mbar (absolute). When stored under normal ambient pressure of
around 1000 mbar (absolute) the measuring cell is in the overload state. An
overload error may occur as a result. The overload error disappears in operation
within the measuring limits. The transmitter then operates to its specification again,
although the start of scale may have to be readjusted.
In pressure measurements with repeated exceeding of the measuring limits (e.g.
batch processes with transitions between vacuum and ventilation) a measuring
cell with a maximum range of 1300 mbar should be selected to avoid overloading.
SITRANS P. Series DS III PA
A5E00053276-04
109
EFTA01216826
Technical data
9.1.5
Filling level
Nominal measuring range
Nominal pressure
250
mbar
=
25.0
kPa
PN 16 or PN 40
600
mbar
=
60.0
kPa
1600
mbar
=
160.0
kPa
5000
mbar
=
500.0
kPa
9.2
Dimensions
IS
65
135(5e
Wet 9011 2) 4-1WPM)
65(3281_,j
_..
2
3
2
A
1 Process connection:
6
Protective cover over keys
-14 NPT (63 bar (914 psi) and above, wrench size 36)
7
Mounting bracket (option)
connection shank G1/2A or
oval flange
9
Screw cover safety bracket (only for explosion-
proof enclosure, not shown in the drawing)
2 Blanking plug
3 Electrical connection:
2) Allow approx. 20 mm (0.70 inch) TM + CSA pa+ xp)'
Not with type of protection 'Explosion proof enclosure"
screwed gland M20 x 1.5,
3) Not with type of protection 'FM + CSA [is + se)'
screwed gland Yi — 14 NPT or
a) Approx. 45 mm (1.77 inch) (for Pg 13.5 with adapter)
PROFIBUS plug M12 2)31
5) MilllITIUT distance for rotating
4
Terminal side
5
Electronics side. digital display (longer overall
length for cover with window)
Figure 44
Dimensions of DS Ill PA series for pressure and absolute pressure from pressure transmitters
series, dimensions in mm (inches)
110
SITFtANS P. Serb s DS III PA
A5O0053276-04
EFTA01216827
Technical data
1 Process connection %-18 NPT (DIN 19 213)
9
Screw cover safety bracket (only for explosion-proof
2 Blanking plug
enclosure, not shown in the drawing)
3 Electrical connection:
10 Side ventilation for liquid measurement
screwed gland M20 x 1.5
screwed gland 'A - 14 NPT or
PROFIBUS plug M12 2)3)
11
I)
2)
Side ventilation for gas measurement (additive H02)
Allow approx. 20 mm (0.79 inch) thread length et addition
Not with type of protection 'Explosion proof enclosure'
4
Terminal side
3) Not with type of protection 'FM + CSA (e • xpl"
5
Electronics side. digital display (longer overall
length for cover with window)
4)
51
92 mm (3.62 inch) for minimum distance to permit rotation
without ex:fiesta
201.5 mm (79.3 inch) for PN 2 420 (MWP 2 6092 psi)
6 Protective cover over keys
6) 54 mm (2.12 inch) for PN 2 420 (MWP 2 6092 psi)
7
Mounting bracket (option)
7)
Approx. 45 mm (1.77 inch) for Pg 13.5 with adapter
8 Sealing screw with valve (option)
Figure 45
Dimensions of OS Ill PA series for differential pressure and flow as well as absolute pressure
from differential pressure transmitter series, dimensions in mm (inches)
SITRANS P, Series DS III PA
A5E00053276-04
111
EFTA01216828
Technical data
sg
67 13.645'
en nes
ws"3O11
3
3
100 i33t)
6
1 Process connection '/.-18 NPT (DIN 19213)
I) Mow approx. 20 mm (0.79 inch) thread length in addition
2
3
Blanking plug
Electrical connection:
screwed gland M20 x 1.5 or
2)
3)
4)
Not
type
Tato
with
of protection
proof enclosure'
Not with type of protection "FM + CSA (is + xpr
92 mm (3.62 inch) for minimum distance to permit rotation
without indicator
screwed gland 'A - 14 NPT or
5)
74 mm (2.9 inch) for PN 2 420 (MWP z 6092 psi)
PROFIBUS plug M12 2)31
6)
7)
91 mm (3.6 inch) for PN 2 420 (MWP z 6092 psi)411
219 mm (8.62 inch) for PN 2 420 (MWP z 6092 psi)
4
Terminal side
II)
Approx. 45 mm (1.77 inch) for Pg 13.5 with adapter
5
ElectroNcs side, digital display (longer overall length
for cover with window)
6 Protective cover over keys
7 Mounting bracket (option)
8 Sealing screw with valve (option)
9 Screw oover safety bracket (only for explosion-proof
enclosure, not shown in the drawing)
Figure 46
Dimensions of DS Ill PA series for differential pressure and flow as well as process covers for
vertical differential pressure lines (order using Order code "H03"), dimensions in mm (inches
A special half flange is available for better reading of the SITRANS P,
Series DS Ill PA transmitter's digital display. It is a particular advantage when moun-
ting the transmitter on a valve manifold with vertical active pressure lines.
SITRANS P. Seri0s DS III PA
112
A5E00053276-04
EFTA01216829
Technical data
1 Process connection 'A-18 NPT (DIN 19213)
Mow approx. 20 mm (0.79 inch) thread length in addrtion
2
3
Blanking plug
Electrical connection:
screwed gland M20 x 1.5 or
2)
3)
4)
Not with type of protection 'Explosion proof enclosure'
Not with type of protection "FM + CSA (is + xpr
92 mm (3.62 inch) for minimum distance to permit rotation
without indicator
screwed gland 'A - 14 NPT or
5)
Approx. 45 mm (1.77 inch) for Pg 13.5 with adapter
PROFIBUS plug M12
4
Terminal side
5
Electronics side, digital display (longer overall length
for cover with window)
6 Protective cover over keys
8 Sealing screw with valve (option)
9 Screw cover safety bracket (only for explosion-proof
enclosure, not shown in the drawing)
Figure 47
Dimensions of DS III PA series for level (transmitter including mounting flange), dimensions in
mm (inches)
SITRANS P, Series DS III PA
A5E00053276-04
113
EFTA01216830
Technical data
1 Process connection 'A-18 NPT (DIN 19213)
2 Blanking plug
3 Electrical connection:
screwed gland M20 x 1.5 or
screwed gland 'A - 14 NPT or
PROFIBUS plug M12
4
Terminal side
5
Electronics side, digital display (longer overall length for cover with window)
6 Protective cover over keys
8 Sealing screw with valve (option)
15 External digital indicator (option)
2)
Not with type of protection 'Explosion proof enclosure
3)
Not with type of protection 'FM • csmis• xpl'
Figure 48
Dimensions of DS Ill PA series for differential pressure and flow as well as digital display
beside input keys (order using Order code -027"), dimensions in mm (inches)
SITRANS P, Series DS III PA
114
A5E00053276-04
EFTA01216831
Care and maintenance
The device's zero point should be checked from time to time.
In the event of a fault decide:
•
whether the internal self-test has detected an error,
e. g. sensor breakdown
Displays:
digital display: Display 'ERROR"
- PROFIBUS: B_016: Sensor error
Diagnosis: Measured value recording error
•
serious hardware error the processor is not working
Displays:
digital display: no defined display
- PROFIBUS: Slave not available
10
In the event of a fault you can exchange the electronics as described in chapter 6,
pg. 79 under consideration of the warnings.
SITRANS P. Series DS III PA
ASE00053276-04
115
EFTA01216832
Care and maintenance
SITRANS P. Series DS III PA
116
A5E00053276-04
EFTA01216833
PROFIBUS
11
The PROFIBUS-PA(PA = Process Automation) is a variant of the PROFIBUS DP
(DP = Decentral Peripheral) which is widely used in manufacturing engineering.
The PROFIBUS (Process Field Bus) is an open communication system for
automation engineering and thousands are used all over the world. It is specified in
the European standard EN 50170.
11.1
Transmission method
The PROFIBUS PA has a special transmission method and therefore satisfies the
requirements of process automation and manufacturing engineering. This
transmission method is defined in the international standard IEC 61158-2. The low
transmission speed reduces the power loss compared to the PROFIBUS-DP and
therefore enables an intrinsically safe technique for use in hazardous areas.
11.2
Topology
The bus topology can, to a large extent, be freely selected so that line, star and tree
structures are possible, as well as mixtures of these. All kinds of field devices such
as transformers, actuators, analyzers, etc. can be connected to the PROFIBUS PA.
SITFtANS P. Series DS III PA
ASE00053276-04
117
EFTA01216834
PROFIBUS
The main advantage is in:
•
the saving of installation costs
•
the possibility of more extensive diagnostics with an increase in the availability of
system parts
•
the possibility of automatic tracing of system documentation
•
the possibility of system optimization in operation
In an automation system, several PROFIBUS PA channels are usually connected to
the fast PROFIBUS-DP with coupling units. The process control system is also linked
to this.
Both bus systems use a uniform protocol layer. This makes the PROFIBUS PA a
communication-compatible extension of the PROFIBUS DP into the field.
Figure 48 Typical PROFIBUS automation system
Figure 48 shows the section of a typical PROFIBUS automation system. The control
system consists of two masters with distributed tasks.
The class 1 master looks after the control and regulation functions, while the class 2
master enables operating and monitoring functions. A cyclic exchange of measuring
and setting data takes place between master 1 and the field devices. Parallel to this
data, the status data of the field devices is transmitted to and evaluated in the class
1 master. No field device parameters are set or other device information read during
cyclic operation.
