GENERAL
POWER
Diesel Generators 10. 3200 Kw I Alternators 6.3500 Kra I Transfer Switches I Fuel Tanks I Trailers I Engles Parts I Alternator Parts
SONO I KOHLER I EROIRYROINN I HIPCMER I JCI-ei CEERE I CUMMINS I PERO'S I MliSODSHI I VOLVO I STA/AFCRO I LEROY SOMER
GP J8OUC3
Engine JOHN DEERE, 4045HFS82, EPA/CARB Tier 3
Alternator LEROY SOMER , LSA43.2L8
80 KW JOHN DEERE GENERATOR
80 KW ! 100 KVA DIESEL GENERATOR SET. FULLY PACKAGED:
•
JOHN DEERE Heavy duty diesel engine. 4 stroke. 1800rpm. Turbo. EPA
•
LEROY SOMER brushless alternator. IP23 protection. Insulation class H
•
SCHNEIDER. Main line circuit breaker. wired. maximum output rated
•
EPA Tier 3 compliant engine per U.S. Environmental Protection Agency
•
Digital auto-start control panel. CE and UL compliant
•
Incorporated metallic fuel tank for day use
•
Auto Start control feature included for interoperation with ATSIAMF
•
12V charging alternator and 12V DC electric starter motor
•
12V charged DC starting battery with electrolyte and cables
•
Dry type air filter. fuel filter and oil filter elements installed
•
Mechanically welded chassis with vibration isolators
•
Each unit prototype and individually factory load bank tested
•
The generator accepts 100% rated load in one step as per NFPA110
and meets IS08528.5 class G-3 for transient response
•
Compliant with ISO3046. ISO8528. BS4999. BS5514. BS500OPT99.
AS1359. IEC34. UTE5100. VDE0530 and IS09001:2000
AVAILABLE ACCESSORIES AND OPTIONS:
•
Steel or Aluminum weather proof. sound attenuated enclosures
•
UL142 listed. double wall fuel tanks from 50 to 10.000 Gal
•
UL1008 listed, automatic transfer switches from 50 to 3000 Amp
MI
compliant heavy duty road trailers from 3000 to 30000 Lbs
•
Automatic battery chargers. Engine pteheaters. Remote annunciators
and many more
Voltage
Power ESP
kWelcVA
Power PRP
kWe,kVA
Standby Amps
Dimensions - Open
Weight - Open
480/277
801100
73 / 91
120
460/265
801100
73/91
126
Length: 1950mm [77in)
1170kg [2579lbs] Net
440/254
78/ 98
71189
129
Width: 1084mm [43in]
1370kg [3020lbs] Gross
240/139
75 / 94
68/85
226
Height: 1350mm [53in)
230/133
70/ 88
64/80
221
220/127
78 / 98
71 /89
257
208/120
74 / 92
67 / 84
255
POWER DEFINITION
PRP : Prime Power is available for an unlimited number of annual operating hours in variable load applications. in accordance with ISO
8528.1.
ESP : The standby power rating is applicable for supplying emergency power in variable load applications in accordance with ISO 8528-
1. Overload is not allowed.
TERM OF USE
Standard reference conditions ESP)PRP 25 C°/25 C° Air Inlet Temp. 1000 m/1000 m m A.S.L. 60 % relative humidity.
WEATHER PROOF / SUPER SILENT ENCLOSURES
Model
dB(A)@31t
dB(A)@231t
Dimensions - Enclosed
Weight - Enclosed
Tank
M129
78
68
Length: 2554mm [101in]
Width: 1150mm 145in]
Height: l 680mm (661n]
1590kg [35051bs]
1790kg [39461bs]
190 L
50 Gal
GENERAL POWER LIMITED, INC
EFTA01097440
GENERAL
POWER
Diesel GenerMors 10.3200Kw 1 ANNTIMOlt 6.3600 Kra I Tress* Snitches I Fuel Tanks I 'Ewen I Engine Puts I Alternator Pelts
SONO I KOHLER I eROPDCROWN I HIPONER I JON DEERE I CUMMINS I PERKIN I MITSUSGHI I VOLVO I STAMFORD I LEROY SUMER
ENGINE SPECIFICATIONS
DATA
GENERAL DATA
Engine model
Cylinders-arrangement
Displacement (C.I.)
