SIEMENS
Field Panel Web Server
weenier..
The Field Panel Web Server provides a Web-based
Graphical User Interface (GUI) compatible with
BACnet® networks. Using the Web Server, the
facility operator can easily monitor and control the
APOGEE® Building Automation System through an
intuitive Web-based user interface.
Description
The Web Server allows system-wide access through
a single log-in. Web pages are populated with data
from any BACnet IP-enabled PXC controller and
associated Field Level Network (FLN) devices.
The Web Server runs on standard PXC controllers,
eliminating the need for separate high-cost 'web
appliances' or dedicated web servers. This means
that the same APOGEE field panel can serve as an
automation controller, with full building automation
and I/O features, and provide the user with system
information and access via a web browser.
The use of web services for communication ensures
that any web browser with Adobe® Flash® is able to
access the Field Panel Web Server.
A Web Server-enabled controller can accommodate
an unlimited number of user accounts and
simultaneous users.
Technical Specification Sheet
Rev. 1, December 2010
Security
The Web Server is secured from IT security threats
by means of password-protected operator access.
The Web Server uses password encryption. User
accounts can be individually configured for
customized access privileges. Operator sessions
may be configured to automatically log off during
periods of user inactivity.
The Field Panel Web Server is compatible with
standard IT security policies and tools established
within a particular facility, and can be protected
within that environment.
Browser/Client Requirements
• Session cookies enabled
• Adobe® Flash® Player Plug-in 10.1 or later
installed
Features
The Field Panel Web Server encompasses the
following operator applications:
• Graphical Monitoring and Control
• Network Layout
• System Status Bar
• Alarm Status and Acknowledgement
• Point Commanding
• Scheduling
• Reporting
• Graphical Trend Display
• User Interface Customization
• Online Database Editing
Document No. 149-1000
Page 1 of 6
EFTA_R1_00017740
EFTA01735386
Graphics
INIECIWN
--11
=MI
FAIT a-4;
. • I
• Customized system graphics
•
Live animation of equipment
•
Real-time point values and status updates
• Link to system schedule and% or historical
trend
Network Layout
C, • v
• e:
et
•!,•••.t,
Ahul
• IT. S•• A111111 OGRAM:TOTKW
• IL Sie bl.t..1 AMU ChoNV
• L See
BLDG1 AHUI worn/
BLDG! AHUI PAH
DLOG1 AHUI PAT
• dr., Graphics
• 71 MST•TUE.02
• ES12.I3TECOI
• I_ Ssernens13 00131
•
Local
**Trends
Schedules
•
▪ Gre•Pmcs
• f.PITUNI
513.A1EC03
..S13.ATECO4
•
513.TEC01
. 1 S13.TEC02
U
• View network layout
• View BACNET MSITP and P1 FLNs
• Navigate to other Web-enabled panels
• Search database for individual points
System Status Bar
•
0 •
•
• Visual indication of new alarms and
unacknowledged alarms
• Visual indication of out of service, faults, and
failed devices
Alarm Status and Acknowledgement
•Los
Repo..
• Ability to view, filter, and acknowledge system
alarms from a single page
Point Commanding
• Change point values
• Place points "Out of Service"
• Command BACnet MS/TP and P1 FLN points
Scheduling
▪ .••••••
>0.10
1611
•
•
•
••• 0111.0.
• View schedules in a daily, weekly, or monthly
view
• Add and delete schedules
• Create exceptions for existing schedules
Page 2 of 6
Siemens Industry, Inc.
EFTA_R1_00017741
EFTA01735387
Reporting
User Interface Customization
• Generate Point Log Report with multiple filters
Graphical Trend Display
• Ability to view one
display
• Ability to view raw
CSV file
or more trends on a single
data values and export to
• Print trend graph to network printers
FM Sae
10
il
l
Isnstage
English
Data Rene:hate.
w"
Altai coat
ulitek mem coot
OC5Cdor
D•vre Fare Cool •
Re:et to Default
FAA CVC,
• Custom Welcome Page
• User interface translatable to any browser-
supported language
• Ability to customize font sizes and display
colors
Online Database Editing
• Database Configuration
o
Add/ Modify/ Delete points
o
Add/ Modify! Delete trend definitions
o
Add/ Modify/ Delete Event Enrollment
Objects
o
Add/ Modify/ Delete Notification Class
Objects
• Schedule
o
Add/ Modify! Delete schedules
o
Add/ Modify/ Delete Command Objects
o
Add! Modify! Delete Calendar Objects
• Custom Program Editor
o
Add/ Modify/ Delete programs
o
View and clear program trace bits
o
View disabled, unresolved, and
comment lines
•
FLN Devices
o
Add/ Modify/ Delete FLN Devices
o
Set and Release TEC Initial values
• User Account
o
Add! Modify/ Delete user accounts
o
Change user passwords
Siemens Industry. Inc
Page 3 of 6
EFTA_R1_00017742
EFTA01735388
Graphics Creation and Editing
• Graphics configuration tool allows remote\
offline creation, modification, and deletion of
graphics.
• Library of predefined graphic backgrounds
• Ability to import standard image formats (.png,
.jpg, and, .gif)
Page 4 of 6
Siemens Industry, Inc.
EFTA_R1_00017743
EFTA01735389
Field Panel Web Server
At least one PXC Compact 36 or PXC Modular
controller with firmware 3.2.2 is required on each
WEB Browser
PXC 36 with
Web Services
Enabled
I.
BACnet MS/TP P1 FLN
Pc 16/24
with Web
Services
Enabled
network. Data from every controller that has the Web
Services license enabled will be automatically
displayed.
Li
WEB Browser
PXC Modular
a
with Web
•
Services
Enabled
BACnet MS/TP/
P1 FLN
±
I
=MI
Inlij
Figure 1 Field Panel Web Server
Siemens Industry. Inc
Page 5 of 6
EFTA_R1_00017744
EFTA01735390
Specifications
Supported BACnet Field Panels
BACnet IP-based PXC Modular
BACnet IP-based PXC Compact 16/24/36
Note: At least one PXC Modular or PXC 36 is required
on each network
Web Browser
Internet Explorer 6.0 or later, or Firefox 3.6 or later
with Adobe Flash Player Plug-in 10.1 or later is
supported
Any browser capable of running and displaying Adobe
Flash Player Plug-in 10.1 or later is compatible.
Ordering Information
Description
Part Number
SSN
Field Panel Web Services License
LSM-FPWEB
P55801-Y104
Field Panel Graphic Editor
571-214
555801-Y139
Information in this document is based on specifications believed coned at the time of publication. The right is reserved to make changes as design
improvements are introduced. APOGEE is a registered trademark of Siemens Industry. Inc.
2010 Siemens Industry. Inc.
Siemens Industry. Inc.
1000 Deerfield Parkway
Buffalo Grove, IL 60089-4513
Country of Origin: US
Page 6 of 6
EFTA_R1_00017745