Case File
efta-efta01084314DOJ Data Set 9OtherFACADE INSPECTION REPORT: CYCLE 7
Date
Unknown
Source
DOJ Data Set 9
Reference
efta-efta01084314
Pages
33
Persons
0
Integrity
No Hash Available
Extracted Text (OCR)
Text extracted via OCR from the original document. May contain errors from the scanning process.
FACADE INSPECTION REPORT: CYCLE 7
PROPERTY:
9 EAST 7151 STREET
NEW YORK, NY 10021
ARCHITECT:
ARC, P.C.
12 WEST 23'3 STREET 3A° FLOOR
NEW YORK, NY 10010
TEL:
INDEX:
I.
EXECUTIVE SUMMARY
A.
PROPERTY INFORMATION
B.
OWNER INFORMATION
C.
DESCRIPTION OF BUILDING
D.
SETTLEMENTS, REPAIRS & REVISIONS
E.
CRITICAL EXAMINATION PROCEDURES
F.
METHODS USED TO CONDUCT INSPECTION
G.
REPORT OF CONDITIONS OBSERVED: CYCLE 7
H.
ANALYSIS OF THE CAUSES OF CONDITIONS REPORTED
I.
STATUS OF EXTERIOR MAINTENANCE
J.
COMPARISON OF FINDINGS WITH PRIOR REPORT
K.
RECOMMENDATIONS FOR REPAIRS OR MAINTENANCE
L.
REQUIRED PERMITS
M.
PHOTOGRAPHS
N.
CLASSIFICATION OF BUILDING
0.
PROFESSIONAL SEAL & SIGNATURE
P.
APPENDICES:
1. BIS PROPERTY INFORMATION PROFILE
2. ECB FACADE VIOLATION SUMMARY
3. ECB FACADE VIOLATION DETAILS
4. BIS APPLICATIONS OVERVIEW
5. REFERENCE DRAWINGS: ROOF PLAN
6: REFERENCE DRAWINGS: ELEVATIONS
7: MAINTENANCE RECOMMENDATIONS
8: LIMITATIONS OF INSPECTIONS & REPORT
CLASSIFIED:
UNSAFE (CYCLE 6 CONDITIONS)
SWARMP
SAFE
DATF: OCTOBER 20. 2010
ARC No: LL 145 2010
Tb: reps, aid topes Ibueol ate to! edeWed la be used In M1,013001 pleases withal lbe pe;atatiun el
• •
35 :Milian", by a Minn," uthle,, o e InMsnaral eirOgati.
2010 Arddecusee Re SEMI o' Uri WI Jfit.-.
1.I i •
Maned-
EFTA01084314
I. EXECUTIVE SUMMARY:
The following summary
is intended to provide an
executive overview consist-
ing of a summary of fled
legs and recommendations,
a concise statement of the
scope of the inspection
and findings, the conclu-
sions and recommendations
and a determination as
to whether the building
is categorized as Safe".
SWAMI", or "Unsafe.
las defined in Pak 32-03 by the
Department of Bulldogs).
Summary of Findings:
9 East 71st Street is a seven (7) story residential building. The structure is
generally rectilinear in shape and is approximately 50' x 92' in plan. Of the four
major facades, the south facade is considered the "street elevation." There are no
fire escapes on the building.
Built ca. 1910, the building's structure is assumed to be steel frame and is listed
as Class 1 fireproof construction. The street facade is clad with St. Maxim's
limestone and off-street facades with beige brick. The building has south facade
balconies at the second floor, fourth floor, sixth floor and a terrace at the seventh
floor. Fenestration consists of wooden French windows and double-casement
windows of varying sizes. Window sills are typically limestone.
Before on-site examinations were conducted, the building's Cycle 6 Local Law
11/98 report was reviewed. Visual examinations were performed from the
bulkhead roof, seventh floor terrace, south yard, east court, and each balcony of
the south facade. 9 East 71st was also examined from the balcony and rear yard
of its neighbor to the west, and roof and rear yard of its neighbor to the east.
A Physical Examination was performed on the street (south) facade from two
suspended swing stage scaffolds.