The information necessary for establishing communication is available to the control
system from the stored, device-specific device master data (GSD) files (available on
the Internet at http://www.ad.siemens.de/csi_e/gsd).
118
SITRANS P. Series DS III PA
A5E00053276-04
EFTA01216835
PROFIBUS
One or more class 2 masters can access the field devices acyclically in addition to
the cyclic mode. With this communication type further information can be fetched
from the devices or settings made in the devices.
11.3
Properties of the PROFIBUS PA
The PROFIBUS PA enables bi-directional communication between a bus master and
the field devices via a shielded two-wire line. At the same time the power is supplied
to the two-wire field devices on the same lines.
11.3.1 Profile
Supplementary to the EN standard 50170, the PNO (PROFIBUSUserorganisation)
has defined the functionality of the individual field device types in a so-called profile
description. This profile defines minimum functional requirements and optional
extensions. The device-internal "Device Management' supplies all the basic
information necessary for finding the profile parameters to the control system
configuration tool. With this, a parametering tool can operate all profile-conforming
devices regardless of type and manufacturer.
Depending on the size of the system and thus the number of field devices and the
required timing, the system must be implemented with one or more PROFIBUS-PA
channels. A PROFIBUS PA channel consists of the components shown in Figure 49.
SITRANS P. Series DS III PA
ASE00053276-04
119
EFTA01216836
PROFIBUS
Control room
Field
PROFIBUS-DP
PLS, PC
Couple
Power
supply
Terminating resistor
FD
Field device
PC
Personal Computer
PLS
Process control system
PROFIBUS-PA
T
additional cable
FD
FD
termination
Figure 49 PR0FIBUS-PA architecture
11.3.2 Interfacing
The central process control system PLS or, in the case of low requirements, a PC, is
responsible for the control.
As a rule the signal conversion DP/PA, bus feeding and bus termination functions are
combined in a coupling module. Depending on the number of PROFIBUS-PA field
devices to be operated in the automation system and the required timing, a DP/PA
coupler or, in the case of higher requirements, a more powerful DP/PA link is used.
An additional terminating resistor T must be fitted at the far end of the bus for
transmission-technical reasons. When using the recommended bus cable, the
theoretically possible line length (sum of all line sections) is a maximum of 1900 mm.
In addition, the voltage drop over the lines supplying the field devices must be taken
into account in the planning.
However, the current requirements of the individual users and voltage drop on the
cable must also be taken into account in the planning. The individual field devices FG
can be connected almost anywhere in the bus system. Further information can be
found in the "PROFIBUS PPNO Guide A" (see chapter 13.1, pg. 137 /1/).
DP/PA-coupler or DP/PA-Link are supplied by a power supply unit with SELV (Safety
ExtraLow Voltage). This power supply must have adequate reserves for bridging
brief power failures.
The maximum number of devices that can be connected to a bus channel depends
on their current consumption and the respective conditions of use. When operating
in a safe area, the couplers/links can feed up to 400 mA into the bus.
SITFtANS P. Series DS Ill PA
120
A5E00053276-04
EFTA01216837
PROFIBUS
For operation in areas at risk of explosion, inherent safety is only guaranteed if all
devices, components etc. (e.g. bus terminal) connected to the bus are certified as
inherently safe equipment and meet the requirements forming the basis of the FISCO
model (Field bus Intrinsic Safety Concept). In particular, supply devices (bus
couplers) must be certified as so-called FISCO supply devices. The safety
regulations on maximum values and other specifications in the EU type test
certificate must be observed in every case.
Supply devices (bus couplers), which are not explosion-proof and certified, must be
connected to inserted EX-certified Zener barriers. The specifications in the EU type
test certificate must be observed.
WARNING
Only supply devices (DP/PA couplers or DP/PA links) certified according to the
FISCO model may be used to supply inherently safe PROFIBUSes. With non EX-
proof supply devices, Zener barriers must be inserted. The requirements can be
found in the EU type test certificate PTB 99 ATEX 2122, 2nd supplement (see
chapter 13.3, pg. 142).
The number of devices which can be connected to a bus channel can be determined
from the maximum current consumption of the devices connected (according to stan-
dards -10 mA per device) and the available current. A current reserve should be
planned for safety reasons, otherwise there is a risk that a defective device could
overload the bus with its increased current consumption and the power supply and
communication with all unaffected users could collapse. The power reserve quantity
depends on the current increase in the event of an error specified by the manufac-
turer.
Every device has its own address to distinguish between the connected process
devices. Address setting is described in chapter 4.2.8, pg. 54.
Further information about components, design guidelines and planning can be found
in the System Description, Field Technology (see chapter 13.1, pg. 137, /2/).
SITRANS P, Series DS III PA
ASE00053276-04
121
EFTA01216838
PROFIBUS
SITFtANS P. Serb s DS III PA
122
A5E00053276-04
EFTA01216839
Ordering Data
see following page
12
SITRANS P. Series DS III PA
ASE00053276-04
123
EFTA01216840
Ordering Data
12.1
Ordering data for basic device
Ordering data
Order No.
Ordering data
Older code
SITRANS P transmitter for pressure.
TIAF4034-
Further designs
OS III PA series
BEM.
♦ AA
Pease add 2' to Order No. and specify Order code(s).
Mess. cell tilling Meas. cell cleaning
Transmitter with mouning bracket made of
Silicone cil
Normal
1
Ilan liquor
Grease-lree
3
• Steel
A01
I
• Stainless steel
A02
Nominal measuring range
I bar
(14.5 psi)
Rating plate inscription (instead of German)
B
4 bar
(58 psi)
C
• English
B11
16 bar
(232 psi)
D
• French
B12
63 bar
(914 psi)
E
160 bar
(2320 psi)
F
• Spanish
B13
400 bar
(5802 psi)
a
• Italian
B14
Wetted parts materials
English rating plate. pressure unts n FnH20 or psi
821
Seal diaphragm
Process connection
Manulactisers test cerolibme M to DIN 55 350. Part t8
Stainless Steel
Stainless steel
A
and to ISO 8402
C11
Hastens,
Stainless steel
Acceptance test condom° B to EN 10 204-3.1 B
C12
Hastelloy
Handley
C
Factory certificate to EN 10 204.2.2
C14
Version fa remote seal
YO
B
007
Acid gas version to NACE
Process connection
• Connection shank OhA
0
(only together with sew diaphragm made of Haste o,
D12
IP 68 (not together with PROFIBUS plug M12)
• female thread
- 14 NPT
Opts indicator beside control keys
027
• Oval flange made of mariless med.
max. span 160 bar
7
(onlh1F4034 -
y with transrneter
MMN01.2A
7MF403
7-1.
Y
0IIIII0.11AM 6 Of
7
N
4-
21)
Moulting thread 1/7(.- 20 UNF
Mciaiting thread M10
3
E01
Use ma on zone ID/a) (only together with basic
deuce cm, type of protection 'Intrinsicaty-sate')
Non-wetted parts materials
Use In zone0 (basic unit EEx ia)
E02
• Housing made of die-cast aluminum
• Housing main_ steel precision casting
0
3
EIO
Oxygen application (max. 160 bar (2320 psi) with oxy.
gen measurement and inert lilting liquid)
Design
Additional Information
• Standard version
• International version (available soon).
Please add 'Zs to Order No. and specify Order code(s)
and plain text.
English label inscriptions. documerea.
ten in 5 languages on CO
Ideasurng-point numberadentifcation
(max. 16 characters). specify in plain text.
Explosion protection
Y1S: —....--- -----------
.
Y15
• Without explosion protection
A
Measurng-pant text (max. 27 characters).
specify in plain text.
• With explosion protection (CENELEC)
Type of protection.
- 'Intnnsic safety' (EEx
Y16.
Y18
- 'Explosion-moot (EEx d) 1)
- 'kunst safety and explosion-proof
Setting fa dgital display.
specify in plain text (standard setting: mbar).
(EEx a and EEx d) 1) (planned)
- 'n' (zone 2) (planned)
P
Y21: mbar, bar, klse, Mee, pal, .-
Y21
• With explosion protection (FM • CSA)
- intrinsic safe and explosion-proof
Note: only pressure dimensions (see page
51) can be selected.
(Is • xp)
(planned)
NC
S
Preset bus address.
specify in plain text (standard setting: 126).
Electrical connectIoNcable Inlet
• Screwed g'and SA20 x 1.5
B
Y25
• Screwed grand 'I; 14 NPT
C
Only the setting for 72r and 725' can be made in the factory.
• PROFIBUS mug 1.1122)
F
Example for ordering:
Indicator
• Without indicator (digital display hid.
den)
Item lire
7k1F4034-1EAC0-1AA7-2
line
A01 • Y21
C tine
Scope of delivery: Tiansrnuer as ordered Instruction Manual is extra
• With indicator (digital display steatite)
ordering item (see accessories on page 135)).
• With indicator (digital deplay steatite
setting as specified. Order code Y21
required)
SITRANS P. Series DS III PA
124
A5E00053276-04
EFTA01216841
Ordering Data
Ordering data
Order No
STUNS P transmitter for absolute
pressure. from pressure transmitter
series.
DS II PA series
Meas. co-Jelling Meas. eel cleaning
Silicone ol
Normal
Inert liquid
Grease-free
Nominal measuring range
250 mbar
(3.63 psi
1.300 mbar
(18.9 psi
5030 wear
(72d psi)
30.000 mbar
(435 psi)
Wetted parte materials
Seal diaphragm
Process connection
Starriest steel
Stainless steel
Hastelloy
Stainless steel
Has‘elby
Version or remote seal )
Process connection
• Cameo-ion shank Grid.