Bore (mm) X Stroke (mm)
Compression ratio
Speed (RPM)
Pistons speed (mis)
Maximum stand-by power at rated RPM (kW)
Frequency regulation (%)
BMEP (bar)
Governor type
JOHN DEERE 4045HFS82,
4-strokes, TURBOCHARGED, AIEVAIR, 4 Cylinders,
U.S. EPA / CARS TIER 3
4-L
4.48
106 X 127
19 : 1
1800
7.62
94
+/-0.5%
12.8
ELECTRONIC
EXHAUST SYSTEM
Exhaust gas temperature (°C)
Exhaust gas flow ([is)
Max. exhaust back pressure (mm CE)
576
307
750
FUEL SYSTEM
Fuel consumption 110% load
Fuel consumption 100% load
Fuel consumption 75% load
Fuel consumption 50% load
Maximum fuel pump Itchy
25.06 Uhr [6.6 gal/hr]
22.8 Uhr [6.0 gaUhr]
20.31 Uhr [5.3 gal/hr]
14.98 Uhr [3.9 gaUhr]
59.29 Mr [15.6 galihr]
OIL
Oil capacity (L)
Min. oil pressure (bar)
Max. oil pressure (bar)
Oil consumption 100% load (L/h)
Carter oil capacity (L)
13
t.05
3
0.06
12
THERMAL BALANCE
Heat rejection to exhaust (kW)
Radiated heat to ambiant (kW)
Haet rejection to coolant (kW)
89.22
11.46
52.55+11.8
AIR INTAKE
AIR INTAKE_entree_max%
Intake air flow (Us)
375
110.67
EMISSIONS
Emissions PM (g/kWh)
Emission CO (g/kW.h)
Emissions HCNOx (g/kWh)
Emission HC (g/kW.h)
0.25
1.47
3.43
0.14
GENERAL POWER LIMITED, INC
EFTA01097441
GENERAL
POWER
Diesel Generators 10.3200 Kw I Altemators 6.3600 Kra I TranslerSvilleMs I Fuel Tanks I Trailers I Engine Parts I Allema!weans
SDVO I KOKER I BRINLIYROWN I IIICKYAER
OCIISCEERE I CUMMINS I PERKINS I VITSVEL.SHI I vas° I STAMFORD I LEROY SOV.ER
ALTERNATOR SPECIFICATIONS
DATA
GENERAL DATA
OTHER
DATA
Alternator brand
Alternator
Number of phase
Power factor (Cos Phi)
Altitude (m)
Overspeed (rpm)
Number of pole
Excitation system
Insulation class / Temperature class
Automatic Voltage Regulator
Total harmonics TGHITHC
Wave form : NEMA=TIF-TGH/THC
Wave form : CEI=FHT-TGH/THC
Number of bearing
Coupling
Voltage regulation 0 to 100%
Recovery time (Delta U = 20% transitoire) (ms)
Continuous Nominal Rating 40°C (kVA)
Standby Rating 27°C (kVA)
Efficiencies 4/4 bad (%)
Air flow (cfm)
Short circuit ratio (Kcc)
Direct axis synchro reactance unsaturated (Xd) (%)
Quadra axis synchro reactance unsaturated (Xq) (%)
Open circuit time constant (Tdo) (ms)
Direct axis transient reactance saturated
(%)
Short circuit transient time constant
(ms)
Direct axis subtransient reactance saturated (XV) (%)
Subtransient time constant (7d) (ms)
Quadra axis subtransient reactance saturated (X-q) (%)
Zero sequence reactance unsaturated (Xo) (%)
Negative sequence reactance saturated (X.2) (%)
Armature time constant (Ta) (ms)
No load excitation current (io) (ms)
Full load excitation current (Ic) (A)
Full load excitation voltage (uc) (A)
Recovery time (Delta U = 20% transitoire) (ms)
Motor start (Delta U = 20% perm. or 50% trans.) (ms)
Transient dip (4/4 charge) - PF : 0.8 AR (%)
No load losses (kW)
Heat rejection (kW)
LEROY SOMER
LSA43.2L8
3
0.8
<1000
2250
4
Sell Excited
H H
R250
<2
<50
<2
1
DIRECT
+1-0.5%
500
95
107
91.1
0.32
0.4
293
176
1431
10
50
5
6.3
0.8
5.8
B
0.4
1.6
29
500
269
14
2.06
7.57
___LEROY®
GENERAL POWER LIMITED, INC
1350 NW 78 Avenue / Miami, Florida 33126
EFTA01097442
LISTED
GENER
POWER
Diesel Generators 10.3200 Kw I Attemstors 6.3500 Kra I TransferSwitches I Fuel Tanks I Trailers I Engine Parts I AllematorPaits
SULIO r KOHLER I BROADCROWN I !LIPNER r KOHL`rl GEER& I CUMI.INS I PERQIS I MIT9JEKSHI I VOLVO I STAMFORD I LEROY SOMER
CONTROL PANELS
Standard
NEXYS
sin
NIEXYS
IMO
• e
Specifications : Frequency meter. Ammeter. Voltmeter
Alarms and faults : Oil pressure, water temperature,
Overcrank. Overspeed ( >60 kVA). Min/max alternator, Low
fuel level. Emergency stop
Engine parameters : Hours counter, Engine speed, Battery
voltage, Fuel level, Alr preheating
0 'lion
TELYS2
ACCESSORIES AND OPTIONS
Specifications : Frequency meter, Ammeter. Voltmeter
Alarms and faults : Oil pressure. water temperature. No start-
up. Overspeed. Minimax alternator. Minimax battery voltage.