Several uncorrected Cycle 6 conditions occur on various facades and include
spalled stone, broken stone units, cracked brick and deteriorated expansion joints.
Conditions that are Safe With A Required Maintenance Program occur on each
facade and include cracked brick, deteriorated steel lintels, spalled stone, and a
cracked window sill. Safe conditions are also found on each facade and include
eroded mortar joints at brick and stone, metal railings and fences in need of
painting and deteriorated sealant.
The building has beed categorized as "Unsafe" due to unaddressed Cycle 6
conditions. We recommend that repairs described within this report commence as
soon as possible to correct "Unsafe" and SWARMP conditions to achieve "Safe"
status.
Building Categorized As:
2, Unsafe
K SWARMP (Safe with a Repair and Maintenance Program)
K Safe
PAGE F 2
9E 71 - FACADE INSPECTION REPORT: CYCLE 7
EFTA01084315
arcpC
A. PROPERTY INFORMATION:
Building Address:
9 East 71st Street
New York, NY 10021
A.K.A.:
NIA
Block/Lot:
1386110
Building Identification No. (BM:
1041354
Certificate of Occupancy:
CO 101428
Landmark Status:
O Landmarked
K Not Landmarked
Nearest Cross Street:
Fifth Avenue I Madison Avenue
Property Profile Overview (BISI:
Refer to Appendix 1: BIS Property Profile Overview
Location Plan:
Nine East 71st Street Corporation
B. OWNER INFORMATION:
Owner's Name:
Owner's Mailing Address:
Owner's Telephone Number:
9 East 71st Street
New York, NY10021
12121750-9895
Principal 1 Title:
Jeffrey Epstein, President
PAGE 13
9 E 71 - FACADE INSPECTION REPORT: CYCLE 7
EFTA01084316
C. DESCRIPTION OF BUILDING
Number of Stories:
1
Building Height fftl.•
120
Approximate Plan Dimensions (fa 50 x 92
Certificate of Occupancy No.:
101428
Usage:
▪
Residential
K Commercial
K Institutional
Approximate Age:
Built in 1910
Exterior Wall Type:
Z.
Masonry
•
Curtain Wall
D. SETTLEMENTS, REPAIRS & REVISIONS TO EXTERIOR ENCLOSURES
Settlements Since Last Report:
No Settlements Observed
•
Settlements Observed, as Follows:
Repairs Since Last Report
O
K
No Repairs Observed
Repairs Observed, as Follows:
K Repointing
.1-3
Window Sill Replacement
K Masonry Restoration
K Stone Repairs
K Parapet Reconstruction
K Repainting of Fire Escapes
K Lintel Replacement
K Cornice Replacement
K Other (Fill In)
K Other (Fill In)
Revisions Since Last Report:
No Revisions Observed
K Revisions Observed, as Follows:
PAGE I 4
9 E 71 - FACADE INSPECTION REPORT: CYCLE 7
EFTA01084317
E. CRITICAL EXAMINATION PROCEDURES
Scope of Examination:
The following procedures were followed in performing the critical
examination:
1. Review of facade inspection report corresponding to prior cycle.
2. Visual examination of all applicable exterior walls subject to examination using
high powered binoculars and digital cameras.
3. Physical examination of representative samples of the exterior walls.
4. Comparison of findings between prior cycle's filed report and current cycle's
examination.
PAGE 15
9 E 71 - FACADE INSPECTION REPORT: CYCLE 7
EFTA01084318
F. METHODS USED TO CONDUCT INSPECTION:
Physical Examination:
A physical examination of a representative sample of a street front wall
was performed from:
ai Suspended Swing Stage Scaffold.
K Telescopic Boom Lift.
K Existing Fire Escape(s).
K Pipe Scaffolding.
Refer to "Location Diagram (Part zr on the next page for the exact
location(s) of physical examination(s).
Critical Examination by:
Joakim Aspegren, R.A.
ARC, M.
12 West 23rd Street, New York, NY 10010
Tel: 1212) 3677472
License Number: 30058
Inspections by:
ate from ARC, PCI
Joakim Aspegren, R.A.
Graham Roscoe, R.A.