• Female thread Y. - 14 NPT
• Oval Range made of starless steel,
max span 160 bar (2320 psi)
- Mounting thread
20 UNF
- Mounting thread M10
Neo-waled parts meledele
• Houseig made of die-east eJurninium
• Houseig stainl. steel precision casting
Design
• Standard version
• International version (available soon).
English label inscriptions. dscumenta.
lion in 5 languages on CD
Explosion protection
• %Milo-et explosion protection
• With explosion protection (CENELEC)
Type of prolectoso-
'Intrinsic salety (EEx ia)
Explosion-proof' (EEx d) 2)
'Intrinsic saleiyandexplosiso-proor
(EEx ia and EEx d) 2) (planned)
W (zone 2) (planned)
• VAth explosion pro-do-co (FM • CSA)
intrinsic sale and explosco-prool
(is • xp) 2) (Planned)
Electrical conneclionkable Inlet
• Screwed gland M20 x 1.5
• Screwed gland 'A 14 NPT
• PROFIBUS plug M12 3)
Ineliselor
• Without nitro-or (digital display hid-
den)
• With imitator (digital display visible)
• With indicator (digital display visible.
seteng as specified. Order code V21
required)
SITRANS P, Series DS III PA
A5E00053276-04
71AF 234 mom.
•
D
F
G
A
B
Yo
0
2
0
3
A
8
NC
D
P
E
C
F
B
Ordering data
Further designs
Plea:* add '2' to Order No. and specify Order code(s)
Tr aro-nue; with moaning bracket made of
• Steel
• Starless steel
Ruing plate inscription (instead of German)
• English
• French
• Spanish
• i ratio-I
English rating prate pressure knits in int le0 or par
Manufacturers test certificate M to DIN SS 350. Part 18
and to ISO 8402
Acceptance test caribou& B to EN 10 204.3.1 B
Factory certificate to EN 10 204-2.2
Acid gas version to NACE
(only together with seal diaphragm made of Hast luv
IP 68 (not together with PROFIBUS plug M12)
Digital indicalor beside control keys
(only with transmitter 7MF4234-111IWW3-EAM6 or
7MF4234-MENWO-OV.07-2. Y2I)
Use in or on zone 10/20 (only together with basic
device with type of protection Infrinsieally-We')
Use ki zone 0 (bask tail EExia)
Oxygen application (max. 160 bar (435 psi)with oxygen
measisement and inert filing liqud)
AdeNbonal Information
Please add l'2* to Order No and specify Order code(s)
and plain text
Mean/ins:4point numberAdentilicalion
(max. 16 characters). specify ri plain text:
Y16: -----------------
.
Meastring-poim text (max. 27 characters).
specily in plan text:
Y16: -------------------
Sating for dgilte display. specify in plain text
(standard setting: mbar):
Y21: mbar, bar. Va. MPai --
Nola: only pressure dimensions (see page
51) can be selected.
Preset bus address. speedy n plain text
(standard setting: 126):
Order code
A01
A02
011
012
013
014
821
C11
C12
C14
007
012
027
E01
E02
EIS
Y15
Y16
Y21
Y25
Only the setting lor WI' and "(25' can be made in the factory.
Example for ordering: see page 126
Scope of delivery: Transmitter as ordered gnawed:el Manual is extra
ordering item (see accessories on page 135)).
11 Verson 7MF4234-1DY... only up to max_ span 200 mbar (2.9 psi).
2) Without cable gland a PROFIBUS plug M12.
3) Not together with type of pro
-action 'Explosion-poser
or FIA•CSA (Inv)
125
EFTA01216842
Ordering Data
Ordering data
SITRANS P transmitter for absolute
pressure, from differential pressure
transmitter series.
DS Ill PA series
Order No.
■ Ordering data
Further designs
Please
Order No.
Order
Order code
7MF4334..
•••■•
♦•Aali
add
to
and specify
code(s).
Transmitter w‘th mcunting bracket made el
• Steel
AM
Meas. cell filling Meat. cell cleaning
• Stainless steel
A02
&Icon* ol
Normal
Inert liquid
Gyease.irec
InslNtt olFPIA (iban). process large 0-M9 netted.
• PTFE (Teflon)
A20
Nominal measuring range
• FEP (with sitcom core. approved (cc food)
A21
250 rrt>ar
(3 63 sc.)
• FFPM (Kalrez (Compound: 4079))
1.3)0 mr>ar
(18.9 psi)
F
• NBR (Bunn N)
A23
5.0)0 sitar
(72.5 psi)
30.0)0 sitar
(435 psi)
Icoo)o rata:
11450 psil
ICE
D
Sealing screws (1. • 18 NPT)Mth valve in material ol pro-
cess Range
AA0
Wetted parts materials
Rating plate inscriation (instead of German)
• English
B11
Seal claphraqm Pans of meas. cell
• French
B12
StmNess sleet
Stainless steel
A
• Spanish
B13
liesteloy
Stainless steel
B
• Haien
B14
Hastetoy
Hastetloy
C
Tantalum
Tantalum
English rating plate. pressure twin in inH20 or psi
B21
Monet
Monet
H
Manufacturer's test certificate M lo DU 65 350. Pan 18
Gold
Gold
L
and!'" ISO 8402
CI1
Version for remote seal )
Y
Acceptance test cedificale B to EN 10204-3.1 B
C12
Process connection
Factory cedilicatelo EN 10 204.2.2
C14
Female thread 'A • 18 NPT with flange
connection to DIN 19 213
Acid gas version to NACE
(only together with seal dapNagrn made of IMulattoy
and process screws made of stainless steel)
007
• 14th seeing screwopposes, process coon
• MouMeg reread
M10
0
Pea (nee together with PROFIBUS plug 1,112)
012
• Mooning thread
'fur 20 UNF
Digilal indicator beside coned keys
027
• Seolro sow. on solo ol process flanges 2)
(wily with transmitter 7(06334 -BO= 2.•/•6 Orr
Mounteg thread
M10
4
714T4334.MMM02 •A•7 -Z. Y21)
Mourteg thread
3/is 20 UNF
Non-wetted parts materials
Use in or al sale 1DaD (only together with basic
device with type of melodic., 'Inaireicalty.safel
E01
Process flange
Electronics housing
screws
Users zone 0 (basic wit EEx ia)
Oxygen apprentice (max. 160 bar (2320 psi)wilh oxy-
gen measurement and ine0 riling liquid)
E02
E10
SlaiNess steel
Die-cast aluminium
Stainless steel
Stain. steel prec. case
Interchanging ol process connection side
1401
Design
Vent on side for gas measurements
1402
• Standard version
Process flange made of:
• International version (available sown).
• Hastelloy
1C01
English label inscriptions. documenta.
• Monet
1CO2
Iron in 5 languages at CD
2
• Stainless steel with PVDF Purl (max. PN 10 (IMP
Nd
145 psi). max. lemperatured medial 90'0 (194'f))
Explosion protection
Additional information
• VA:Naul explosion protection
A
• VAth expbsion protection (CENELEC)
Please add •2• lo Order No. and specify Order code(s)
and plan text.
Type ol protection:
'Intrinsic safety' (EEx u)
• Explosce•proot (EEx d) 2)
B
Measuring•poinl nurterfdentificaticri
(max. 16 characters). specify h plain text:
• 'Intrinric safetyand expbsion-proor
Y16-
---
V16
(EEx is .EEx d)') (planned)
• W (sore 2) (planned)
P
E
Measuring.painl text (max. 27 characters).
specify in plain len:
• VMh expbsion protection (FM • CSA)
716:
V16
• intrinsic safe and exposion-proot
Selling for clgtal display. specify in plain teN
(is • xp)3) (planned)
N C
(standard setting mbar).
Electrical connection/cable inlet
V21: mbar. bar. kPa. Mita, psi....
V21
• Screwed Band 6120 x 1.5
B
Note: only pressure dmensions Kee page
• Screwed Band Yr • 14 NPT
C
51) can be selected.
• PROFIBUS plug MI24)
F
Preset bus address. specify in plain lest
(slandard selling: 126):
Indkalor
Y25
-
V25
• Withoul indicator (digital cast:layhid.
Only the setting tar 'Y21' and 'Y25' can be made in the factory.
den)
• VAM indicator (cisital display visible)
Example for ordering: see page 126
• YAM Potato/ (cfptal display visible.
Order
Y21
Scope of cleilverr Transrritler as ordered (Instruction Manual is extra
ordering cern (see accessories on page 135)).
setting as specified.
code
required)
41
Version MIF4334.113Y... only up to max. span 200 mbar (2.9 psi).
Not far flannel measuring range 160 bar (2320 psi).
3) Waled cable gland or PROFIBUS plug 6112.
4) Nol together with typed protection 'Explosionproct
or FM .CSA (is•xp)
126
SITRANS P. Series DS III PA
ASE00053276-04
EFTA01216843
Ordering Data
Ordering date
Order NO.
&TRANS P transmitter for differential
pressure and flow. DS III PA series.
PH 32/160 (IMP 464/2320 psi)
Meas. cell filing Meas. cell cleaning
Silicone or
Normal
Men hand
Grease free
Nominal measuring range
PN 32 (MW? 436 ps)
20mbar 1)
(029 psi)
PN 160 0.4WP 2320 psi)
60 mbar
(0.87 psi)
250 mbar
(3.63 psi)
600 mbar
(8.7 psi)
1.600 mbar
(23.2 psi)
5.000 mbar
(72.6 psi)
30.000 mbar
(435 psi)
Wetted parts materials
(process flange made ol stanless sleet)
Seal daptuagm
Pails ol limas cell
Slainess steel
Stemless steel
Ilasteloy
Stemless steel
Hasteloy
Hattelloy
Tantakrn2)
Tantalum
Monet?)