Low fuel level, Emergency stop
Engine parameters : Hours counter, Oil pressure. Water
temperature, Engine speed. Battery voltage. Fuel level
Remote monitoring and control
0•ti011
Automatic Transfer Switches, UL1008 listed: 100 to 4000 AMPS
ASCA
EMERSON r
U
I
With a Series 300 transfer switch, you get a product backed by
ASCO Power Technologies, the industry leader
•True double-throw operation: single solenoid design is inherently
interlocked & prevents contacts from stopping between sources
•Easy-to-read flush-mounted control and display panel provides
LED indicators for switch position and source availability
•Standard engine exerciser for weekly automatic testing with or
without load
•UL 1008 listed for Transfer Equipment and CSA C22.2 listed
•NFPA 110 for Emergency & Standby Power & the National
Electrical (NEC) Articles 700. 701 and 702
0 • ion
Fuel Tanks, UL142 listed: 50 to 5000 GAL
•UL listed. Secondary containment tank meeting UL 142 tank
requirements
•NFPA compliant. Designed to comply with the installation
standards of NFPA 30 and NFPA 37
•Emergency pressure relief vents. Meets UL requirements: ensures
adequate venting of inner and outer tank under extreme pressure
and/or emergency conditions
•Electrical stub-up area with removable end channel
•Normal vent • Inner tank emergency vent sized to UL 142 specs
•Direct reading mechanical fuel gauge • Fuel in basin switch
•Satin black paint finish
GENERAL POWER LIMITED, INC
1350 NW 78 Avenue Miami, Florida 33126
EFTA01097443
Diesel Generators 10.3200 Kw I Alternators 0.3500 Kra I TransferSwitches I Fuel Tanks I Trailers I Engine Parts I MarnelorParts
SOMO I KOHLER I BROADCROWN I HIPOMER I !GIN DEERE I CUMMINS I PERMS I MITSUDSHI I VOLVO I STAMFCRO I LEROY SOMER
M129
STANDARD FEATURES
Weatherproof / Super silent
Enclosure
▪
12 gauge electro-zinc powder coated steel for maximum corrosion resistance (Phosphatizing degreasing. Non-chromic
passivafion, Osmosis purified rinsing and High durability polyester resin thermosetting powder paint)
■ 29dB(A) Internal-mounted critical silencer and flexible exhaust connector offering maximum component life and
operator safety
■ Fade-. scratch-, and corrosion-resistant. Automotive-grade textured finish resulting in advanced corrosion and
abrasion protection as well as enhanced edge coverage and color retention
■ Up to 51mm (2in) Acoustic insulation with hydrocarbon sealing film that meets FMVSS 302 flammability classification
and repels moisture absorption
■ Interchangeable modular panel construction. Allows complete serviceability or replacement without compromising
enclosure design
■ Service access. Multi-personnel doors for easy access to generator set controller. breaker and service points
■ Externally mounted emergency stop button, Single point lifting hook and Tamper proof "securit" viewing control window
■ Cooling air discharge. Weather protective design featuring a vertical air discharge outlet grille. Redirects cooling air up
and above enclosure to reduce ambient noise
■ Cooling/combustion air intake with a horizontal air inlet. Sized for maximum cooling airflow
■ Heavy duty Polyamide plastic hinges. Dichromate galvanized bolting and Stainless steel rivets for lifetime longevity
■ Meets and exceeds NFX41002 Salt spray test, NFT30049 UV Performance test, NFT30038 Paint adhesion test and
2000/14EC Low sound directives
C •
•
E
GENErtiaL
EIR
www.genpowerusa.com
I
I
Sound Level
•
Model
dB(A)@31I
d8(A)(6)23ft
LW A
Dimensions
(in)
Weight
Fuel Tank
(Lbs)
(Gal)
GP J8OUC3
78
68
N/A
101 x 45 x 66
3505
50
GENERAL POWER LIMITED, INC
EFTA01097444
Technical Artifacts (9)
View in Artifacts BrowserEmail addresses, URLs, phone numbers, and other technical indicators extracted from this document.
Domain
www.genpowerusa.comFlight #
AS1359SWIFT/BIC
EROIRYROINNWire Ref
Transfer EquipmentWire Ref
Transfer SwitchesWire Ref
TransferSwitchesWire Ref
referenceWire Ref
transfer switchWire Ref
transfer switchesForum Discussions
This document was digitized, indexed, and cross-referenced with 1,400+ persons in the Epstein files. 100% free, ad-free, and independent.
Annotations powered by Hypothesis. Select any text on this page to annotate or highlight it.