Mamata Melia, Assoc. AIA
Rigging by:
Herbert Rose, Inc.
4025 Crescent Street
Long Island City, NY 11101
(718) 7294900
License No: 5739
Location Diagram Part 1):
The adjoining location diagram
depicts the overall context of the
property for the purpose of indi.
eating the nearest cross street.
The building's main entrance and
locations of close•up inspections
have been depicted in the follow-
ing page under Location Diagram
Part 2/.
IORT
0
C
I
PAGE 16
9 E 71 - FACADE INSPECTION REPORT: CYCLE 7
EFTA01084319
F. METHODS USED TO CONDUCT INSPECTION (CONTINUED FROM PRIOR PAGE):
Location Diagram (Part 21:
The adjoining location diagram
depicts the location of the build-
ing's main entrance and locations
of close-up inspections which have
been identified through the follow-
ing legends:
0 MAIN ENTRANCE
A PlITSICAL EXAMINATION
Refer to Location Diagram (Part 11
shown on prior page for a depic-
tion of the building's overall con-
text and nearest cross street.
,..,__.;
1-_-+
El
0
MIMEO
0
r I
OUU009
EAST COURT
I
MAIN ROOF
BUlatAD
6FL BUXOM'
i
i
-11
0C11
AFL BALCONT
Critical and Physical Examination Dates:
Start
Finish
Physical Inspections
06.08.2010
06.08.2010
Critical Examination
04.13.2010
10.20.2010
PAGE I7
9 E 71 - FACADE INSPECTION REPORT: CYCLE 7
EFTA01084320
G. REPORT OF CONDITIONS OBSERVED: CYCLE 7
Significant Deterioration:
•
No Significant Deterioration or Movement Detected.
K Significant Deterioration andlor Movement Detected. Refer to Section
Di. of this report for further information.
Budding Water Tightness:
K Leaks Reported. Building is not watertight
E No Leaks Reported. Building is watertight
Classification of Conditions
Observed.
For a classification of each condition observed refer to:
IE Appendix 5: Reference Drawings: Roof Plan
IE Appendix 6: Reference Drawings: Elevations
Condition of Exterior
Appurtenances
Existing exterior appurtenances
have been identified under the
"In-Situ" column. Those appur-
tenances whose condition is
considered deleterious have been
identified as such under the
Deleterious' column on the adja-
cent table.
Appurtenance
In-Situ
Deleterious
Exterior Fixtures
Flag Poles
Signs
Parapets
Copings
Guard Rails I Balustrades
Window Frames
Window Guards
Flower Boxes
Communication Equipment
Air Conditioners
Balconies
Cornice
Chimneys
Safe Conditions Requiring
Maintenance:
For a list of Safe Conditions requiring monitoring andlor routine maintenance refer
to:
•
Appendix 5: Reference Drawings: Roof Plan
•
Appendix 6: Reference Drawings: Elevations
•
Appendix 7: Maintenance Recommendations
PAGE I 8
9E 71 - FACADE INSPECTION REPORT: CYCLE 7
EFTA01084321
H. ANALYSIS OF THE CAUSES OF THE CONDITIONS REPORTED AS UNSAFE OR SWARMP
The following are deemed to be
a Eroded Masonry, Stone or Terra Cotta Joints
the causes for conditions reported
Natural weathering.
as Unsafe or SWARMP:
a Cracked I Spoiled Brick Masonry, Stone or Terra Cotta
Thermal expansion and contraction, corrosion of underlying or adjacent
steel, deteriorated joints.
Cracked I Spoiled Stucco
Thermal expansion and contraction, corrosion of underlying or adjacent steel.
a Cracked I Spoiled Window Sill
Thermal expansion and contraction, corrosion of underlying steel, deteriorated
joints.
a Deflected Steel Lintells)
Corrosion of steel.
a Peeling Paint or Coating
Natural weathering.
a Deteriorated Sealant
Natural weathering.
I. STATUS OF EXTERIOR MAINTENANCE
This property has been found to
be:
a Regularly Maintained.
K Not Maintained.