Mond
Gold )
Geld
Version kg remote seal
Process connection
Female Ihread 14 • 18 NPT with flange
connection lo DIN 19213
• Seating screw opposite process corn
• Mounting thread
4110
• Mounting thread
lie • 20 UNF
• Seeing screw onside ol process flanges
• Mounting thread
M10
Mounting 'Mold
7/is • 20 UNF
Norywatted parts materials
Process flange
Electronics housing
wows
Slaintess steel
Die-cast aluminium
StaiNess steel
Slain, steel prec. cast.
Design
• Standard version
• International VOIS/Cel (available soon).
English label inscriptions. documents.
lion in 5 languages on CO
Explosion protection
• Without explosion protection
• With explosion proteclion (CENELEC)
Type of protection:
• 'Intrinsic safely (EEx ia)
• 'Explosionoroor (EEx di 3)
• 'Intrinsic safety and explosion.prcor
(EEx ia • EEx d) I (gamed)
• W (zone 2) (planned)
• krAth explosion protection (FM • CSA)
• intrinsic sale and explosion•proof
(is • xp) )) (planned)
Electrkal connection/cable Inlet
• Screwed gland M20 x 1.5
• Screwed gland fel • 14 NPT
• PflOFIBUS plug M124)
Indicator
• Without indicates (digilal display hid-
den)
• With indicator (digital displayvisible)
• With MI:Mater (digital displayvisible.
maim as specified. Order code Y21
remit' ed)
7MF4434-
1
F
H
C
Et
L
V
0
C
4
•
•■
•
2 a
A
NC
8
D
8
F
C
7
EC•tbattng data
Further designs
Pease add 'Z to Order No. and specify Order ccde(s)
Transmitter with mounting packet made ol
• Steel
• Stawiess steel
Instead of FPM Wilan), process have Peng erode of
• PTFE (Teflon)
• FEP (with Scone core. approved for food)
• FFPM (Keller (Compound: 4079))
• Nea (Gum N)
Sealing screws (A. 18 NPT)with vake in material ol pro
cess flange
Rating plate inscrjolien (instead of German)
• English
• French
• Spanish
• Italian
English rating plate. Pressure uncs in inIti O or psi
ManiAacturers test codified* M to DIN 66 350. Part 18
and to ISO 8402
Acceptance lest certificate 8 to EN 10 204-3.1 8
Factory certificate lo EN 10204-2.2
Acid gas vemon to NAGE
(ony together with seal diaphragm made of I lastel lay
and process screws made ol starless steel)
IP 68 (not together welt PRCFEUS plug M12)
&gut mica's beside Decibel Ire
(only with transmitter 7154434.
-NANO a
7MF4434•MOMM2-MAM7.2. Y21)
Use ins on zone 1D/20 (only together with basic
device with type of proteclion'Intrinsicaly•safel
Use in zone 0 (bade rail EEtc ia)
Over.filfirg safety dance for flammable and
non•ftommable liquids (max_ PN 32 (MVP 464 psi))
(basic Link EEx ia)
Oxygen application (max. 160 bar (2320 psi)with
gem measurement and inert filling liquid)
Interchanging ol process connection side
Wet on side for gas measurements
&artless steel process flanges fo verlical ddlerential
pressure Ines (not together w'th K01.1(02 and 1(04) 11
Process flange made d Hash:Say
Process Range made oil Monet
Statics, sled with P1/CF used (max. PN 10 0.45VP 145
psi). max. lempetaitre of medium 90 °C (194 'F))
Additional hibernation
Pease add 'Z to Order No. and specify Order code(s)
and plain text.
4.4easurng.point numberridenbfkaton (max. It charac-
ters). speedy in plain text: 1115:
Measunng-point text (max 27 characters).
specify in plan teal: Y16: ...-.--
Setting for digital display, specify in plain text
(standard setting: mbar):
Y21: mbar, bar. laps. MPs. pal
Note: only pressure dmensions (see page
51) can be selected.
Preset bus address. specify in plain text
(standard setting: 126):
----
Orly the sating for Y21• and 725 can be made n the lactory.
Example for ordering: see page 126
Scope of delivery: Transmitter as ordered (Instruction Manual is extra
ordering item (see accessories on page 136)).
1) Not suitable Ion cennecbon of remote seal.
2) Only together with nominal measumg range 250. 1600. 5060 and
30300 mbar (3.63. 23.21.72.5 end 436 psi).
3) WilhoA cable gland or FROFILIUS plug MI2.
4) Not together with type d protection 'Explosionproce
or FM•CSA (mop)
Order code
401
A02
A20
A21
422
A23
MO
811
812
813
814
821
C11
C12
C14
007
012
027
E01
E02
LOS
E10
H01
H02
H03
1(01
1(02
1(04
715
716
Y21
Y25
SITRANS P. Series DS III PA
A5EOOO53276-04
127
EFTA01216844
Ordering Data
I Ordering data
SITRANS P transmitter for dMerentlal
pressure and now. DS HI PA series.
PN 420 (IMP 6092 psi)
Nominal measuring range
250 mbar (3.63 pal
600 mbar
(8.7 psi
1.600 mbar (232 psi
5.000 mbar (72.5 psi
3000 mbar (435 psi
Wetted parts materials
(process flange made of stainless steel)
Sea diaphragm
Parts of meas. cell
Stainless steel
Stainless steel
Novella,
Stainless steel
Gold')
Gold
Nooses connection
Female thread '4 - 18 NPT and flange
connection to DIN 19213
• Sealing screw cppostle process con-
nection
- Mounting thread
MI2
- Mounting thread
2r/i6 20 UHF
• Sealing screw on side of process
flanges
- Mounting thread
M12
- Mounting thread
qta - 20 UNF
Non-wetted parts materials
Process flange
Electronics housing
somas
Stainless steel
De -cast aluminum
Stainless steel
Stan. steel prec cast.
Design
• Standard version
• International version (available soon).
English label inscnptIons. documenta-
tion in 5 languages on CO
Explosion protection
• Wahout explosion protection
• With explosion protection (CENELEC)
Type of protection.
- Intrinsic safety' (EEx la)
-'Explosion-proof (EEx d) 4)
- Intrinsic safety4nd explosion-proof
(EEx IlEx d) ef (planned)
-'n' (zone 2) (planned)
• With explosion protection (FM .• GSA)
intrinsic safe and explosion-proof
In .• xpl 2) (planned)
Electrical connectionkable Inlet
• Screwed gland h120 x 1.5
• Screwed gland K - 14 NPT
• PROFIBLIS plug MI23)
Indicator
• Without indicator (digital cisplay hid-
den)
• With indicator (digital display nsable)
• With indicator (digital display wade.
setting as specified. Order code Y21
required)
128
Order No.
71.1,4534-
lOINE•-••••
t
AA iAA4
E
D
F
H
3
2
E
NC
C
F
B
7
Thderit'
Further designs
Please add l" to Order No. and specify Order code(s).
Transmitter with morning bracket made of
• Steel
• Stainless steel
Instead of FPM (Won). process Serge 0-rIng made of
• PTFE (Tenon)
• FEP (mth silicone core. approved Jr lad)
• FFPM (Kalrez (Compound: 4079))
• N8R (Bums N)
Sealing screw (A 18 NPT) wen wive in matenal of pro-
cess flange
Rating plate insalpbon (instead of German)
• English
• French
• Spanish
• Ratan
English rating plate. pressure units in int-lz0 or psi
Manufacturer's test certificate M to DIN 55 350. Pan 1B
and to ISO 8402
Acceptance test certificate B to EN 10204x.1
Factory certificate to EN 10 204-2.2
Acid gas version to NACE
(only together with seal diaphragm made of Hosteler/
and access screws made of stainless steel)
IP 68 (not together ugh PF1OFIBUS plug M12)
Dgital indicator teside contra keys
(only with transmitter 71.1F4534.S.12.MAZ 6 or
7MF4534 -NNEM2.MAN 7-2. Y21)
Use in or on zone ID/20 (only together w,th basic
device with type of protection 'Intrinsically-sale')
Use in zone 0(baslc unit EEx la)
Interchangng of process oomenon side
Stainless steel process flanges for vertical differential
presume fines
Additional Information
Please add 1" to Order No and specify Order code(s)
and plan text
Measuring-pant numbegidemilicatko
(max. 16 characters). specify n plain text:
Y15:......
Measuring-pant text (max 27 characters).
specify in pram text.
Y16,
Setting for digital casptay. specify in plan text
(standard sang: mba0.
Y21: mbat, bar, kPa, MPa, pal, ...
Nob: only pressure dimensions (see page
51) can be selected.
Preset bus adaess. specify n plain text
(standard setting 126).
Order code
AM
A02
MO
A21
A22
A23
A40
B11
B12
B13
B14
B21
C11
C12
C14
DO7
012
D27
201
E02
H01
1193
Y16
Y16
Y21
Y26
Only the setting for 721' and "(25' can be made in the factory.
Example for ordering: see page 126
Scope of delivery: Transmitter as ordered (Instruction Manual is extra
orderng item (see accessories at page 135)).
Only tooetter with nominal measuring ranee 250. IWO. 5000 and
SITRANS P. Sodas DS III PA
ASE00053276-04
EFTA01216845
Ordering Data
Ordering data
S$TRANS P transmitter
for level.
DS III PA series
Crcer No.
Ordering data
Further designs
Reese add .7. to Order No. and specify Order code(s).
