MITCH102A / 19 W 31st Street. NY
Non-Conformance Log
05/25/2018
GRANT Engineering
139 Fulton Street, Suite 907
New York. NY. 10038
_NCR Log
#
DATE
MEMBER
SIR Reference #
COMME
01
T612017
MITCH102A
First floor dock behind
elevator core
20170306 EM
-
-
Contractor installed dock and placed concrete without informing the inspector. No inspection was
performed. Contractor to get approval by EoR/RA for as-built conditions
Closed
02
31812017
Cellar and First floor Lobby
area
MITCH102A 20170308 EM
-
-
Deck installation and placement of concrete was placed without inspection. Contractor to get approval by
EoR for as-built conditions
Closed
03
atioi2o17
Member size changes
MITCH102A_20170310_O1" Some beam sizes different that shown in draws. EoR-to-iletine-ceurse-ei-astien
Closed
04
3./10/2017
Post connected to wall with
2 clips
MITCH102A_201703I0_OP Drawing call for min. 3 rows. EoR to define course of action
Closed
05
a/ 0/2017
No shop drawings on Site
MITCH102A_201703I0_OP No shop drawings with detail of connections and members. EoR to approve field solutions
Closed
06
3122/2017
Cellar Level
MITCHI02A_201703228 - EM Not approved fireproofing product was used on exposed steel at cellar. Contractor to get specs
and approval from AoR for fireproofing material used at exposed steel
Closed
07
3./22/2017
Cellar Level Concrete Pour MITCH102A_20170322A_EM Not approved dwgs found on site for pour at the cellar level. Contractor to get directions from EoR
Closed
08
3/29/2017
Steel frame stair connection MITCHI02A_20170329A_EM
Changes in connection. Grout not used at connections with bolts. Sketch on site has no stamp.
Contractor to get approval for changes from EoR on a stamped dwgfSketch before placement of
concrete
Closed
09
3./3112017
Rebar E-102
MITCH102A_20170331_EM Rebar installation and connection details for steel. Contractor to get approval for from EoR brfore
concrete placement
Closed
10
4/3/2017
SK-05 rebar
MITCH102A_20170403_EM No stamp on drawings. Contractor to seek stamp from EoR
Closed
II
4/32017
S-105 Rebar
MITCH102A_20170403_EM No details found. Grant to reinspect after dnvs are on site
Closed
12
4/3/2017
Sk-05 Landing for cellar
steel stair
_
_
MITCH102A 20170403 EM Shop Drawings used must be stamped by FOR
Closed
13
4/32017
Steel Stair
MITCH102A_20170403_EM
Changes to the stair design do not reflect on arch dwgs. Railings and step height does not conform to
drawings. Height of step is 8.06' and not 7.1/2" as per approved sketch. Contractor to provide updated
approved architectural dwgs
Dosed
14
4/312017
Connections at Steel Stair
from Cellar to First Floor
MITCH102A_20170403_EM As-built connection details not reflected on plans. Approved sketch on 03130/17 and E-102. Contractor to
provide updated approved architectural dwgs
Closed
EFTA00805551
MITCH102A / 19 W 31st Street, NY
Non-Conformance Log
05/25/2018
GRANT Engineering
139 Fulton Street, Suite 907
New York. NY. 10038
15
4/5/2017
Mechanical: Connection of
ductwork to unit
MITCH102A _ 20170405A EM
—
16
4/5/2017
Mechanical: Duct Work
Hangers Min
MITCH102A_20170405A_EM
17
7/18/2017
Cellar Fireproofing of Steel MITCH102A_20170718A_EM
Connection detail and size of ductwork could not be verified. No approved drawings on site. Contractor
to provide updated approved architectural dwgs
Closed
Spacing of ductwork hangers not yet verified. No drawings on site. Contractor to provide approved
architectural dwgs
Closed
Performing of avrg required thickness for fireproof material as per requirements of structural members.
Density test performed.does not conform to min. Required (15pcf) per specs of approved products
reflected on plans. Approved sketch on 03/30/17 and E-102. AoR to provide directions. Contractor to
send to inspector approved thickness for structural members
Closed
EFTA00805552
Technical Artifacts (3)
View in Artifacts BrowserEmail addresses, URLs, phone numbers, and other technical indicators extracted from this document.
Phone
3112017Wire Ref
ReferenceWire Ref
reflectedForum Discussions
This document was digitized, indexed, and cross-referenced with 1,400+ persons in the Epstein files. 100% free, ad-free, and independent.
Annotations powered by Hypothesis. Select any text on this page to annotate or highlight it.