PAGE 19
9 E 71 - FACADE INSPECTION REPORT: CYCLE 7
EFTA01084322
J. COMPARISON OF FINDINGS WITH PRIOR REPORT: CYCLE 6 LOCAL LAW 11198 REPORT
This section consists of a com-
parison of currently observed con-
ditions with conditions observed
during the previous report filing
cycle examination, including the
status of repairs or maintenance
performed with respect to the
prior conditions.
This section lists any permits used
after the prior report was filed for
the purpose of correcting condi-
tions noted for repair in the Cycle
6 Local Law 11/98 Report.
Prior Observed Conditions:
K No Conditions Reported
a Deteriorated Paint Finishes
K Open Masonry Joints
a Open Sealants
O Deteriorated Brickwork
0 Deteriorated Masonry
K Deteriorated Parapet
K Rusted Fire Escapes
K Deflected Lintels
K Deteriorated Cornice
K Cracked Window Sills
Comparison of Conditions Reported:
K No Prior Conditions Reported
K Conditions Partially Corrected
K Conditions Uncorrected
K Conditions Corrected. All conditions observed in the prior Cycle 6
report have been corrected.
Department of Buildings Permits:
•
No Facade Work Permits Since Prior Report On Record
•
Facade Work Permits on Record Since Prior Report:
Item
Permit Number
Sign•off Date
Open Facade Violations:
•
No ECB Violations on Record
7 ECB Violations on Record:
Violation No:
Violation Type
Date Issued
PAGE 1 10
9 E 71 - FACADE INSPECTION REPORT: CYCLE 7
EFTA01084323
K. RECOMMENDATIONS FOR REPAIRS OR MAINTENANCE
Repair Code
Repair Recommendations
Repair By
Permit
B-PNT 075 CON
Brick Pointing: Concave Tooling. Cut existing mortart to at
least 314" and apply new mortar in lifts. Provide concave tooled
SAFE
finish.
No
BAST 101
Brick Restoration: 1 Wythe. Remove one (1) wythe of deterio-
rated brick(s) and stitch in new face brick(s).
UNSAFE: C6
Yes
BAST 101 CRK
Brick Restoration: Replacement of Cracked Bricks. Remove
cracked brick; stitch in new face brick with stainless steel
anchors along path of crack.
Steel Painting. Scrape, prep and paint steel elements li.e.
lintels, fire escapes, railings, etc.).
1012015
Yes
F-MTL 101
SAFE
No
M-FLA 002
Metal Flashing. Provide metal or fluid applied flashing.
SAFE
Yes
Lintel Replacement (Less than 41 Installation of new steel
M-LIN 103 L
lintel to match existing; includes flashing, anchors & (3) courses
1012012
of brick above.
No
MA-PNT 101 CON
Masonry Pointing. Rake joints & finish with a standard
concave joint.
Masonry Patching Repair. Remove loose material, saw cut
edge of void and fill with patching material.
Masonry Sill Replacement: Limestone. Replace window sill
with limestone unit. Install fluid applied waterproofing under sill.
Sealant Replacement at Gutter. Remove existing sealant,
prime substrate and install new sealant.
SAFE
No
MA-PTC 101
UNSAFE: C6
Yes
MA-SIL 101 L-FLD
1012015
Yes
S-GUT 101
SAFE
No
S-WAL 101 EXP
Sealant Replacement at Expansion Joint. Remove existing
sealant, prime substrate and install new sealant set on backer
UNSAFE: C6
No
rod.
Sealant Replacement at Window Perimeter. Remove existing
S-WIN 101
sealant, prime substrate and install new sealant set on backer
SAFE
rod or bond breaking tape.
No
ST-COP 101 L
Stone Coping Replacement: Replace limestone coping with
new unit.