Order code
7MF4634-
11E1•11-11111111
t
D
E
F
G
2
3
ti n t
2
A
B
D
P
E
C
F
Nominal measuring range
250 mbar
(3.63 psi
600 mbar
(8.7 psi)
1.600 mbar
(23.2 pa)
5000 mbar
(72.5 psi)
Instead of FPM (Vilon). process flange O-nng on low-
pressure side made d:
• PTFE (Teflon)
• FEP (with silicone core, approved fa food)
• FFPM (Kenn (Compound: 4079))
• NBR (Beta N)
A20
A2I
A22
A23
A40
B11
B12
B13
B14
B21
C11
C12
C14
012
E01
E02
E06
H01
Process connection of low-pressure
side
Female tread
18 PT and flange
connection to DIN 19213 with mounting
thread
• WO
• 'IR,- 20 UP
Seeing screws (1/4 - IS NPT) with valve in material of pro-
cess flange
Rating plate inscription (instead of German)
• Engtsh
• French
• Spanish
• Italian
Non-wetted parts materials
Process flange
Electronics housng
screws
English rating plate, pressure wits in riH2O or psi
Mandacesets test certificate M to DIN 55 350. Pan 18
and to LS08402
Acceptance test certificate B to EN 10204-3.1 B
Factory certificate to EN 10 204-22
Stainless steel
De-cast alurnmurn
Stainless steel
Sian steel prec. cast.
Design
• Standard version
• International yawn (available soon).
English label inscriptions. documenta-
tion in S languages on CD
IP 68 (not together web PRORBUS plug M12)
Use m or on zone 1C420 (only together with basic
device with type of protection intrinsicalty-safe)
Use in zone 0 (basic urn EEx la)
Over-tilling safety device for Ilarrmable and non-flamma-
ble 'Muds (max. PN 32 (MVP 464 psi) (basic use EEx la)
Explosion protection
• Without explosion proteceon
• VIM explosuan protection (CENB_EC)
Type of protection
-'Intrinsic safety' (EEx ia)
-'Explosion-proof' (EEx d)')
-'Intrinsic safety and explosion-proot
(EEx is sEEx d) l) (planned)
-'n' (zone 2) (planned)
Interchanging of process connection side
Additional Information
Reese add "r :o Order No. and specify Order ccde(s)
and plain text.
Measwing-pont 'timber/Identification
(max. 16 characters). speedy in plain text:
Y15:
Y15
Y16
Y21
Y25
Electrical connection/cable Inlet
• Screwed gland M20 x 1
• Screwed gland th 14 NPT
• PRORBUS plug M12 2)
Measuring.pont text (max. 27 characters).
specify in plan text:
Y16-
Indicator
• ',tetrad indicator (digital display hid-
den)
• With rid color (digital display viable)
• With rid color (digital display viable.
setting as specified. Order code Y21
requred)
Setting for digital *spay. specify et plain text
(standard salting: mbar):
Y21: mbar, bar, kft, 102, psi, .-
Note: only pressure dimensions (see page
51)can be selected.
Preset bus address. specify in plain text
(standard setting 126):
Ordering note:
1st order nem: Traneauter 7/AF4634-...
2nd ceder item: Mounting flange 7MF4912-3...
Example for ordering:
hem line
7MF4634-IEY20-1AAI
hem line 2
7M1C4912-30E01
Only the seeing for121' and *125' can be made in the lac-tory.
Scope of delivery: Transmitter as ordered (Instruction Manual is extra
ordering item (see accessories an page 135)).
SITRANS P. Series DS III PA
ASE00053276-04
129
EFTA01216846
Ordering Data
I
Ordering data
°Me No. Order Code
Mounting flange
Dcectly Nted onto SI1RANS
transmitter for level.
Ice
DS III PA series
Flange
Connection
to
DIN 2601
Connection
to
ANSI 816.5
Nom. dawn. Norm press.
EN 80
DN 100
PN 40
PN 16
PN 40
class 150
class 300
class 150
class 300
3 inch
4 inch
Other version
Add Order code and plain text,
Nominal diameter:...: Nom. pressure: ...
Wetted parts materiels
• Stainless steel. mat. No. 1.4571/3181i')
• Coated with PFA
• Coated with PTFE
• Coated with ECTFE
• Mond 400. mat. No. 2.4380
• Hasteeoy B2. mat. No. 2.4817
• Hastelloy C278. mat. No. 2.4819
• Hastelloy C4. mat. No. 2.4810
• Tantalum
Other version
Add Order code and plain text:
Wetted parts materials:...
Sealing lace: see 'Technical data'
Mae length
• Without tube
• 60 mm (1.97 inch
• 100mm (3.94 inch)
• 160 mm (6.90 inch)
• 200 mm (7.87 inch)
Filling liquid
• Silicone al M5
• Sificone oil M50
• High.ternperature al
• Halocarben oil (tor 02 measurements)
• Vegetable oil
• GlycerineAvater 2)
Other version
Add Order code and plain text:
Filling liquid:....
Further designs
Please add 2' to Order No. and specify
Order code(s).
With flame flashover lockout for mount-
ing on Sale 0 (include.; documentation)
Manufacturerb test certificate M to
DIN 66 350. Part 18. and to ISO 8402
Acceptance test certificate B to
EN 10 2043.1 B
Vacuum-rot...Mani design nor or.° in
vacuum range)
Calculation of span of associated trans-
meter (enclose filled-in questionnwe
nth order)
Note:
Suffix •Yor required with transmitterl
7MF4912..
0
2
A
0
G
U
K
J
2
a
4
2
3
4
S
J1V
K1Y
lily
Order code
A01
C11
C12
VO4
TO5
I) For vactsen on request.
2) Not suitable for use in low-presvure range.
Example for ordering: see page 131
1/52
130
Siemens Fl 01 • May 2003
SITFtANS P. Series DS III PA
A5E00053276-04
EFTA01216847
Ordering Data
12.2
Ordering data for spare parts
Ordering data
Order No.
6 Ordering data
Order No.
Snare pada
Spare pans (continued)
Mounting bracket and mounting pans
Mounting earn
For pressure transmitters.
MK 11 series (7MF40104MEMM-IMCM)
For measuring-pant Zabel la MK II. MS and
DS III (PA) series, eartNng and connection
MS series (7R4F40134MEMS 'MGM) and
'ennuis or la digital display (50 off)
7MF49a7-1CD
DS III (PA) series (7MF4COMOMMMIMCM)
For absolute pressure transrniters.
Sealing scree
DS III (PA) series (7MF423MaMMISIMCM)
(I set a 2 WO for process range
• Made of steel
7W4997-1A8
• Stainless steel
7MF49a7-1C0
• Made of stemless steel
7lIF4917-1AH
• Flagella/
7MF4997-1CH
Mounting bracket and mounting parts
For pressure transmitters.
Vent valves
complete (1 set
2 ott)
MK II series (7MF4010-EMMOIMAR
• Stainless steel
7h1F4997-1CP
-IMB• and •IMUMI.
MS sales (ThAFE1134MMOM-IMAM.
• Haney
7MF4997-1C0
-MBE and -INCE).
Electronics lot
DS III (PA) sales (7ME403MMEMEle
-1MB• and -1M0f).
• SIMIANS P. DS III series
71AF4997-1DK
For absolute pressure transmners
• SITRANS P. DS III PA series
7MF4997-1DL
DS III (PA) sales (7MF423MMEMEIM 'MAO)
Connection board for
-MBE and -1MDM).
• Made at heel
TAF4997-1AC
• SITRANS P. DS III series
7MF49a7-1CoN
• Made of stemless steel
7W4997-1AJ
• &MANS P. DS III PA series
7MF49a7-1DP
Mounting bracket and mounting parts for
0 -ringer. la process flanges made of:
WI. pressure trananiters with MID flange
• FPM (Viten)
7MF4997-20A
thread (7MF43 MM-... and 7MF44
• PIPE (Terial)
7MF4997-2D8
• Made of steel
71IF4907-1AD
• FEP (with silicone core. approved tar food)
7MF4997-200
• Made of stemless steel
• FITM (Kalrez (Compowd. 4079))
7MF4997-2DD
71/F4997-1AX
• NBA (Buns N)
7MF4997-2DE
Mounting bracket and mourning pals for
d nerenal pressure transmders with Dill2
range thread 17ME45 MO-.•
• Made of steel
71/F4997-1AE
• Made of stantess steel
71/F4997-IAL
Mounting bracket and mounting pans to
dilemma pressure and absolute pressure
Vansmiters with flange head /,a 20 UNF
(7MF41.3MM-.... 7MF44
MF45
• Made of steel
7W4997-1AF
• Made of stainless steel
7W4997-1AM
Cover (die-cast aluminium) without window.
including gasket
• For MK II. MS and DS III (PA) series
7W4997-1BB
Cover (stainless steel) without wham.
incliding gasket. la DS III (PA) series
7W4997-1BC
Cover (die-cast aluminium) %nth vando.v.
including gasket
• for MK II. MS and DS III (PA) senes
TAF4997-1BE
Cover (stainless steel) with whdaw.
including gasket for DS III (PA) sales
TAF4997-1BF
Analog Indicator. scale 0 to 100%
TAF4997-1BN
Analog Indicator. custanewspecific scale
TAF4997-1BP-2
CiViSORS as specified In plain text
Digital display including mounting material
la MS and DS III (PA) series
UE4997-188
Measuring-polM label
• Withcut inscription (5 on)
TIN4997-1 CA
• Printed ( I oft). data according to
7P/F4997-1 CB-Z
Y01 or Y02. Y15 and 716 (see Ordering
data for SITAANS P transmitters)
SITRANS P. Series DS III PA
A5E00053276-04
131
EFTA01216848
Ordering Data
Ordering data
SCRAMS P measuring cell fee pres-
swe
or DS III and DS Ill PA series
Mews. Ml Sing Mesa.
