METROPOLITAN TESTING AND BALANCING CORP.
22-14 124TH STREET
COLLEGE POINT, N.Y. 11356
OFFICE (718) 747-5545
FAX (718) 747-5547
VENTILATION TEST REPORT
EPSTEIN RESIDENCE
9 EAST 71ST STREET
NEW YORK, N.Y.
3RD FLOOR
PREPARED FOR
A.D. WINSTON SERVICECORP.
43-15 36"1 STREET
L.I.C., N.Y. 11101
JOB NO. 4582
EFTA01107704
METROPOLITAN TESTING AND
BALANCING CORP.
Date
5/21/13
Page
1
of 3
Project
9 EAST 71ST STREET
System No
MASTER BEDROOM UNIT (MB UNIT1
Flood! ON el FLOOR (SERVES 3RD)
AIR DISTRIBUTION TEST SHEET
FAN MAKE
MAGIC AIRF.
SIZE
120-BVW / BVX-A
MOTOR HP
3
RPM
1775
STATIC PRESSURE:
SUCTION
SEE SP
IN. w.O.
DISCHARGE
PROFILE.
IN WG
MOTOR AMPS
RATED
ACTUAL
LINE VOLTS
208/3/60
208
7.4/7.4/7.4 (WITH AC-3 ON )
8.1/8.1(7.9 (WITH AC-3 OFF)
9.9
FAN RPM
REQUIRED
N.A.
ACTUAL
LW (Willi AL-3 UN)
1283 (WMI AC-3 OFF)
2192 (WITH AC-3 ON)
2783 (WITH AC-3 OFF)
SYSTEM CFM
2100
Terminal
Number
Terminal
Factor
Design
Final
Static Pressure (in.w.g.)
Type
Size
FPM
CFM
FPM
CFM
AC-3 ON
Fr-MB
PPLY
SU
MAIN
DUCT 26X15
2.7
777
2100
812
2192
+2.0
AC-3 OFF
PT-MB
SUPPLY
MAIN
DUCT 26X15
2.7
777
2100
1031
2783
+3.0
AC-I OFF*
ACCESS
DOOR
IDOWNSTPJAI
REMOVED
PT-MB
SUPPLY
MAIN
DUCT 26X15
2.7
777
2100
1337
3610
+1.3
Remarks:
EFTA01107705
METROPOLITAN TESTING AND
BALANCING CORP.
Date
5/21/11
Page
2
of
3
Project
9 EAST 71ST STREET
System No
MASTER BEDROOM UNIT (MB UNIT)
AIR DISTRIBUTION TEST SHEET
Floor!!
3RD
Terminal
Number
Room
Number
Terminal
Factor
_
Design
Final
Remarks
Type
Size
FPM
CFM
FPM
CFM
WITH
AC-3 ON
1
SG
42X2
NA
291
2
SG
42X2
NA
263
3
SG
38X2
NA
299
4
FG
5'0"
NA
740
5
FG
5'0"
NA
745
TOTAL
2100
2338
WITH
AC-3 OFF
1
SG
42X2
NA
349
2
SG
42X2
NA
322
3
SG
38X2
NA
349
4
FG
5'0"
NA
900
5
FG
Sr
NA
890
TOTAL
2100
2810
Remarks:
EFTA01107706
METROPOLITAN TESTING AND
BALANCING CORP.
Date
5/21/13
Page
of 1
'roject Name
9 EAST 71ST STREET
STATIC PRESSURE PROFILE
o.a. dampers
I
mix. box
•~7•
g
UNIT
a
b
c
d
e
f
g
h
j
•M5 UNIT
-.88
X
X
X
-1.0
X
X
X
+2.0
••MB UNIT
-.30
X
X
X
-.46
X
X
X
+3.0
:marks *READINGS WITH AC-3 ON
**READINGS WITH AC-3 OFF
EFTA01107707
16x8 TOILET EXH.
UP TO EF-8
550 CFM
24x10
x6
28x10
24x5 DN.
16x6 UP
12x4 TAP
140 CFM EA
TYP. FOR 2
12-Wx6-Hx3.-
A.L. PLENUM
TYPICAL FOR 3,- I
-12x6
16. 1Vx6-Hx4.-41.
A.L. PLENUM
SUPPLY GRILLES 1
170 CFM
10x6
6
\ 18'Wx10-1-ix5.-0"L
16x10 R.A. OPNG.
ABOVE CLG.
500
10x6 UP
250 CFM UP TO
GUEST SITTING RM
-16x10 R.A. OPNG.
ABOVE CLG. 500 CFM
28x10 R.A. OPGN.
ABOVE CLG. 670 CFM
A.L.PLENUM
TYPICAL FOR 2
12%8' TAP
W/ C.O.D. - 325
TYPICAL FOR 2
18-Wx8"Hx4.-0'L
A.L. PLENUM©
14-x6-
TAp
W/ CO D. - 290 CFM
EFTA01107708
Technical Artifacts (3)
View in Artifacts BrowserEmail addresses, URLs, phone numbers, and other technical indicators extracted from this document.
Fax
FAX (718) 747-5547Phone
(718) 747-5545Phone
(718) 747-5547Forum Discussions
This document was digitized, indexed, and cross-referenced with 1,400+ persons in the Epstein files. 100% free, ad-free, and independent.
Annotations powered by Hypothesis. Select any text on this page to annotate or highlight it.