UNSAFE: C6
Yes
PAGE I II
9 E 71 - FACADE INSPECTION REPORT: CYCLE 7
EFTA01084324
MrcpC
L. WORK PERMITS REQUIRED
The following permits Kul/b°
General Construction Permit for Exterior Work (Alteration Type 2)
required to perform the work roc-
"3Is' Sidewalk Shed Permit
&mended in this report:
0
Scaffolding Equipment Permitls1
O Certificate of No Effect from Landmarks Preservation Commission
K
No Work Permits Are Required Because:
Work is Exempt from Permit Requirement as per TPPN 1199
No Work is Required
PAGE 1 12
9 E 71 - FACADE INSPECTION REPORT: CYCLE 7
EFTA01084325
M
M. PHOTOGRAPHS
1. Street facade.
9 E 71 - FACADE INSPECTION REPORT: CYCLE 7
PAGE I 13
EFTA01084326
MrcpC
M. PHOTOGRAPHS
Photo No. Repair Code:
Repair Recommendation:
01
B.PNT 075 CON
BRICK POINTING: CONCAVE TOOLING
Repair Cede:
r.
Repair Recommendation:
B•RST 101
BRICK RESTORATION: 1 WYTHE
PAGE 14
9 E 71 - FACADE INSPECTION REPORT: CYCLE 7
EFTA01084327
MrcpC
M. PHOTOGRAPHS
1
_
Photo No
03
Repair Code:
Repair Recommendation:
B•RST 101 CRK
1 BRICK RESTORATION: REPLACEMENT OF CRACKED BRICKS
9 E 71 - FACADE INSPECTION REPORT: CYCLE 7
EFTA01084328
MrcpC
M. PHOTOGRAPHS
PAGE li
9 E 71 - FACADE INSPECTION REPORT: CYCLE 7
EFTA01084329
MrcpC
M. PHOTOGRAPHS
Repair Recommendation:
STONE COPING REPLACEMENT: LIMESTONE
Repair Recommendation:
MASONRY POINTING: CONCAVE FINISH
9 E 71 - FACADE INSPECTION REPORT: CYCLE 7
EFTA01084330
MrcpC
M. PHOTOGRAPHS
Photo No.' Repair Code:
09
I MA•PTC 101
Repair Recommendation:
MASONRY PATCHING REPAIR
Photo No.' Repair Code:
Repair Recommendation:
10
MA SIL 101 FLO
MASONRY SILL REPLACEMENT: LIMESTONE
PAGE 1$
9E 71 - FACADE INSPECTION REPORT: CYCLE 7
EFTA01084331
M. PHOTOGRAPHS
No. Repair Code:
Repair Recommendation:
SEALANT REPLACEMENT AT GUTTER
9 E 71 - FACADE INSPECTION REPORT: CYCLE 7
EFTA01084332
MrcpC
M. PHOTOGRAPHS
Photo No.' Repair Code:
I Repair Recommendation:
13
&WIN 101
SEALANT REPLACEMENT AT WINDOW PERIMETER
PAGE 1 20
9E 71 - FACADE INSPECTION REPORT: CYCLE 7
EFTA01084333
N. CLASSIFICATION OF BUILDING
Building Categorized as:
las defined in Rule 3203 by the
Department of Burldngsl.
Definitions
Safe Conditions:
Z Unsafe
:LT
SWARMP (Safe with a Repair and Maintenance Program)
Safe
Safe means a condition of a building wall, any appurtenances thereto or any part
thereof not requiring repair or maintenance to sustain the structural integrity of
i
the exterior of the building and that will not become unsafe during the next five
years.
Safe Conditions with a Repair and Safe with a repair and maintenance program means a condition of a building wall,
Maintenance Pro gram awARmpt any appurtenances thereto or any part thereof that is safe at the time of inspec-
tion, but requires repairs or maintenance during the next five years in order to
prevent its deterioration during that five year period into an unsafe condition.
Unsafe Conditions:
Unsafe Conditions are defined as "a condition of a building wall, any appurte•
nances thereto or part thereof that is dangerous to persons or property and
requires prompt remedial action. In addition, any condition which was reported
as safe with a repair and maintenance program .in an earlier report and which is
not corrected at the time of the current inspection shall be reported as an unsafe
condition."