Cleaning
Silicone oil
Normal
Inert Ming lipid Grease-free
Rated measuring range
1 bar
(14.5 psi)
obar
(58 psi)
16 bar
(232 pe)
63 bar
(914 re)
150 bar
(2320 psi)
490 bar
15802 Psi,
Wetted parts materials
Seal diaphragm
Connection shank
Stainless steel
Stainless steel
Hastedoy
Stainless steel
Hamasy
Hasleloy
Process connection
• Connection shank GNA
• Female tread
- 14 NPT
• Oral Ilange made ol stainless sleet
max. span 160 bar (2320 psi)
Mounting ahead 'Ac 20 UNF
Moulting Mead MIO
Further designs
Please add "Z" to Order No. and spec-
ily Order code(s).
Acceptance teal Cerldreale B to
EN 10 204-3.1 B
Order No.
TUFAMI • • •••
O
B c
D
E
F
G
A
B
C
Cyder code
C12
Ordering data
°ideę No.
SITRANS P measuring cell for abso-
lute pressure (from pressure trans-
mitter series)
Nr DS III 4-id D3 ill PA te, ib,
Meas. cell filling Meas. celi cleaning
Silcox oil
Normal
Inert tillng liquid Grease-tree
Rated measuring range
250 mbar
(3 63pol
1.300 mbar
(18.9 pol
5.000 mbar
(72.5 ps)
3b000 mbar
(435 psi
Wetted parts materials
Seal diaphragm
Cconeclicn shark
Stainless steel
Slabless steel
lisstettoy
Slahless steel
lisstettoy
Hastelloy
Process connection
• Ccnneclicn shark GM
• Female head W 14 OPT
• Oval flange erode of slahless stad.
max. span 160 bar ()MOW
Mounling thread Vic 20 UNF
Mounling Thread
Further designs
Please add -r M Order No. and spec-
ify Order codes).
Acceplance lest CerliliCate B to
EN 10204-3.1 B
711F4992 • ••••
O
1
D
F
G
H
A
B
C
2
3
Order code
C12
SITRANS P. Sedes DS III PA
132
A5E00O53276.04
EFTA01216849
Ordering Data
Ordering data
Omer No.
SITRANS P measuring cell for abso-
lute pressure (horn differential pres-
sure transmitter series)
fcr OS 11 and CS ill PA ',cues
Meas. cell filing Maas. cell cleaning
&Scene of
Normal
Inert filling liquid Grease-free
Rated measuring range
250 mbar
(3.63 ps)
1.300 mbar
(I8 9 ps)
5.000 mbar
(72 5 ps)
3).000 mbar
1435 ps)
100.000 mbar
(1450 ps)
Wetted parts materials
Seal daphragm Pans or mess. cet
Stainless steel
Hadeloy
Hadeloy
Tantalum
Monet
Gad
Process connection
Female [Mead 'A 18 NPT with flange
convenor', to DIN 19213
• Vent opposite process connection
Moulting thread
MID
246- 20 UNF
• Vent on side 01 process flange
Moaning thread
MID
/,6.20 UNF
Hon-wetted parts materiels
Process flange screws:
• Staines& steel
Staines& steel
Staines& steel
Hasielby
Tantalum
Mont
Gold
Further designs
Pease add'
to Order No. and spec-
ify Order code(s).
Instead 01 PPM (1./iforg, process flange
0 -Mg made of:
• PTFE (Teflon)
• FEP (with shear* core. approved for
loud)
• FFpld (Kalre2 (Compound: 4079))
• NES (Buns N)
Acceptance lest senile-de B to
EN 10204-3.1 B
Process connection Gb2A
Remote seal connection (tat together
wish K01. KO2 and K04)
Vent on side for gas measurements
Without process flanges
With process flange made tel:
• Ilasielloy
• Monet
• Stainless steel with PVDF insert (Max_
PN 10 (MWP 145 psi). max. tempera-
lure of medium 90 IC (194 IF))
') Only together with max span 250. 1.600. 5.000 and 30.003 mbar
(3.63. 23.21. 72.5 and 435 psi).
2) Not suitable for connection et remote seal.
7MF4993
1
3
1 A ..
D
H
K E
A
C
E
H
L
B
0
4
8
•
2
Order code
420
A21
A22
A23
C12
D111
D20
H02
KOO
K01
K02
KM
SITRANS P. Series DS III PA
A5E00053276-04
Ordering data
Order No.
SITRANS P measuring cell for differ-
ential pressure and PN 32/160
(MWP 481)2320 psi)
for DS 111 and OS III PA Spero
Men, eel Nang Neat eel] cleaning
Siloam oil
Normal
Iced lilting limad Grease-free
rated measuring range
TIN 32 (heA,P 464 psi)
20 mba")
(0.29 psi)
FIN 160 (MWP 2320 ps)
60 Mbar
(0.87 put
250 Mbar
(3.63 put
600 Mbar
(8.7 put
1.600 mbar
(23.2 put
5.000 mbar
(72.5 put
30.000 mbar
(435 psi)
Wetted pens materiels
(process flanges made of stainless
steel)
Seal diaphragm
Pans or meas. cell
Stainless steel
Slairtess steel
Hasidic/
Stainless steel
Hasidic/
Hasielloy
Tantalum
Tantalum
Monet I)
Menet
Gold
Gold
Process connection
Female thread'' 18 NPT with flange
connector, to DIN 19 213
• Vent opposite process connection
Mounting thread
4410
(/15- 20 UNF
• Vent on side of process Range
Mounting thread
M10
2/ To 20 UNF
Non-wetted pees materiels
Process flange screws:
• Stanton steel
Further designs
Pease acid '2' to Order No. and Spee-
dy Order code(*)
Instead of FPM (Viton). process flange
0 -ring made 01:
• P1FE (Teflon)
• FEP (with silicone CCM approved Mr
Moth
• FFPM (Kaire2 (Compound: 40798
• NBA (Buns N)
Acceptance teal candidate B to
EN 10 204-3.1 B
Remote seal flanges (not together with
KOI. KO2 and K04)
Vent on side for gas measurements
Stainless steel process flanges for verti-
cal ditterentol pressure Ines (non
together with 1(01. KO2 or K04)
Without process singes
With process flange made of:
• Hasielroy
• Monet
• Stainless steel with PVDF insert (max.
PN 10 (idM/P 145 psi). max. tempera-
lye 01 medium 90.IC (194 'F))
71.1T-4994 •
B
C
D
E
F
H
C
E
H
L
B
2
Order code
A20
A21
A22
A23
C12
D20
H02
H03
KOO
K02
KM
133
EFTA01216850
Ordering Data
Ordering data
Cof C..1 No
SITRANS P measuring cell
for differential pressure and PN 420.
(MWP 6092 psi)
DS III and DS III PA series
Rated measuring range
250 mbar (3.63 pi2)
600 mbar
(8.7 psi)
1.603 mbar (23.2 psi)
5933 mbar (725 psi)
330:0 mbar cads psi)
Wetted parts materials
(process flanges made 01 stainless
steel)
Seal dopnragm
Parts of mess. cell
Stainless steel
Stainless steel
Hasteloy
Stainless steel
Geed')
Gold
Process connection
Female thread S6 - 18 NPT Mtn flange
connection to DIN 19 213
• Vent opposite process conrect.cn
- Mounting thread
9112
20 UNF
• Vent on side of process flange
- Mounting thread
9112
116 . 20 UNF
Non-wetted parts materials
Process flange screw.
• Stainless steel
Further designs
Please add 'Z' to Order No. and spec-
ify Order code(s).
Instead of FPM (Vann). process flange
O-ring made cf:
• PTFE (Teflon)
• FEP (wth silicone cote. approved for
food)
• FFPM (Kairez (Compound. 4079))
• MIR (Bona N)
Acceptance test certificate B to
EN 10204-3.1 B
Stainless steel process flanges for verb-
cal differential pressure lines
Witt011t process flanges
') ONy together nith max_ span 250. 1.600. 5.000 and 30.000 mbar
(3.63. 23.21. 72.5 and 435 psi).
7MF4995 - 1 MINIM
I 5AA
D
E
F
G
H
3
7
Order code
A20
A21
A22
A29
C12
1103
KOO
Ordering data
Order No.
SITRANS P measuring cell
for level.
DS Ill and DS Ill PA series
Rated measuring range
250 mbar
(3.63 pa)
600 Inbar
(8.7 ps.)
1.600 mbar
(232 psi)
5.000 mbar
(725 psi)
Wetted parts materials
I process flanges made of stainless
steel)
Seal diaphragm
Pans of mess. cell
Stainless steel
Stainless steel
Process connection of low-pressure
side
Fenae thread !A IS NPT Mtn flange
connection to DIN 19 213
• Vent opposite process connection
Mounting thread
9110
116 . 20 UNF
Non-wetted parts materials
Process flange screes
• Stainless steel
Further designs
Please add .2. to Order No. and spec-
ify Order code(s).
Instead of FPM (Won). process flange
0 -ring made of:
• PTFE (Teflon)
• FEP (with silicone core. approved foe
food)
• FFPM (Ken (Compound: 4079))
• MR (Bona N)
Acceptance test certificate B to
EN 10204-3.1 B
Witnoat process flanges
71/F4996 -1 la •
D
E
F
O
0
2
2
Order code
A20
MI
A22
A29
C12
KOO
SITRANS P. Serb s DS III PA
134
A5E00053276.04
EFTA01216851
Ordering Data
12.3
Ordering data for accessories
I Ordering data
Insiructo-
Matniction Manual IL,
0611 swift
• German
ASE00047090
• English
ASE00047092
• French
ASE00033216
• Spanish
ASE00033220
• Ratan
A5E00053219
Brief instructions (Leporello)
to. SI TRANS R DS III series
• German/English
ASE00047093
CO with documentation
be SITRANS R DS III series. DS III PA. MS.
MX II MPS and 2
• German. Engish. French. Spanish. Italian
Service Manual lot replacement of elec-
tronics. measiang cell and conneelicn board
• GermanfEnglish
ASE0009034S
ASE00078060
Way available on the
Internee)
HART commtnicalion
HART communicator
See on the right side
HART modem
711F49074DA
Note:
You can download the above-mentioned Instruction Manuals
free-of-char
from the Internet site
Order No.
Ordering data
HART communicator with
rechargeable battery.
charger fee AC 230 V
Type or protection irerinsic safely
Ea is IIC T4. nilh carrying case.
4 MB MettOry,
Wel COI of Siemens devices
Language
• German
• Encash
Loading of further device
descriptions
Pea t.pecily DDs in plan text
Out.
TIAF4998-8KF
71.1Ft:998-SKI
VIAF4998-8KU
SITRANS P, Series DS III PA
ASE00053276-04
135
EFTA01216852
Ordering Data
SITFtANS P. Serb s DS III PA
136
A5E00053276-04
EFTA01216853
Certificates
13
The certificates are enclosed as a collection of loose leaves in the operating
instructions (or on CD).
SITFtANS P. Series DS III PA
ASE00053276-04
137
EFTA01216854
Certificates
SITFtANS P. Serb s DS III PA
138
A5E00053276-04
EFTA01216855
Index
A
Assembly 82
B
Blanking plug 15
Block diagram 17, 18, 19
Bridge output voltage 18, 20
C
Cable gland 15
Care 115
Class 1 Master 33
Commissioning 95
Configuration message 33
Connection 90
to screw terminals 90
Connection diagram 90
Cyclic operation 33
D
Data consistency 33
Design 13
Device Master Data file 33
Diagnostic Information 44
DMD file 33
E
Electrical connection 89
Error 44
Error signaling 44
F
Filling liquid 19
Flange 19
Front view of the device 15
Functional diagram 17, 18, 19, 20
H
Hardware error 115
Input keys 45
Installation 81, 82
Interfacing
PROFIBUS 120
K
Keyboard 45
L
Locking screw 88
M
Measured value display 44
14
SITRANS P. Series DS III PA
ASE00053276-04
139
EFTA01216856
Measuring
gases 97
liquid 98
vapor 98
Measuring point plate 15
Modular 79
Mounting bracket 83
0
Operation
Key functions 46
locally 43
Ordering 123
P
Plastic cover 15
Process connection 14
PROFIBUS 117
Bus topology 117
PROFIBUS automation system
Figure 118, 120
Profile PROFIBUS PA 119
R
Range of rotation. 87
Rating plate 15
Rear view of device 15
S
Seal diaphragm 20
Self test 115
Shutoff valve 102
Status display 44
System integration 33
T
Technical 103
Technical Data
Dimensions 110
Terminating resistor T 119, 120
Test plug 90
Window 15
SITRANS P. Series DS III PA
140
A5E00053276-04
EFTA01216857
Appendix
15.1
Literature and catalogs
15
No.
Title
Issued by
Order number
111
PNO guide
PROFIBUS PA
PNO
Technologiefabrik
Haid-und-Neu-Str. 7
D-76131 Karlsruhe
2.091
121
SIMATIC field technology package
Siemens AG
Internet address:
http://www.ad.siemens.de:8080/vIrlib/html_00/
doc/index.htm
on: Profibus desaiptions (free) 1 system
description i PA system description, German
131
Catalog, ST 50
SIMATIC SS/PC/505
Automation Systems
Siemens AG
E86060-K4650-A111-A8-7600
141
Catalog, ST 70
Components for Totaly Integrated
Automation
Siemens AG
E86060-K4670-A111-A7-7600
151
Catalog, ST 80
Human Machine Interface
Products/Systems
Siemens AG
E86060-K4680a101-A9-7600
/6/
Catalog, IK P1
SIMATIC NET
Industrial Communication and Field
Devices
Siemens AG
E86060-K6710-A101.82-7600
RI
Catalog, ST PCS 7
SIMATIC PCS 7
Process Control System
Siemens AG
E86060-K4678-A111-A5-7600
SITRANS P, Series DS III PA
ASE00053276-04
141
EFTA01216858
Appendix
15.2
Summary of error messages and status codes
I Hex
Digital
display
Source of mea-
sured value set
PDM display
Cause
Measure
00
B_000
Output (cyclic data
only), counter output
(cyclic data only)
Bad
Is used if no other
information is
available.
Device not available
or cyclic connection
interrupted.
—
08
8_011
Secondary variable 3
Bad. not con-
nectod. value
constant
Variable is not calcu-
lated
Correct the `Measur-
ing transducer type"
setting
OC
B_012
Non-linearized pres-
sure value, secondary
variable 1, secondary
variable 2, measured
value (primary vari-
able). secondary vari-
able 3, output 1),
counter output 2)
Bad, device
error
Device has an irrepa-
rable error
Replace the electron-
ics.
04
B_004
Non-linearized pres-
sure value, secondary
variable 1, secondary
variable 2, measured
value (primary van-
able). secondary vari-
able 3, output .).
counter output 2)
Bad, configure-
lion error
Adjustment range too
small
Repeat the adjust-
ment process with
pressure valueswhich
are further apart from
one another.
OF
8_015
Non-linearized pres-
sure value, secondary
variable 1, secondary
variable 2, measured
value (primary vari-
able). secondary vari-
able 3, output .),
counter output 2)
Bad, device
error, value con-
scant
Device has an
irreparable error.
Change the
electronics.
10
B_016
Non-linearized pres-
sure value, secondary
variable 1, secondary
variable 2, measured
value (primary vari-
able). secondary vari-
able 3, output .),
counter output 2)
Bad, sensor
error
Sensor shows error.
Have the measuring
cell checked by
service personnel.
11
8_017
Non-linearized pres-
sure value, secondary
variable 1, secondary
variable 2, measured
value (primary van-
able). secondary vari-
able 3, output .),
counter output 2)
Bad, sensor
error, fallen
below limit value
Negative pressure
too high Fallen below
lower overload limit
(c -20 % of nominal
measuring range).
increase the pressure
in a positive direction.
142
SITFtANS P. Series DS III PA
A5E00053276-04
EFTA01216859
Appendix
Hex
Digital
display
Source of mea-
sured value set
PDM display
Cause
Measure
12
8_018
Non-linearized pres-
sure value, secondary
variable 1, secondary
variable 2, measured
value (primary van-
able), secondary vari-
able 3, output .),
counter output 2)
Bad, sensor
error, limit value
exceeded
Positive pressure too
high Upper overload
limit exceeded (>
120 % of nominal
measuring range).
Reduce the pressure.
11
B_031
Output, counter output
Bad, out of
order, value
constant
The function block is
put out of order with
a target mode corn-
mand. A parameter-
ized safety value is
output.
For normal operation,
reset the target mode
to "AUTO".
47
U_071
Output
Uncertain, last
usable value,
value constant
Input condition Wail
safe" is met, the
parameterized
safety setting is set
to "Keep last valid
value'.
Chock the recording
of measured values.
48
U_072
Counter output
Uncertain.
replacement
value
Use of the totalizer
block when the mea-
sured value status =
'bad and the param-
eterized safety set-
ting is set to "Safe
operation". The total
value changes. Fault
behavior = safe oper-
ation.
Check the recording
of measured data.
4B
U_075
Output, counter output
Uncertain,
replacement
value, value
constant
Value is not an auto-
matic measured
value. This identifies
a parameterized,
static substitute
value or a preset
value.
Check the recording
of measured values.
4F
U_079
Output, counter output
Uncertain, initial
value, value
constant
After run-up, an intlal
value is entered
in the device mem-
ory.
Reject the value in the
user program.
50
U_080
Non-linearized pries-
sure value, secondary
variable 1, secondary
variable 2, (measured
value (primary van-
able). secondary rani-
able 3, output, counter
output
Uncertain, value
inaccurate
Non-permissible
operatlngparameters
or maintenance
alarm
Check the operating
parameters, e.g. the
permitted ambient
temperature.
Immediate mainte-
nance work required.
1) Only if fault behavior of the analog input function block is set to 'Incorrectly calculated measured value at
the output'.
2) Only if fault behavior of the counter function block is set to 'Operation".
SITRANS P, Series DS III PA
ASE00053276-04
143
EFTA01216860
Appendix
Hex
Digital
display
Source of mea-
sured value set
PDM display
Cause
Measure
51
U_081
Non-linearized pros-
sure value, secondary
variable 1, secondary
variable 2, measured
value (primary vari-
able). secondary vari-
able 3, output, counter
output
Uncertain, value
inaccurate.
fallen below limit
value
Fallen below lower
nominal measuring
range limit
(c 0 %).
Increase the pres-
sure in a positive
direction.
52
U_082
Non-linearized pries-
sure value, secondary
variable 1, secondary
variable 2, measured
value (primary vari-
able). secondary vari-
able 3, output, counter
output
Uncertain, value
inaccurate. limit
value exceeded
Upper nominal mea-
suring range limit
exceeded
(> 100 %).
Reduce the pressure.