0. PROFESSIONAL SEAL & SIGNATURE
Professional Seal:
Signature:
1012012010
PAGE 21
9 E 71 - FACADE INSPECTION REPORT: CYCLE 7
EFTA01084334
MrcpC
P. APPENDIX 1: BIS PROPERTY PROFILE OVERVIEW
Po :petty Profile Overview
I or I
NYC
Buildings
9 EAST 71 STREET
EAST 71 STREET
hup://a8I0-biswebaot.govjelsweb/ProoeityProfileOverviewServIerheq...
tie
.gov
always open
cucx HERE TO SIGN UP FOR BUILDINGS NEWS
NYC Department of Buildings
Property Profile Overview
MANHATTAN 10021
BINS 101364
9 . 9
Health Area
:0100
Tax Block
1386
Census Tract
:130
Tax Lot
10
Community Board
:108
Condo
NO
Buildings on Lot
: 1
Vacant
NO
View DCP Addresses...
Browse Block
Ykw Zoning rtnrurnroll
View Ch.11enge Results
Yir w Certificates of Occupancy
Cross Streegs):
DOB Special Place Name:
DOB Building Remarks:
5 AVENUE. MADGCN AVENUE
Landmark Status:
L- LANDMARK
Special Status:
ALA
Local Law:
YES
Loll Law:
NO
SRO Restricted:
NO
TA Restricted:
NO
US Restricted:
NO
Little I' Restricted:
N/A
Grandlathered Sign:
ND
Legal Adult Use:
NO
City Owned:
NO
Additional BIN, for Building:
NONE
Special District:
LII.IA LIMITED HEIGHT
This property is not located in an area that may be affected by Tidal Wetlands. Freshwater Wetlands. or Coastal Erosion Hazard
Area. Click here ler more inlorrrolion
Department of Finance Building Classification:
A5.1 FAMLY DWELLING
Please Nola: 11•4 Depactmen al F Waxes bolero csassiscavan elormalcn sham a Palings tix stans.wilt maim, been same as mokbal moor On
snet.na recoveries te Veal us* el a sirucloo. towaich the wrote; ce tie merrier' *musings
TOW
Open
Elevator Records
Complaints
2
0
gittsuira/Staliaain
Viobtions.DOB
21
4
Permits In•Process / Issued
Violationstat (DOBI
3
0
Illuminated Signs Annual Permits
Jobs,rdinos
10
Plumbing Inspections
ARA ILAA Jobs
0
Open Plumbing Jobs I Work Types
Facades
Total Jobs
10
Marquee Annual Permits
Actions
as
Boiler Records
OR Enter Action Type:
DEP Boller Information
OR Select from List:
Select...
AND Show Actions
If you have any questions please review these Frequently Asked CI-anions. the Glossary. or call the 311 Citizen Service
Center by dialing 311 or (212) NEW YORK outside of New York City.
716/20106:03 PM
PAGE 122
9 E 71 - FACADE INSPECTION REPORT: CYCLE 7
EFTA01084335
MrcpC
P. APPENDIX 2: ECB FACADE VIOLATION SUMMARY
No open Environmental Control Board (EGO) facade violations.
Open violations. Refer to list below.
ECB Query By Location
NYC
Buildings
hup://a810-bisweb.nyc.grwfbisweb/ECBQueryByLocationServier?reques...
NYC Department of Buildings
ECB Query By Location
ICC
ga
t '
always open
CI ICK HFRF TO MP, UP FOR RUH DINGS NEWT
Premises: 9 EAST 71 STREET MANHATTAN
BIN: 1041354
Block: 1386
Lot: 10 CB: 108
A Eat NUM
RESPONDENT NAME
DATE OF ISSUANCE 8
DOB VIOL NUMBER
VIOL TYPE
STATUS
INF CDPROV LAW
S 38062427J
9.11111 JEFFREY J
C430697E825A2
ELEV
AFF ACC
BP7
27987
S 34314696K
NNE EAST 71 STREET
060302LL1080HAZ
LLAW
Mr ACC 805 27-129(DR1)
0 34012554L
BRCH VNIAT HEN SCHOOL
082488CBGCO2
CONS
AFF ACC
802 27-215
If you have any questions please review these Eteaueosyssted_cyaspons, the Glossary, or call the 311 Citizen
Service Center by dialing 311 or (212) NEW YORK outside of New York City.