80
Electronics tempera-
lure,
Sensor temperature,
non-linearized pres-
sure value, secondary
variable 1, secondary
variable 2, measured
value (primary vari-
able). secondary vari-
able 3, output, counter
output
Normal operation
--
84
G_132
Electronics tempera-
ture, Sensor tempera-
Lure, non-linearized
pressure value, sec-
ondary variable 1. sec-
ondary variable 2,
measured value (pri-
mary variable), sec-
ondary variable 3.
output, counter output
Good. update
event
A parameter rale-
vent to the behavior
of the slave has been
changed.
The display is extin-
guished after 10s.
Message to the con-
trot system.
89
G_137
Output, counter output
Good. fallen
below warning
limit
Fallen below lower
parameterized warn-
ing limit
Correct error using
user programme.
8A
G_138
Output, counter output
Good, warning
limit exceeded
Upper parameter-
ized warning limit
exceeded.
Correct error using
user programme.
8D
G_141
Electronics tempera-
lure, output, counter
output
Good. fallen
below alarm
limit
Fallen below lower
parameterized alarm
limit.
Correct error using
user programme.
8E
G_142
Electronics tempera-
tuna, output counter
output
Good. alarm
limit exceeded
Upper parameter-
ized alarm limit
exceeded.
Correct error using
user programme.
A4
G_164
Non-linearized pries-
sure value, secondary
variable 1, secondary
variable 2, measured
value (primary vari-
able). secondary vari-
able 3, output, counter
output
Good, mainte-
nance required
Maintenance interval
has expired: Calibre-
bon or servicing.
Maintenance work.
calibration of the elec-
tronics or servicing of
the measuring cell is
required.
144
SITFtANS P. Series DS Ill PA
A5E00053276-04
EFTA01216861
Appendix
Hex
Digital
display
Source of mea-
sured value set
PDM display
Cause
Measure
-
F_001
-
-
Local operation
disabled
Release write
protection
-
F_002
-
-
Change of bus
address not possible
as the device is
exchanging data with
class 1 master.
End communication
with class 1 Master.
-
F_003
-
Change of device
operating mode not
possible, as the
device is exchanging
data with class 1
master.
End communication
with class 1 Master.
-
F_004
Display overflow
Check the physical
unit and decimal point
position settings, and
adjust them to the =-
rent measured value.
-
F_005
-
Value is read-only.
-
F_006
-
Adjustment unsuc-
oessful.
Check adjustment
range, repeat proce-
dure.
-
F_007
-
Measurements
across whole mea-
suring range no
longer possible after
zero point adjust-
ment.
Check measuring
range, if necessary
reduce inconsistency.
-
F_008
-
Local operation is
disabled by SIMATIC
PDM.
Set the parameter
"Local operation" to
"Enabled" with
SIMATIC PDM.
SITRANS P, Series DS III PA
ASE00053276-04
145
EFTA01216862
Appendix
15.3
Certificates
The certificates are enclosed with the operating instructions in compiled form as a
loose collection of sheets.
l General
The pressure equipment directive 97/23/EC applies to the align-
ment of the statutory orders of the European member slates for
pressure equipment. Such equipment in the sense of the direc-
tive includes vessels. pipelines and accessories with a maxi-
mum permissible pressure of more than 0.5 bar above
atmospheric.
The pressure equipment directive can be used starting Novem-
ber 29. 1999. and is compulsory starting May 29. 2002.
I Division according to the danger potential
Equipment is divided n line with the pressure equipment direc-
tive according to the danger potential (medium/pressure/vol-
ume/nominal diameter) Mto the categories Ito IV or Article 3
Paragraph 3.
The following criteria are decisive for assessment of the danger
potential. and are also shoran in Diagrams 1 to 4 and 610 9:
• Fluid group
• Aggregate slate
• Type of pressurized equoners
Vessel
- Octane
Group 1 a 2
Liquid or gaseous
Rectum a pressure and vokime
(PS' V paarLj)
Nominal diameter. pressure or
preduci 0( prestige and nominal
diameter (PS' COO
Fuelled pressure equipment or equipment heated in another
manner are shown separately in Diagram 5.
Note:
Liquids according to Article 3 are those liquids whose steam
pressure is not more than 0.5 bar above standard at nosphenc
pressure (1013 mbar) at the maximum permissible temperature.
The maximum permissible temperature for the used liquids
is the maximum process temperature which can occur. as
defined by the user. This must be within the limits defined for
the equipment.
Conformity rating
•••••
■ Division of media (liquid/gaseous) Into the fluid groups
Fluids are divided according to Article 9 into The to II vang fluid
groups:
Group 1
Potentially
explosive
B phrases:
e.g.: 2.3(1.4.
5. B.9. it It
19. 44)
IRONY
fbmrnable
phrases:
eg.' 12(17)
Highly toxic
B phrases.
e.g,. 26. 27. 28.
39(32)
Teals
B phrases.
e.g.: 23. 24. 25
(29.31)
Readily
Fire
flammable
stimulating
pirates:
B pirates.
e.g.: 11.15.17
e.g.: 7.8.9
(10.30)
(is, 15, 19)
Flammable it the maximum permissible temperature is above the dash
point.
Group 2
All duds not belonging to Group I
Also applies to Iluids nhicn ate e.g. dangerous a the erivirarters. cor-
rosive. dangerous to health. inilars of carchogeruc (it rot nighty toxic).
Pressure equipment of categories Ito IV must comply with the
safety requirements of the directive and be assigned the CE
symbol.
They must comply %vith a conformity rating procedure according
to Appendix III of the diective.
Pressure equipment according to Article 3 Paragraph 3 must be
designed and manufactured in agreement with the sotrid engi-
neering practice SEP apptyi-ig i1 a member country. and must
net be assigned a CE symbol (CE symbols fran other diectives
are not affected).
Siemens has carried out a conformity rating. assigned a CE sym-
bol. and issued a declaration of conformity for its products (pro-
viding the equipment is not within the context of Article 3
Paragraph 3).
Supervision of the design. dimensioning. testing and manufac-
ture is carried out according to module H (comprehensive qual-
ity assurance) by the TIN Nord (Northern Technical
Inspectorate) as the specified office.
Notes:
• Equipment designed for media with a high danger potential
(e.g. gases of fluid group 1) may also be used for media with a
lower danger potential (e.g. gases of fluid group 2. or liquids of
fluid groups 1 and 2).
• The pressure equipment directive according to Article 1 Para-
graph 1 does not apply to equipment such as e.g. mobile off-
shore plants. ships. Strait. water supply and waste water
networks. nuclear plants. rockets and pipelines outside indus-
trial plants.
SITRANS P. Serios DS III PA
146
A5E00053276-04
EFTA01216863
Appendix
I Diagrams
nom
Imo
too
a
io
Diagram 1
• Gases of uid groups
• Vessels according to Article 3 Number 1.1 Letter a) Frst dash
• Exception unstable gases belonging to Categories I and II
must be included ri Category Ill.
• Liquids of fluid group 1
•Vessels according to Article 3 Number 1.1 Letter b) First dash
Diagram 2
Al
1
to
too ari MO
10000
Vg
• Gases of luid group 2
• Vessels according to Article 3 Number 1.1 Letter a) Second
dash
• Exception ire extinguishers and bottles fa breathing appara-
tus: at least Category III.
Diagram
41
I
10
wo
1000
10000
VII
• Liquids of fluid group 2
• Vessels according to Article 3 Number 1.1 Letter b) Second
dash
• Exception: modules for producing warm water
• Fuelled pressure equipment or equipment heated ri another
manner above 110 `C and liable to overheating.
• Vessel according to Article 3 Number 1_2
• Exception: pressure cooker. test procedure at least accordrig
to Category Ill.
SITRANS P, Series DS III PA
ASE00053276-04
147
EFTA01216864
Appendix
0,1
1
10
100
1010
10000
0.1
1
10
KO
WOO
10003
ON
1000
10
co
1
10
Ito
Diagram 7
PS.05
0000
ON
• Gases of fluid group 1
• Gases of I uid group 2
• Pipelines according to Article 3 Number 13 Letter a) First dash
• Pipelines according to Arbcle 3 Number 1.3 Letter a) Second
• Exception: unstable gases belonging to Categories I and II
dash
must be included in Category Ill.
• Exception: licitids al temperatures > 350 °C belonging to Cat-
egory II must be included in Category III.
Diagram 8
rt
PS-00
ON
• Liquids of fluid group 1
• Pipelines according to Article 3 Number 1.3 Letter b)First dash
Ma 3
PS-rlip't 3
Diagram 9
PS4C0
®
'4/.5.
PS.*
PS45
0.1
I
10
10)
IMO
IWO
ON
• Liquids o4 fluid gaup 2
• Pipelines according to Article 3 Number 1.3 Latter b) Second
dash
SITRANS P. Serb s DS III PA
148
A5E00053276-04
EFTA01216865
EFTA01216866
IIIV II I
074995
II II II III III II
P
A5E00053276
Siemens AG
Bereich Automation and Drives
Geschaeftsgebiet Process Instrumentation and Analytics
D-76181 Karlsruhe
www.siemens.comfprocessinstrumentation
A5E00053276-04
EFTA01216867
Technical Artifacts (20)
View in Artifacts BrowserEmail addresses, URLs, phone numbers, and other technical indicators extracted from this document.
Domain
conrect.cnFlight #
AA0Flight #
AC230Flight #
AF4634Flight #
OS11IPv4
23.21.72.5Phone
310 2320Phone
481)2320Phone
510 5802Phone
7154434Phone
763
1044Tail #
N8RURL
http://www.ad.siemens.de/csi_e/gsdURL
http://www.ad.siemens.de:8080/vIrlib/html_00URL
http://www.ad.siemens.deicsi_e/gsdWire Ref