PAGE 123
9 E 71 - FACADE INSPECTION REPORT: CYCLE 7
EFTA01084336
MrcpC
P. APPENDIX 3: ECB FACADE VIOLATION DETAILS
No open Environmental Control Board (FOB} facade violations.
Open violationIsl. Refer to violation below.
PAGE 120
9 E 71 - FACADE INSPECTION REPORT: CYCLE 7
EFTA01084337
P. APPENDIX 4: BIS PROPERTY PROFILE OVERVIEW, FACADE & SHED APPLICATIONS
Permits In•Process /Issted by Nowise*
NYC
Buildings
hap://a810-biswob.nyc.gov/bisweb/PenritsInhotessIssuedByBinServIeL..
NYC Department of Buildings
PIC
gov
always open
tg CLICK HERE TO SIGN UP FOR Bull Divas tom
Permits In-Process
Premises: 9 EAST 71 STREET MANHATTAN
JOB
SEG
ISSUED
NUMBER
TYPE
NO
DATE
Issued by Premises
BIN:
EXPIRATION
DATE
STATUS
1041364 Mode 1386 Lot: 10
APPLICANT NAME
103172406-01-EO SF
A3 ALT3
01
08/04/2002
0401/2033
ISSUED
OFARRELL PETER
10317148901 .EN' OT
A2 - ALT2
02
0119/2002
0501/2003
ISSUED
ROSENWACH ANDREW
103068564.01.EO SH
A3 -ALT3
01
01012002
12/31/2002
ISSUED
OFARRELL PETER
10037478101.EW FP
A2 - ALT2
01
0327/1992
0110/11993
ISSUED
KERR PAICHEAL
100089093-01-EO SF
A3 -ALT3
02
01111990
10011991
REISSUED
BUTTNER JOHN
100057876-01-E007
A3 -ALT3
02
01001991
010B1902
ISSUED
BOPP JOSEPH
100051514431-FW
A2 - ALT2
01
0312/1991
11437/1991
ISSUED
HIRSCH MORTY
1P0004541501-
04
0420/992
0301/1993
ISSUED
VAN NOSTRANO SAL
'P0007071501-
04
08251992
1001/1993
REISSUED
BUTTNER JOHN
I oil
If you have any questions please review these Frectuently Allred Coed:one the Glossary or call the 311 Citizen
Service Center by dialing 311 or (212) NEW YORK outside of New York City.
7/6/20106:06 PM
PAGE 125
9 E 71 - FACADE INSPECTION REPORT: CYCLE 7
EFTA01084338
P. APPENDIX 5: REFERENCE DRAWINGS: ROOF PLAN
991.101EAD
C-Lit lOI UN ON
BHT
CYCLE 6 CONDITION
SI-COP 101 L
WE
1®IB®FVt
e
MAIN ROOF
BULKHEAD
EAST COURT
BUMF-4
0
6 FL BALCONY
r
1
r
i
r I
4 FL BALCONY
ROOF PLAN
9 E 71 - FACADE INSPECTION REPORT. CYCLE 7
EFTA01084339
P. APPENDIX 6: REFERENCE DRAWINGS: ELEVATIONS
TIM FI
OW 6 cowman
bo-ptc ICH IN PIP
Mar
I
6114 ROM
tl
r.
.„._—_,..
,,,,...
UK FIC01
• •
Isis
f •E
-
I I
1
1
N.
I
PH I
PI
L.ME
CI=
VA-PIC 101 WI
\
LI:
I
lil
l
lin
LN
1_1
n
MR
L__
IA ROOR
6-
i
_
)
.:.
( )
,
I '.\,
..,,,
(---,,--)
..,
r.i
—
EMT—
IM-Pla 101 COI IMMO 010
ENIVOti011 I:
SOUTH FACADE
9 E 71 - FACADE INSPECTION REPORT. CYCLE 7
EFTA01084340
6
P. APPENDIX 6: REFERENCE DRAWINGS: ELEVATIONS
EFTA01084341
arc„
P. APPENDIX 6: REFERENCE DRAWINGS: ELEVATIONS
Elevation 3:
WEST FACADE
9 E 71 - FACADE INSPECTION REPORT. CYCLE 7
EFTA01084342
P. APPENDIX 6: REFERENCE DRAWINGS: ELEVATIONS
Elevation 4:
_MI
EAST FACADE
9 E 71 - FACADE INSPECTION REPORT: CYCLE 7
EFTA01084343
P. APPENDIX 6: REFERENCE DRAWINGS: ELEVATIONS
Elevation 5.
EAST COURTYARD
9 E 71 - FACADC IWSPECBO 寸 RCPORT CYCLE?
EFTA01084344
P. APPENDIX 7: MAINTENANCE RECOMMENDATIONS
Maintenance Recommendations: The following recommendations pertain to normal building maintenance practices
which are not within the scope of this Report. They are intended for implementation
by Building Management:
•
The condition of the building facades and appurtenances should be monitored
regularly and routine maintenance performed. Maintain a file of building leaks
and of work performed on the building's envelope.
•
Potential problems should be promptly referred by Building Management to a
registered architect or professional engineer to determine whether precaution•
ary or corrective work is required.
•
Window ledges, terrace, railings and other areas should be monitored to confirm
that no loose or unstable items or objects that may fall are placed upon them.
These items are sometimes installed on a temporary basis.
•
Periodically verify that window mounted, through•the-wall and other removable
air conditioner units are properly installed, and supported at all times.
•
Roof and terrace drains should be monitored and maintained clear at all times.
PAGE 132
9 E 71 - FACADE INSPECTION REPORT: CYCLE 7
EFTA01084345
P. APPENDIX 8: LIMITATIONS OF INSPECTION & REPORT
Limitations of Inspection & Report:
Nothing in this report is intended as an opinion as to the adequacy of the original
design, construction, any additions, repairs or maintenance work, past or future.
Dimensions included herein are approximate, within the accuracy requirements of
the report. Information as to building age and history have been obtained from
independent sources and accuracy is not guaranteed.
This report was prepared solely for compliance with the requirements of Local Law
11198 for Periodic Inspection of Exterior, Walls and Appurtenances. This inspection
was limited to a critical visual and physical inspection of building elements evalu-
ated herein, preparation and filing of this report. The opinions expressed in this
report are based upon conditions observed at the dates of inspection. This report
is without benefit of an inspection involving sub-surface exploration, testing, or
structural analysis.
The repair recommendations contained herein are general in nature and further,
detailed information will be required for construction purposes.
A copy of this report was given to the Owner prior to filing with the Department of
Buildings and no exceptions were taken. The owner has acknowledged awareness
of the required repairs and/or maintenance, if any, and the time frame for same.
PAGE 133
9 E 71 - FACADE INSPECTION REPORT: CYCLE 7
EFTA01084346
Technical Artifacts (14)
View in Artifacts BrowserEmail addresses, URLs, phone numbers, and other technical indicators extracted from this document.
Domain
a810-biswob.nyc.govPhone
(718) 7294900Phone
12012010Phone
1212) 3677472Phone
12121750Phone
17148901Phone
3068564Phone
3172406Phone
4541501Phone
7071501Phone
7478101Phone
8251992Wire Ref
REFERENCEWire Ref
ReferenceRelated Documents (6)
DOJ Data Set 10OtherUnknown
EFTA01682184
186p
DOJ Data Set 10OtherUnknown
EFTA01370863
1p
Dept. of JusticeOtherUnknown
Medical Record/Clinical Encounter: DOJ-OGR-00026334
This clinical encounter document from the Bureau of Prisons details a medical evaluation of Jeffrey Epstein on July 12, 2019. It covers his medical history, current complaints, and treatment, including discussions around his triglyceride levels, sleep apnea, and back pain. The document was generated by the treating physician at the Metropolitan Correctional Center in New York.
1p
DOJ Data Set 8CorrespondenceUnknown
EFTA00014087
0p
DOJ Data Set 11OtherUnknown
EFTA02367961
1p
DOJ Data Set 10OtherUnknown
EFTA01977826
2p
Forum Discussions
This document was digitized, indexed, and cross-referenced with 1,400+ persons in the Epstein files. 100% free, ad-free, and independent.
Annotations powered by Hypothesis. Select any text on this page to annotate or highlight it.